Plan Review Notes
Plan Review Notes For Permit 20020004
Permit Number 20020004
Review Stop P
Sequence Number 3
Notes
Date Text
2020-06-10 08:01:48PLUMBING PROVISOS:
  
 1) PLUMBING APPROVAL IS FOR UNDERSLAB PLUMBING ONLY.
  
 SEPARATE PERMITS ARE REQUIRED FOR THE GREASE
 INTERCEPTORS, BACKFLOW PREVENTER, GAS PIPING, FIRE
 LINE, AND FOR THE MAIN BUILDING PLUMBING SYSTEMS.
  
 2) A REVISION TO THE FOUNDATION PERMIT IS REQUIRED TO
 PROVIDE THE REQUIRED ACCESSIBLE DRINKING FOUNTAINS IN
 THE 1ST FLOOR BUSINESS OCCUPANCY.
 NO PLUMBING INSPECTIONS WILL BE PERFORMED UNTIL THE
 REVISON IS SUBMITTED AND APPROVED.
  
 CCOLE- 6/10/2020
2020-06-08 12:58:42 
 3RD REVIEW FBC-2017 PLUMBING
 PERMIT #20020004
 6/8/20
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REQUIRED DRINKING FOUNTAINS IN THE BUSINESS
 OCCUPANCY ON THE 1ST FLOOR WERE NOT PROVIDED. A WATER
 COOLER CANNOT REPLACE THE REQUIRED ACCESSIBLE DRINKING
 FOUNTAINS PER SECTION 211.2 AND 211.3 FBC ACC.
  
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 PLEASE SEE SECTIONS 602.1- 602.7 FBC ACC AND REVISE THE
 DRAWINGS.
  
 2) COMMENT #9 PRINTED BELOW IS PASSED WITH PROVISO FOR
 A SEPARATE PERMIT TO BE OBTAINED FOR THE GREASE
 INTERCEPTORS PRIOR TO INSTALLATION BELOW THE FOUNDATION
 SLAB.
 9) P1.00B GREASE INTERCEPTORS: REFER TO SECTION 8.3.1
 PDI G101 AND INDICATE IN THE NOTE THE 1/4" PER FT.
 SLOPES OF THE GREASE WASTE PIPES. PLEASE NOTE THAT IN
 ACCORDANCE WITH THIS SECTION, THE INTERCEPTOR MUST BE
 SIZED AT A MINIMUM FLOW RATE OF 75 GPM @ 2 MINUTES
 DRAIN TIME. A) SHOW THE LOCATIONS OF STUB UPS FOR THE
 INTERCEPTOR VENTS, SAMPLE PORTS, CLEANOUTS, AND AIR
 INTAKES- SECTION 107.2.1. B) SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE SELECTED INTERCEPTORS- SEE
 SECTION 1003.3.4 FBC P FOR ACCEPTABLE APPROVAL
 STANDARDS. C) PROVIDE AN ENLARGED INSTALLATION DETAIL
 ON THE PLANS. PLEASE NOTE THAT THE INTERCEPTORS SHALL
 BE INSTALLED PER MANUFACTURER'S GUIDELINES AND SHALL BE
 APPROVED FOR INSTALLATION BY THE CITY OF WEST PALM
 BEACH UTILITIES DEPARTMENT. PLEASE CONTACT CHIEF
 PLUMBING INSPECTOR TIMOTHY LARGE FOR MORE INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBINGPLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  