2020-06-23 11:18:25PLAN REVIEW - PLUMBING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE A PLUMBING PLAN WITH DETAILED SCOPE OF WORK.
 SHOW EXISTING AND PROPOSED WORK.
 107.2 CONSTRUCTION DOCUMENTS.
  
 2. PROVIDE A SANITARY RISER DIAGRAHM.
 PLUMBING RISER - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1 ADMINISTRATION SECTION
 107.3.5.3 (12)
  
 3. PROVIDE A WATER DISTRIBUTION RISER DIAGRAHM.
 P2903.1WATER SUPPLY SYSTEM DESIGN CRITERIA. THE WATER
 SERVICE AND WATER DISTRIBUTION SYSTEMS SHALL BE
 DESIGNED, AND PIPE SIZES SHALL BE SELECTED SUCH THAT
 UNDER CONDITIONS OF PEAK DEMAND, THE CAPACITIES AT THE
 POINT OF OUTLET DISCHARGE SHALL NOT BE LESS THAN SHOWN
 IN TABLE P2903.1.
  
 4. PROVIDE SPECIFICATIONS FOR WATER CONTROL VALVES.
 607.2 HOT OR TEMPERED WATER SUPPLY TO FIXTURES.