| Date |
Text |
| 2020-05-05 11:22:20 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT #20011288 |
| | 5/5/20 |
| | |
| | CODES IN EFFECT. |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P1 & P2: PROVIDE A CLEANOUT AT THE POINT |
| | WHERE THE GUEST HOUSE BUILDING DRAIN EXITS THE |
| | STRUCTURE AND CONNECTS TO THE SEWER PIPE- SECTION |
| | P3005.2.3 FBC RES. |
| | |
| | 2) P1 & P2: PROVIDE A VENT FOR THE GUEST ROOM BATH |
| | GROUP. IT APPEARS BY THE DRAWING THAT A VENT STACK |
| | CONNECTED TO THE LAV. DRAIN WOULD BE A GOOD LOCATION- |
| | SEE SECTION P3108.1 HORIZONTAL WET VENT- FBC RES. |
| | |
| | 3) P2: PLEASE SHOW THE WYE FITTING DRAIN CONNECTIONS |
| | POSITIONED IN THE DIRECTION OF FLOW- SECTION P2608.1 |
| | FBC RES. |
| | |
| | 4) P2: SHOW THE REQUIRED 2" TRAP AND 3" BRANCH DRAIN |
| | FOR THE WASHING MACHINE- P3201.7 FBC RES & 406.2 FBC P. |
| | |
| | 5) P1 & P2: SHOW THE DISHWASHER LOCATIONS AND DRAIN |
| | CONNECTION- P2717.2 FBC RES. |
| | |
| | 6) P1 & P2: THE SHOWER PANS SHALL COMPLY WITH SECTION |
| | P2709.2 FBC RES, AND THE SHOWER VALVES SHALL COMPLY |
| | WITH SECTION P2708.2 FBC RES. PLEASE PLACE NOTES AND/OR |
| | DETAILS ON THE PLAN TO SHOW COMPLIANCE. |
| | |
| | 7) INSTALLATION OF AN RPZ BACKFLOW PREVENTER IS |
| | REQUIRED FOR THE WATER SERVICE TO THE TWO SEPARATE |
| | DWELLINGS ON THE SAME LOT. A FL. LICENSED PLUMBING |
| | CONTRACTOR CERTIFIED FOR INSTALLATION SHALL SUBMIT A |
| | SEPARATE PERMIT APPLICATION TO BE APPROVED BY THE WPB |
| | BUILDING AND UTILITIES DEPARTMENTS. |
| | |
| | 8) P1: ACCORDING TO THE ENERGY COMPLIANCE SUBMITTAL AND |
| | THE ELECTRIC PANEL SCHEDULES, GAS-FIRED TANKLESS WATER |
| | HEATERS ARE TO BE INSTALLED FOR EACH BUILDING. |
| | A) SHOW THE LOCATIONS OF THE UNITS ON THE PLAN ALONG |
| | WITH ANY OTHER GAS-FIRED APPLIANCES EITHER NEW OR |
| | EXISTING- SECTION 107.2.1 WPB. |
| | B) PROVIDE WATER HEATER EQUIPMENT SCHEDULES ON THE PLAN |
| | AND SUBMIT MANUFACTURE'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE WATER HEATERS AND ALL |
| | NEW APPLIANCES- SECTION 107.2.1 WPB. |
| | C) PROVIDE GAS ISOMETRIC DRAWINGS FOR EACH BUILDING |
| | SHOWING THE TYPES AND SIZES OF GAS PIPING, DELIVERY |
| | PRESSURES, TOTAL DEVELOPED LENGTH OF THE PIPING RUNS, |
| | LENGTHS OF ALL CUT SECTIONS OF PIPING, LOCATIONS OF |
| | REGULATORS, UNIONS, DRIP LEGS, AND PIPE CONNECTION |
| | FITTINGS- SECTIONS G2413.4.1, G2413.4.2, G2413.3, |
| | G2413.4, AND TABLES G2413.4(1) THROUGH G2413.4(21) FBC |
| | RES. |
| | D) SHOW LOCATIONS OF REQUIRED VENTS AND PROVIDE VENTING |
| | DIAGRAMS THAT INDICATE THE TYPE AND SIZE OF VENT, TOTAL |
| | RUN LENGTHS, TERMINATION LOCATIONS, AND SUPPORT |
| | DETAILS- G2426- G2429 FBC RES. |
| | E) PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR THE |
| | GAS PIPING INSTALLATION- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |