| 2020-08-11 05:28:22 | 1) SHT. P-2 - THE GAS CALCULATION NOTES SHOW A BTU LOAD | | | OF 607,000 BTU'S BUT THE PLANS SHOW A TOTAL BTU LOAD OF | | | 207,000 BTU'S. CLARIFY. | | | 2) LIST THE BTU LOAD OF EACH APPLIANCE ON THE SYSTEM. | | | REFER TO THE 2017 FBC-FUEL GAS SECS.401.8, 402.2, AND | | | TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. | | | G2413.3, G2413.4 AND TABLES G2413.4 (1 ) THROUGH | | | G2413.4 (21). | | | 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 | | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | NOTE: CITY RECORDS ONLY SHOW A GAS PERMIT FOR THE | | | TANKLESS WATER HEATER AND THE RANGE. ANY OTHER GAS | | | APPLIANCES THAT ARE CURRENTLY ON THIS SYSTEM MUST BE | | | PERMITTED. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|