| 2020-02-04 18:38:39 | 02/04/20 1ST PLUMBING/GAS REVIEW **DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE SYSTEM IN 1996 SHOWS A WATER HEATER INSTALLED |
| | WITH 40 BTU'S AND NOW THE ONE YOU ARE SUBMITTING IS |
| | HIGHER IN BTU'S. A FULL EVALUATION OF THE SYSTEM WILL |
| | BE REQUIRED. PLEASE SUBMIT A GAS RISER DIAGRAM SIZE OF |
| | UNIT AND UPDATED ISOMETRIC PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. |
| | 2. A SUB ELECTRICAL PERMIT WILL BE REQUIRED FOR THE |
| | SOURCE OF IGNITION, WPB AMENDMENTS TO THE FBC SEC. |
| | 105.1. |
| | 3. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | 4. THE PHYSICAL ADDRESS OF THE PROJECT MUST BE ON PLANS |
| | IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP CODE PER |
| | THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | 5. IF THIS UNIT HAS 199 BTU'S AND IT MAY REQUIRE A |
| | REGULATOR, IF THE SYSTEM IS AT 12" WC AND AT WHICH THE |
| | UNIT CALL FOR 10.5? A REGULATOR IS REQUIRED, SUBMIT |
| | MANUFACTURER?S SPECIFICATIONS FOR THE PRESSURE |
| | REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE |
| | BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION. |
| | 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC FUEL GAS RES. |
| | SEC. G2421.1. |
| | 6. PLEASE SUBMIT MANUFACTURES SPECIFICATION AND |
| | INSTALLATION INSTRUCTION VERIFY COMPLIANCE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 105.1. |
| | 7. THE CITY MAY SUPPLY THE ISOMETRIC FROM 1996 BUT |
| | THERE MAY BE A COST TO THE CUSTOMER PLEASE CALL 561 |
| | 805-6700. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6720 |