Plan Review Notes
Plan Review Notes For Permit 20020015
Permit Number 20020015
Review Stop E
Sequence Number 1
Notes
Date Text
2020-03-01 11:56:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 BE ADVISED THAT PLAN SUBMISSION HAS MORE THAN 25 SHEETS
 AND IS REQUIRED TO BE A DIGITAL SUBMISSION. ALL FUTURE
 SUBMISSION SHALL BE IN DIGITAL FORMAT. WPB FBC 107.1
  
 1. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. THE
 RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL OR
 PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN
 COUNTERTOP, LOCATED ON THE COUNTERTOP, OR INSTALLED ON
 THE SIDE OR FACE OF THE BASIN CABINET. THIS IS NOT
 SHOWN FOR ALL BATHROOM BASINS. PROVIDE CORRECTION. NEC
 210.11(C)(3), 210.52(D); FBC RE E3901.6
 2. NOTE 7 OF ELECTRICAL WIRING NOTES STATES THE 2011
 NEC AS BASIS OF DESIGN. THIS IS NOT THE CURRENT CODE.
 PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES
 ABOVE)
 3. NOTES UNDER PANEL SCHEDULES (2 LOCATIONS) STATE THAT
 LIGHTING IN CLOSETS SHALL COMPLY WITH NEC 410.8 . THIS
 CODE SECTION DOES NOT APPLY TO CLOSET LIGHTING. PROVIDE
 CORRECTION OR NOTE OR COMPLIANCE. NEC 410.16; FBC RE
 E4003.12
 4. NOTES UNDER PANEL SCHEDULES (2 LOCATIONS) STATE THAT
 RECEPTACLES SHALL BE TAMPER RESISTANT PER NEC 406.11.
 THIS CODE SECTION DOES NOT APPLY TO TAMPER RESISTANT
 RECEPTACLES. PROVIDE CORRECTION. NEC 406.12; FBC RE
 E4002.14
 5. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4
 6. ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS
 SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9
 7. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR RECEPTACLE OUTLETS. RECEPTACLES SHALL
 BE INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE OUTLET. THE WALL SPACING
 REQUIREMENTS FOR KITCHEN COUNTER SPACE STATE THAT
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 24 INCHES MEASURED
 HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT SPACE.
 THE PLAN PROVIDED DOES NOT MEET THIS CODE IN SOME
 AREAS. PROVIDE CORRECTION. NEC 210.52(C)(1); FBC RE
 E3901
 8.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  