| Date |
Text |
| 2020-06-10 08:01:48 | PLUMBING PROVISOS: |
| | |
| | 1) PLUMBING APPROVAL IS FOR UNDERSLAB PLUMBING ONLY. |
| | |
| | SEPARATE PERMITS ARE REQUIRED FOR THE GREASE |
| | INTERCEPTORS, BACKFLOW PREVENTER, GAS PIPING, FIRE |
| | LINE, AND FOR THE MAIN BUILDING PLUMBING SYSTEMS. |
| | |
| | 2) A REVISION TO THE FOUNDATION PERMIT IS REQUIRED TO |
| | PROVIDE THE REQUIRED ACCESSIBLE DRINKING FOUNTAINS IN |
| | THE 1ST FLOOR BUSINESS OCCUPANCY. |
| | NO PLUMBING INSPECTIONS WILL BE PERFORMED UNTIL THE |
| | REVISON IS SUBMITTED AND APPROVED. |
| | |
| | CCOLE- 6/10/2020 |
| 2020-06-08 12:58:42 | |
| | 3RD REVIEW FBC-2017 PLUMBING |
| | PERMIT #20020004 |
| | 6/8/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE REQUIRED DRINKING FOUNTAINS IN THE BUSINESS |
| | OCCUPANCY ON THE 1ST FLOOR WERE NOT PROVIDED. A WATER |
| | COOLER CANNOT REPLACE THE REQUIRED ACCESSIBLE DRINKING |
| | FOUNTAINS PER SECTION 211.2 AND 211.3 FBC ACC. |
| | |
| | 211.2 MINIMUM NUMBER. |
| | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| | FOUNTAINS. |
| | |
| | PLEASE SEE SECTIONS 602.1- 602.7 FBC ACC AND REVISE THE |
| | DRAWINGS. |
| | |
| | 2) COMMENT #9 PRINTED BELOW IS PASSED WITH PROVISO FOR |
| | A SEPARATE PERMIT TO BE OBTAINED FOR THE GREASE |
| | INTERCEPTORS PRIOR TO INSTALLATION BELOW THE FOUNDATION |
| | SLAB. |
| | 9) P1.00B GREASE INTERCEPTORS: REFER TO SECTION 8.3.1 |
| | PDI G101 AND INDICATE IN THE NOTE THE 1/4" PER FT. |
| | SLOPES OF THE GREASE WASTE PIPES. PLEASE NOTE THAT IN |
| | ACCORDANCE WITH THIS SECTION, THE INTERCEPTOR MUST BE |
| | SIZED AT A MINIMUM FLOW RATE OF 75 GPM @ 2 MINUTES |
| | DRAIN TIME. A) SHOW THE LOCATIONS OF STUB UPS FOR THE |
| | INTERCEPTOR VENTS, SAMPLE PORTS, CLEANOUTS, AND AIR |
| | INTAKES- SECTION 107.2.1. B) SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE SELECTED INTERCEPTORS- SEE |
| | SECTION 1003.3.4 FBC P FOR ACCEPTABLE APPROVAL |
| | STANDARDS. C) PROVIDE AN ENLARGED INSTALLATION DETAIL |
| | ON THE PLANS. PLEASE NOTE THAT THE INTERCEPTORS SHALL |
| | BE INSTALLED PER MANUFACTURER'S GUIDELINES AND SHALL BE |
| | APPROVED FOR INSTALLATION BY THE CITY OF WEST PALM |
| | BEACH UTILITIES DEPARTMENT. PLEASE CONTACT CHIEF |
| | PLUMBING INSPECTOR TIMOTHY LARGE FOR MORE INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBINGPLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |