| 2020-04-21 12:30:12 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT #20020004 |
| | 4/21/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | PLEASE NOTE THAT THERE ARE NO SITE OR CIVIL PLANS |
| | INCLUDED IN THE PLAN SET TO INDICATE LOCATIONS OF |
| | UTILITY ENTRANCES AND MAIN SANITARY AND STORM DRAINAGE |
| | CONNECTIONS TO THE CITY SERVICES. |
| | |
| | 1) PLEASE CHOOSE A PLAN SHEET RELATIVE TO THE PLUMBING |
| | PORTION OF THE PROPOSED PROJECT AND PROVIDE A DETAILED |
| | SCOPE OF WORK OUTLINE INDICATING THE LIMITATION OF |
| | PLUMBING WORK TO BE PERFORMED UNDER THIS FOUNDATION |
| | ONLY PERMIT. THIS CAN ALSO BE PROVIDED AS A DOCUMENT- |
| | SECTION 107.2.1 WPB. INDICATE WHICH SHEETS ARE TO BE |
| | INCLUDED THE SCOPE AND MARK ALL OTHERS AS "FOR |
| | REFERENCE ONLY". |
| | |
| | 2) SHEETS CD-01, A1.01. A1.01A: THE OCCUPANT LOAD |
| | CALCULATIONS ON THE PLANS FOR THE BUSINESS AREAS DO NOT |
| | INCLUDE THE SEATING CALCULATIONS FOR THE COFFEE BAR- |
| | SEE MAIN PERMIT PLANS UNDER #20011267. THIS AREA IS |
| | CALCULATED AT 15 NET PERSONS PER SQ. FT.- TABLE |
| | 1004.1.2 FBC B. PLEASE CORRECT THE CALCULATIONS- |
| | SECTION 107.2.1 WPB. |
| | |
| | 3) SHEETS CD-01, A1.01, A1.0A, P1.00A: REFER TO TABLE |
| | 403.3 FBC P AND PROVIDE A SCHEDULE ON THE PLAN SHOWING |
| | THE MINIMUM REQUIRED PLUMBING FIXTURES REQUIRED AND THE |
| | FIXTURES PROVIDED. CHOOSE ANY RELEVANT SHEET TO PROVIDE |
| | THE SCHEDULE. PLEASE NOTE THAT SEPARATE TOILET |
| | FACILITIES FOR MALE AND FEMALE USE ARE REQUIRED IN |
| | BUSINESS OCCUPANCIES, AND A DRINKING FOUNTAIN AND A |
| | SERVICE SINK. REVISE THE DRAWINGS TO SHOW THE LOCATIONS |
| | OF THE REQUIRED FIXTURES AND PLUMBING PIPING |
| | REQUIREMENTS- SECTION 107.2.1 WPB. |
| | |
| | 4) SHEET CD-03: THE PLUMBING FIXTURES REQUIRED IN THE |
| | BUSINESS AREA ARE DESIGNATED FOR PUBLIC USE AND SHALL |
| | BE INSTALLED IN COMPLIANCE WITH THE FLORIDA |
| | ACCESSIBILITY CODE SIXTH EDITION 2017- PLEASE CORRECT |
| | THE REFERENCE TO THE 2010 ADA. ALSO CORRECT THE |
| | REFERENCE TO FHA TO INCLUDE "PUBLIC AND COMMON USE |
| | FACILITIES". A) PLEASE REPLACE ALL TYPICAL FIGURES |
| | SHOWN ON THE PLAN FOR PUBLIC USE WITH THE TYPICAL |
| | FIGURES SHOWN IN THE FBC ACC. B) PROVIDE TYPICAL |
| | FIGURES RELEVANT TO FAIR HOUSING COMPLIANCE FROM THE |
| | FAIR HOUSING ACT DESIGN MANUAL. |
| | |
| | 5) PROVIDE PROJECT SPECIFIC ENLARGED AND DIMENSIONED |
| | DRAWINGS FOR THE PUBLIC AND COMMON USE TOILET ROOMS ON |
| | THE 1ST FLOOR THAT INDICATE ALL ACCESSIBLE FIXTURE AND |
