Plan Review Notes For Permit 20011267
Permit Number 20011267
Review Stop P
Sequence Number 5
Notes
Date Text
2020-08-04 11:51:20PASSED WITH PROVISOS.
 PROVISOS
  
 1) THE SAMPLING PORT FOR ALL GREASE INTERCEPTORS IS TO
 BE LOCATED ON THE DISCHARGE SIDE OF THE UNIT PER THE
 CITY OF WPB REQUIREMENTS.
 2) THE BOTTOM OF THE RACKED TANKLESS WATER HEATER UNITS
 ON THE ROOF SHALL ALSO MEET THE CLEARANCES REQUIRED IN
 FBC-BUILDING SEC.1510.10 AND TABLE 1510.10.
 3) SUBMIT A CONDENSATE RISER FOR REVIEW. THE SIZING
 SHALL COMPLY WITH FBC-PLUMBING SEC.314.2.2 & TABLE
 314.2.2. 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
 .