| 2020-03-02 18:27:51 | PLUMBING 1ST REVIEW**DENIED**2002004 | | | | | | 1) PROVIDE FLOOR PLAN SHOWING ALL 1ST FLOOR ROOM | | | DIMENSIONS. FBC 107.3.5 | | | 2) PROVIDE OCCUPANCY AND OCCUPANT LOAD FOR THE 1ST | | | FLOOR. I WAS ONLY ABLE TO LOCATE 1 TOILET ROOM. SHOW | | | THE REQUIRED PLUMBING FIXTURE PER FBC-PLB TABLE 403.1 | | | 3) PROVIDE HOW YOU SIZED THE INTERCEPTOR AND BY WHAT | | | MEANS (PDI G101 OR FAC 64E-6). FBC-PLB 1003.3.4 | | | 4) PROVIDE A PLUMBING SANITARY AND WATER ISOMETRIC | | | DRAWING. FBC 107.3.5 | | | 5) PROVIDE ALL ACCESSIBILITY DETAILS FOR THE 1ST FLOOR. | | | FBC 107.3.5 | | | | | | | | | TIM HUNT | | | PLUMBING PLAN REVIEW | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | 561-248-2703 | | | [email protected] | | | | | | |
|