| 2020-04-13 17:14:05 | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 1- PLANS ARE SUBMITTED ELECTRONICALLY. NEED PLANS WITH |
| | DIGITAL SIGNATURE. |
| | 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | RESPONSE: |
| | PLANS SUBMITTED NOW HAVE A DIGITAL SIGNATURE THAT |
| | BELONGS TO DANIEL CLAVIJO. ACCORDING TO THE DBPR |
| | WEBSITE, DANIEL CLAVIJO IS NOT A FLORIDA LICENSED |
| | ARCHITECT. NEED THE DIGITAL SIGNATURE OF A LICENSED |
| | ARCHITECT WHEN SUBMITTING PLANS ELECTRONICALLY. |
| | ORIGINAL PLANS D AND PLANS SUBMITTED NOW HAVE A THE |
| | PRINTED IMAGE OF THE SEAL AND SIGNATURE OF PATRICK W. |
| | SEGRAVES REGISTERED ARCHITECT. ACCORDING TO THIS, THIS |
| | IS THE ARCHITECT RESPONSIBLE FOR THESE PLANS. WHY IS |
| | ANOTHER PERSON THAT IS NOT LICENSED IN FLORIDA SIGNING |
| | AND SEALING THESE PLANS? |
| | PLEASE COMPLY WITH 61G1-16.005 PROCEDURES FOR DIGITALLY |
| | SIGNING AND SEALING AND FOR ELECTRONICALLY TRANSMITTING |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 2- SCOPE OF WORK IS NOT CLEAR. THE DESCRIPTION OF THE |
| | SCOPE OF WORK SPECIFIED ON THE PERMIT APPLICATION |
| | SUBMITTED IS FOR "EXTERIOR LAP SIDING" ONLY. PLANS |
| | SUBMITTED ARE FOR COMPLETE RENOVATION (ALTERATION LEVEL |
| | 3) FOR THE FRONT AND REAR BUILDINGS. SCOPE OF WORK |
| | SPECIFIED ON THE PERMIT APPLICATION AND SCOPE OF WORK |
| | SHOWN ON PLANS NEED TO MATCH. REVISE AS REQUIRED. SEC. |
| | 107.2.1 CITY AMENDMENTS. COMPLETE REVIEW PROCESS WILL |
| | BE PERFORMED WHEN SCOPE OF WORK IS CORRECTED, INCLUDING |
| | PLAN REVIEW BY ALL RELEVANT TRADES. NOTE: REVISE |
| | VALUATION ACCORDINGLY. THE PERMIT FOR THE LAP SIDING |
| | ONLY CAN NOT BE ISSUED AT THIS TIME BECAUSE BASED ON |
| | DRAWINGS SUBMITTED THE EXTERIOR ELEVATIONS ARE GOING TO |
| | BE CHANGED AND THERE IS AN PROPOSED ADDITION ALSO) ALL |
| | THIS WORK WILL NEED TO BE APPROVED. |
| | |
| | RESPONSE: |
| | SCOPE OF WORK WAS CLARIFIED. COMPLETE RENOVATION OF |
| | BOTH BUILDINGS. THIS IS ALTERATION LEVEL 3. COMPLETE |
| | BUILDING REVIEW WILL BE PERFORMED NOW. SEE COMMENTS |
| | BELOW UNDER "NEW COMMENTS". |
| | |
| | 3- OK. |
| | 4- OK |
| | |
| | ORIGINAL COMMENT: |
| | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL). |
| | (A) INSWING EXTERIOR DOORS AS SHOWN ON PLANS. |
| | (B) OUTSWING EXTERIOR DOORS AS SHOWN ON PLANS. |
| | (C) CARRIAGE DOOR SHUTTERS AS SHOWN ON PLANS. |
| | (D) WINDOWS AS SHOWN ON PLANS. OPERABLE WINDOWS AND |
| | FIXED WINDOWS. |
| | (E) SHUTTERS AS SHOWN ON PLANS. AND PROVIDE COMPLETE |
| | INSTALLATION SCHEDULE. SEE CITY SAMPLE. |
| | |
| | |
| | NEW COMMENTS. ALTERATION LEVEL 3. SEC. 505 FBC-EXISTING |
| | BUILDING: |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 6- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| | FOR THE NEW DOORS AND WINDOWS OPENINGS AS SHOWN ON |
| | PLANS. SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. SEC. |
| | R301.1 FBC-RESIDENTIAL. |
| | |
| | 7- WALL SECTION ON SHEET A-7. SPECIFY ALL STRUCTURAL |
| | CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 8- MISSING THE STRUCTURAL DRAWINGS THAT ARE LISTED IN |
| | THE INDEX ON THE COVER SHEET. PROVIDE ALL DRAWINGS THAT |
| | ARE LISTED IN THE INDEX. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 9- IMPACT FEES - |
| | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE |
| | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS |
| | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST |
| | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE |
| | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL |
| | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME |
| | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM |
| | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS |
| | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| | YOUR PROJECT OR EMAIL IT TO [email protected] . |
| | |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |