2020-04-02 16:28:4804/02/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. A BACKFLOW PREVENTER MAY BE REQUIRED SINCE THIS A
 DUAL DWELLING PER THE CITY OF WEST PALM BEACH ORD
 #2853-95. A PERMIT REQUIRED BY A LICENSED CONTRACTOR
 AND MUST BE CERTIFIED BY UTILITIES PRIOR TO FINAL
 INSPECTION. PLEASE CONTACT THE CITY OF WPB UTILITIES AT
 561-822-2240 FOR FURTHER DIRECTIONS.
  
 3. PLUMBING RISER DIAGRAM REQUIRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL
 PLUMBING.
  
 4. THERE IS NO VALUE LISTED ON ANY PLUMBING OR
 SUB-APPLICATION AND THE OVERALL VALUE IS LOW. WPB
 AMENDMENTS TO THE FBC 109.3 BUILDING PERMITS
 VALUATIONS. IF IN THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF BUILDING, ALTERATION,
 STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, THE VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN
 FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST
 ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS
 PUBLISHED BY INTERNATIONAL CODE CONGRESS. FINAL
 BUILDING PERMIT VALUATION SHALL BE SET BY THE BUILDING
 OFFICIAL.
  
 5. HOT WATER REQUIRED, PLEASE SHOW THE SOURCE AND
 APERTURE OF HOT WATER PER THE 2017 FBC R 2722.2.
  
 6. PLANS ARE REQUIRED TO BE DESIGNED AND SIGNED AND
 SEALED BY A LICENSED ENGINEER OR ARCHITECT. PLANS
 FURNISHED BY AN INTERIOR DESIGNER ARE NOT ACCEPTABLE.
 PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; FBC
 107.2.1, 107.3.5.
  
 7. IF THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE
 LINING FBC R 2709.2, NOTE: SHOWER PAN MUST HAVE A
 SLOPED MORTAR BED THAT IS PRE-PITCHED BENEATH PRIOR TO
 LINER INSTALLATION OF 1/4" IN PER FOOT TOWARD THE
 DRAIN, MUST HAVE DAM CORNER, BACKING AROUND THE
 PERIMETER AND BEFORE FINAL MORTAR APPLICATION PLACE
 SOME PEA GRAVEL OVER WEEP HOLES SO THE MORTAR DOES NOT
 COVER THEM PER MANUFACTURES SPECIFICATIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  