| 2020-07-13 15:11:21 | 3RD REVIEW |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | PLAN REVIEW COMMENTS |
| | THRESHOLD BUILDING |
| | 8 STORY APARTMENT BUILDING (MIXED USE M, S-2, R-2, A-3 |
| | AND B) |
| | CONST. TYPE I-A, SPRINKLERED |
| | 170 MPH, EXPOSURE "D" |
| | FLOOD ZONE "X" |
| | 625 S. OLIVE AVE. |
| | PERMIT #20011267 |
| | |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) NOT COMPLIED. REQUEST TO DEFER HAS NOT BEEN RECEIVED |
| | FROM THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE |
| | CHARGE. THE ITEMS TO BE DEFERRED NEED TO BE LISTED ON |
| | THE PLANS. PREVIOUSLY (#38) THE FBC 107.3.4.1 DEFERRED |
| | SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL |
| | ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| | THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A |
| | NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 2) NOT COMPLIED. THE NOTE IN THE RESPONSE NARRATIVE |
| | NEEDS TO BE ON THE PLANS. PREVIOUSLY (#39) SHOW |
| | COMPLIANCE FBC ACCESSIBILITY SECTION 242 FOR ACCESSIBLE |
| | ENTRY INTO THE POOL OR SPECIFY ON THE PLANS WHY IT IS |
| | NOT REQUIRED. COMMUNITY POOLS THAT ARE ASSOCIATED WITH |
| | A PRIVATE RESIDENTIAL COMMUNITY THAT DO NOT RECEIVE |
| | GOVERNMENTAL FINANCIAL ASSISTANCE OR SPONSORSHIP AND |
| | ARE LIMITED TO THE EXCLUSIVE OF RESIDENTS AND THEIR |
| | GUESTS ARE NOT COVERED BY THE ADA ACCESSIBILITY |
| | REQUIREMENTS, INCLUDING PROVISIONS FOR POOL LIFTS OR |
| | SLOPED ENTRIES. IF A SWIMMING POOL LOCATED IN A |
| | RESIDENTIAL COMMUNITY IS MADE AVAILABLE TO THE PUBLIC |
| | FOR RENTAL OR USE IT IS REQUIRED TO COMPLY WITH TITLE |
| | II OF THE ADA. SPECIFY ON THE PLANS THE FORMER OR SHOW |
| | COMPLIANCE WITH THE LATTER STATEMENTS. SEE DECLARATORY |
| | STATEMENT, DS 2013-011. |
| | |
| | 3) NOT COMPLIED. PREVIOUSLY (#40) SEPARATE PERMITS, |
| | REVIEWS AND FEES ARE REQUIRED FOR SOME ITEMS THAT MAY |
| | HAVE BEEN INCLUDED IN THE VALUE FOR THIS PROJECT. ITEMS |
| | SUCH AS FIRE ALARM, FIRE SPRINKLER, LOW VOLTAGE, |
| | LANDSCAPING, IRRIGATION AND ALL ITEMS OTHER THAN |
| | BUILDING, MECHANICAL, ELECTRIC AND PLUMBING. PLEASE |
| | PROVIDE A COST BREAKDOWN SO THAT WE CAN DEDUCT THESE |
| | ITEMS FROM THE PERMIT VALUE SO THAT YOU WILL NOT BE |
| | CHARGED TWICE FOR THE SAME ITEM. |
| | |
| | 4) NEW COMMENT. THE PROPOSED DOOR FROM SUITE 300, THE |
| | REST./RETAIL AREA, ON THE GROUND FLOOR THAT OPENS INTO |
| | THE PARKING GARAGE IS LOCATED IN A ONE HOUR FIRE |
| | RESISTIVE RATED WALL. TABLE 508.4 REQUIRES A ONE HOUR |
| | FIRE SEPARATION BETWEEN S-2 AND M OR B OCCUPANCIES IN A |
| | SPRINKLERED BUILDING. THIS DOOR IS REQUIRED TO BE FIRE |
| | RATED AND THE DOOR SCHEDULE ON SHEET A8-01 DOES NOT |
| | SHOW A FIRE RATING FOR DOOR C300C. THIS DOOR IS |
| | SPECIFIED AS TYPE D5 WHICH IS A GLAZED DOOR. |
| | |
| | 5) PLEASE PROVIDE A RESPONSE LETTER ADDRESSING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |