Plan Review Notes
Plan Review Notes For Permit 20011283
Permit Number 20011283
Review Stop NFIP
Sequence Number 3
Notes
Date Text
2020-03-25 06:58:18RECIEVED 2ND APPRAISAL VIA E-MAIL - SEE 3RD NFIP REVIEW
 FOR COMMENTS
  
 ADDRESS: 1007 N FLAGLER DR MASTER PERMIT:
  20011283
  
 NFIP REVIEW - APPRAISAL FOR SI/SD DETERMINATION
  
 REQUIREMENT - NFIP COMPLIANT APPRAISAL
 (MARKET VALUE OF THE STRUCTURE MINUS DEPRECIATION)
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 6TH EDITION 2017
 CITY OF WEST PALM BEACH ORDINANCE NO. 4729-17
 USPAP = UNIFORM STANDARDS OF PROFESSIONAL APPRAISAL
 PRACTICE
 FEMA P-758 = SI/SD DESK REFERENCE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW OF APPRAISAL
  
 RESULTS: DENIED
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES.
 ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
  
 TYPE OF APPRAISAL: UNIFORM RESIDENTIAL APPRAISAL
 REPORT
  
 METHODOLOGY: CONVENTIONAL MARKET VALUE APPRAISAL
 (RE-SUB INCLUDES COST APPROACH METHODOLOGY TO ESTABLISH
 FEMA MARKET VALUE - REPLACEMENT COST MINUS DEPRECIATION
 - ACTUAL CASH VALUE - ACV) CORRECTED
 (ANALYSIS OF COMPARABLE SALES) (COST APPROACH)
 CORRECTED
  
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. USPAP SR 2-2 (A) (I) REQUIRES APPRAISERS TO REPORT
 THE APPRAISALS INTENDED USERS. CORRECTED
  
 2. USPAP SR 2-2 (A) (II) REQUIRES APPRAISERS TO REPORT
 THE APPRAISALS INTENDED USE. CORRECTED
  
 3. USPAP SR 2-2 (A) (V) REQUIRES APPRAISERS TO STATE
 THE TYPE AND DEFINITION OF VALUE. VALUE STATED IS
 MARKET VALUE BASED ON AN ANALYSIS OF COMPARABLE SALES.
 CORRECTED (COST APPROACH SUBMITTED FOR REVIEW) (TOTAL
 COST NEW OBTAINED USING RS MEANS)
  
 4. USPAP SR 2-2(A) (X) (I) STANDARD 1 - PROVIDE A NFIP
 COMPLIANT REPLACEMENT COST ESTIMATE WITH DEPRECIATION
 (ACTUAL CASH VALUE - ACV) FROM A RECOGNIZED COST
 ESTIMATING SERVICE SUPPORTED BY ADEQUATE DOCUMENTATION.
 (SEE NEW COMMENTS BELOW)
  
 5. PROVIDE A COST BREAKDOWN OF PROPOSED WORK. CORRECTED
 FEMA P-758 DESK REFERENCE SECTION 4.4
  
 NEW COMMENTS
  
 4A. REPLACEMENT COST ESTIMATE ESTABLISHED USING RS
 MEANS - CORRECTED
  
 4B.USPAP SR 2-2 (A) (X) (I) DEPRECIATION - STANDARD 1 -
 REQUIRES APPRAISERS TO USE AN ANALYTICAL PROCESS IN
 REACHING THEIR CONCLUSIONS.
 PLEASE REFERENCE - APPRAISAL / COST APPROACH /
 CALCULATIONS / PHYSICAL DETERIORATION FOR THE
 FOLLOWING:
 ECONOMIC LIFE WAS ESTABLISHED AT 70 YEARS
 EFFECTIVE LIFE WAS ESTABLISHED AT 10 YEARS
 10/70=14.29%
 STRUCTURE WAS BUILT IN 1953 - THIS WOULD ESTABLISH A
 REMAINING HISTORICAL LIFE OF 4 YEARS (70-66)
  
 PROVIDE A RATIONAL ANALYSIS FOR THE INCREASE FROM A
 REMAINING HISTORICAL LIFE OF 4 YEARS TO AN EFFECTIVE
 LIFE OF 10 YEARS.
  
 6. PLEASE REFERENCE - APPRAISAL - COST APPROACH -
 ANALYSIS/COMMENTS SECTION - RECONCILIATION :
 $411,000.00 IS THE DEPRECIATED COST OF THE MAIN
 BUILDING, EXCLUDING LAND VALUE, THE REAR BUILDING AND
 SITE IMPROVEMENTS.
  
 DEPRECIATED VALUE (ACV) OF THE BUILDING WAS ESTABLISHED
 AT $317,188 IN THE CALCULATIONS AND SUMMARY OF COST
 SECTIONS, PROVIDE CLARIFICATION FOR THIS RECONCILIATION
 STATEMENT OF $411.000.00.
  
  
  
  
  