Plan Review Notes
Plan Review Notes For Permit 20020004
Permit Number 20020004
Review Stop B
Sequence Number 1
Notes
Date Text
2020-03-04 08:33:56PLAN REVIEW COMMENTS
 FOUNDATION ONLY PERMIT
 625 S. OLIVE AVE.
 PERMIT #20020004
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. PER
 CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND CITY
 OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, ART
 IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST. PER CITY OF WEST PALM BEACH
 CODE OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES,
 SECTION 78-122, RENOVATION AND NEW CONSTRUCTION
 PROJECTS ARE ASSESSED CUMULATIVELY, SO THE ART
 ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE PROJECTS.
 FOR INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR AT
 822-1515 OR E-MAIL: [email protected]
  
 2) THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE CURRENT ( OCTOBER
 2018 ) CITY GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING THRESHOLD/SPECIAL INSPECTORS AND RESIDENT
 INSPECTORS.
  
 3) THE GEOTECHNICAL REPORT THAT WAS SUBMITTED INDICATES
 THAT THE RECOMMENDED VIBRO COMPACTION SOIL PREPARATION
 WILL PRODUCE A SOIL BEARING VALUE OF UP TO 6,000 PSF.
 NOTE 3A ON SHEET S200 OF THE PLANS STATES THAT THE
 BUILDING DESIGN REQUIRES A SOIL BEARING CAPACITY OF
 8,000 PSF. PLEASE INDICATE HOW THIS WILL BE ADDRESSED.
 FBC 1801.2
  
 4) SPECIFY HOW COMPLIANCE WITH FBC CHAPTER 33
 SAFEGUARDS DURING CONSTRUCTION FOR THE FOUNDATION
 PERMIT WILL BE MET.
  
 5) FBC 3002.4 REQUIRES ANY BUILDING THAT IS MORE THAN
 THREE STORIES HIGH OR IN WHICH THE VERTICAL DISTANCE
 BETWEEN THE BOTTOM TERMINAL LANDING AND THE TOP
 TERMINAL LANDING EXCEEDS 25 FEET TO BE CONSTRUCTED TO
 CONTAIN AT LEAST ONE PASSENGER ELEVATOR THAT IS
 OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE DEPARTMENT
 ACCESS TO ALL FLOORS. THE ELEVATOR CAR SHALL BE OF A
 SIZE AND ARRANGEMENT TO ACCOMMODATE AN AMBULANCE
 STRETCHER 24 INCHES BY 76 INCHES WITH NOT LESS THAN
 5-INCH RADIUS CORNERS, IN THE HORIZONTAL, OPEN POSITION
 AND SHALL BE IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR
 EMERENCY MEDICAL SERVICES (STAR OF LIFE).
  
 6) THE TRASH CHUTE DISCHARGE ROOM IS REQUIRED TO BE
 SEPARATED BY FIRE BARRIERS WITH A FIRE-RESISTANCE
 RATING NOT LESS THAN THE REQUIRED FIRE RATING OF THE
 SHAFT ENCLOSURE. FBC 713.13.4
  
 7) THE EXIT PASSAGEWAY AT STAIR 01 IS INCORRECTLY
 LABELED AS AN EXIT ACCESS CORRIDOR. AN EXIT PASSAGEWAY
 IS AN EXTENSION OF THE ENCLOSED INTERIOR EXIT STAIRWAY
 AND HAS REQUIREMENTS SIMILAR TO THE STAIRWAY. PLEASE
 CORRECT. SEE FBC 1023.1 AND 1024.
  
 8) PLEASE REVIEW THE ELEVATIONS AROUND THE EXTERIOR OF
 THE BUILDING AND COMPARE THEM WITH THE FLOOR ELEVATION
 (11.97') OF THE BUILDING TO MAKE SURE THAT THE EXITS
 DISCHARGE AT GRADE AND THE ELEVATIONS AND SLOPES OF
 LANDINGS AND WALK WAYS WILL MEET THE RUNNING SLOPE AND
 CROSS SLOPE REQUIREMENTS OF THE FLORIDA ACCESSIBILITY
 CODE SECTION 403.
  
 9) THIS FOUNDATION PERMIT IS BEING APPLIED FOR UNDER
 SECTION 105.13 OF THE CITY OF WEST PALM BEACH
 AMENDMENTS TO THE 2017 FBC. THE HOLDER OF THIS
 FOUNDATION PERMIT SHALL PROCEED AT THE HOLDER'S OWN
 RISK WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE
 THAT A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED.
  
 10) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  