Plan Review Notes
Plan Review Notes For Permit 20011298
Permit Number 20011298
Review Stop G
Sequence Number 2
Notes
Date Text
2020-04-10 11:57:2704/10/20 2ND PLUMBING/GAS REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SECOND REQUEST, THE UNIT SPECIFIED REQUIRES A
 REGULATOR AS NOTED ON PAGE 3 OF MANUAL A 10.5" W.C.,
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE PRESSURE
 REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER
 THE 2017 FBC FUEL GAS RES. SEC. G2421.1.
 2. A SUB ELECTRICAL PERMIT WILL BE REQUIRED FOR THE
 SOURCE OF IGNITION, WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 3. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. THE TOTAL JOB COST SEEMS LOW. THE VALUE MUST INCLUDE
 THE COST OF ALL EQUIPMENT INCLUDING TANKLESS AND STOVE.
 PROVIDE BONA FIDE SIGNED CONTRACT PER THE WPB
 AMENDMENTS TO THE FBC 109.3
  
 5. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2017 FBC RES. SEC. G2413.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  