Plan Review Notes
Plan Review Notes For Permit 20011267
Permit Number 20011267
Review Stop P
Sequence Number 3
Notes
Date Text
2020-07-17 14:06:54 
  
 1) THE SAMPLING PORT FOR ALL GREASE INTERCEPTORS IS TO
 BE LOCATED ON THE DISCHARGE SIDE OF THE UNIT PER THE
 CITY OF WPB REQUIREMENTS.
 2) THE BOTTOM OF THE RACKED TANKLESS WATER HEATER UNITS
 ON THE ROOF SHALL ALSO MEET THE CLEARANCES REQUIRED IN
 FBC-BUILDING SEC.1510.10 AND TABLE 1510.10.
 3) SUBMIT AN EXPANDED DETAIL AS TO HOW THE HOT WATER
 RETURN LINE IS CONNECTED BACK TO THE WATER SYSTEM. WPB
 AMEND. TO FBC SEC. 107 2.1.
 4) SHTS. P6-01, P6-02, P6-04 - PLACE A NOTE ON THESE
 PLANS THAT READS "SEE PLAN VIEW DRAWINGS FOR THE
 SPECIFIC LEVELS FOR KEYNOTE LEGEND FOR THE RISERS."
 5) SUBMIT A CONDENSATE RISER FOR REVIEW. THE SIZING
 SHALL COMPLY WITH FBC-PLUMBING SEC.314.2.2 & TABLE
 314.2.2. 2ND REQUEST.
 6) RIGID SUPPORT SWAY BRACING SHALL BE PROVIDED AT
 CHANGES IN DIRECTION GREATER THAN 45 DEGREES FOR PIPE
 SIZES 4 INCHES AND LARGER IN THE SANITARY SYSTEM PER
 2017 FBC-PLUMBING SEC.308.6. PROVIDE A DETAIL FOR THESE
 SUPPORTS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  