Plan Review Notes
Plan Review Notes For Permit 20011283
Permit Number 20011283
Review Stop G
Sequence Number 2
Notes
Date Text
2020-08-22 07:34:33PLAN REVIEW - FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 FBC RES-FUEL GAS CHPT. 24
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS FROM 1ST REVIEW AND
 RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 1ST REVIEW COMMENTS:
  
 1) SHT. P-2 - THE GAS CALCULATION NOTES SHOW A BTU LOAD
 OF 607,000 BTU'S BUT THE PLANS SHOW A TOTAL BTU LOAD OF
 207,000 BTU'S. CLARIFY. (GAS CALCULATIONS ON PLAN PAGE
 P-2 INDICATE POOL HEATER AS EXISTING. PER NOTE BELOW,
 THERE IS NO RECORD OF THE POOL HEATER BEING PERMITTED.
 INCLUDE THE POOL HEATER ON ISO AND IDENTIFY LOCATION ON
 GAS PLAN. SHOW PIPE TYPE, SIZE AND LENGTH. PROVIDE
 MANUFACTURERES INSTALLATION INSTRUCTIONS)
  
 2) LIST THE BTU LOAD OF EACH APPLIANCE ON THE SYSTEM.
 REFER TO THE 2017 FBC-FUEL GAS SECS.401.8, 402.2, AND
 TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2413.4 AND TABLES G2413.4 (1 ) THROUGH
 G2413.4 (21). (SEE COMMENTS ABOVE)
  
 3) SUBMIT MANUFACTURERS SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 (MANUFACTURERS SPECIFICATIONS NOT SUBMITTED FOR REVIEW)
  
 NOTE: CITY RECORDS ONLY SHOW A GAS PERMIT FOR THE
 TANKLESS WATER HEATER AND THE RANGE. ANY OTHER GAS
 APPLIANCES THAT ARE CURRENTLY ON THIS SYSTEM MUST BE
 PERMITTED. (POOL HEATER SHALL BE PERMITTED AND
 INSPECTED. SEE COMMENTS ABOVE)
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  