| | ACCESSORY INSTALLATION AND CLEARANCE REQUIREMENTS IN |
| | ACCORDANCE WITH CHAPTER 6 OF THE FBC ACC. PLEASE |
| | INCLUDE DIMENSIONED ELEVATION VIEWS AND DIAGRAMS |
| | SHOWING COMPLIANCE. PLEASE NOTE THAT COMPLETE |
| | ACCESSIBILITY DETAILS FOR THE 1ST FLOOR INCLUDING THE |
| | COFFEE BAR MAY BE DEFERRED AT THIS TIME, HOWEVER IT IS |
| | NOT CLEAR AS THE EXTENT OF WORK TO BE COVERED UNDER |
| | THIS FOUNDATION PERMIT- SEE COMMENT #1 ABOVE. |
| | |
| | 6) P1.00A & P100B: INDICATE PIPE MATERIALS FOR THE |
| | SANITARY SEWER, DWV, GREASE WASTE LINE, AND WATER |
| | SERVICE- TABLES 605.3, 702.1, 702.2, 702.3 FBC P. |
| | PROVIDE A SUBMITTAL PACKAGE FOR ALL MATERIALS |
| | SPECIFIED- SECTION 107.2.1 WPB. |
| | |
| | 7) P1.00A: INDICATE HOW THE MAIN 6" WATER LINE WILL BE |
| | PROTECTED FROM CORROSION AND STRESS AND STRAIN- |
| | SECTIONS 305.1, 305.1.1 AND 305.2 FBC P. PROVIDE |
| | SLEEVING DETAILS WHERE REQUIRED. |
| | |
| | 8) P1.00A & B: PROVIDE MANHOLE INSTALLATION DETAILS AND |
| | SHOW THEIR LOCATIONS ON THE MAIN 1ST FLOOR PLAN (SHEET |
| | A1.01). INDICATE THEY WILL BE EQUIPPED WITH GAS-TIGHT |
| | COVERS- SECTION 708.1.7 FBC P. |
| | |
| | 9) P1.00B GREASE INTERCEPTORS: REFER TO SECTION 8.3.1 |
| | PDI G101 AND INDICATE IN THE NOTE THE 1/4" PER FT. |
| | SLOPES OF THE GREASE WASTE PIPES. PLEASE NOTE THAT IN |
| | ACCORDANCE WITH THIS SECTION, THE INTERCEPTOR MUST BE |
| | SIZED AT A MINIMUM FLOW RATE OF 75 GPM @ 2 MINUTES |
| | DRAIN TIME. A) SHOW THE LOCATIONS OF STUB UPS FOR THE |
| | INTERCEPTOR VENTS, SAMPLE PORTS, CLEANOUTS, AND AIR |
| | INTAKES- SECTION 107.2.1. B) SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE SELECTED INTERCEPTORS- SEE |
| | SECTION 1003.3.4 FBC P FOR ACCEPTABLE APPROVAL |
| | STANDARDS. C) PROVIDE AN ENLARGED INSTALLATION DETAIL |
| | ON THE PLANS. PLEASE NOTE THAT THE INTERCEPTORS SHALL |
| | BE INSTALLED PER MANUFACTURER'S GUIDELINES AND SHALL BE |
| | APPROVED FOR INSTALLATION BY THE CITY OF WEST PALM |
| | BEACH UTILITIES DEPARTMENT. PLEASE CONTACT CHIEF |
| | PLUMBING INSPECTOR TIMOTHY LARGE FOR MORE INFORMATION. |
| | |
| | 10) P1.00 A & B, & P6.01: INDICATE HOW THE WATER |
| | SERVICE LINE AND BOOSTER PUMP WERE SIZED. PROVIDE |
| | CALCULATIONS- SECTION 604.1 FBC P. |
| | |
| | 11) P1.00 A & B, & P6.02: PROVIDE DRAINAGE AND SEWER |
| | SYSTEM SIZING CALCULATIONS- TABLE 710.1(1) FBC P. |
| | |
| | 12) P1.00 A & B: PROVIDE STORM DRAINAGE CALCULATIONS IN |
| | ACCORDANCE WITH SECTION 1106.1 & TABLES 1106.2 & 1106.3 |
| | FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | CCOLE |
| | |
| | |