Plan Review Notes
Plan Review Notes For Permit 20011267
Permit Number 20011267
Review Stop P
Sequence Number 2
Notes
Date Text
2020-06-04 10:54:061) SUBMIT A SET OF SIGNED AND SEALED CIVIL DRAWINGS FOR
 REVIEW. THE CIVIL DRAWINGS SHALL SHOW THE GAS, SANITARY
 AND STORM SYSTEMS ON THE PLANS. WPB AMEND. TO FBC
 SEC.107.2..1.
 THE FOLLOWING COMMENTS #2 THROUGH #6 ALL REFER TO SHT.
 CD-21:
 2) THE DETAILS FOR THE REINFORCEMENT FOR THE GRAB BARS
 SHOW THE BOTTOM OF THE REINFORCEMENT AT 30 INCHES
 MAXIMUM BUT THE FAIR HOUSING GUIDELINES SHOW 32 INCHES
 MAX. CLARIFY.REVISE ALL DETAILS AS NEEDED.
 3) DETAIL #3 - SHOW THE LENGTH OF THE REINFORCEMENT FOR
 THE GRAB BAR. A MINIMUM OF 24 INCHES IS REQUIRED PER
 THE FHA GUIDELINES.
 4) DETAIL #5 - SHOW THE MAXIMUM HEIGHT DIMENSION FOR
 THE REINFORCEMENT FOR THE GRAB BAR.COMPLY WITH THE FAIR
 HOUSING ACT GUIDELINES.
 5) DETAIL #14 - SHOW THE REQUIRED CLEAR FLOOR SPACE FOR
 THE PERPENDICULAR APPROACHTO THE TUB. COMPLY WITH FHA
 GUIDELINES.
 6) DETAIL #16 - THERE IS A NOTE BY THE SHOWER DIAGRAM
 THAT REFERS TO A 23 INCH BY 60 INCH ROLL IN SHOWER.
 CLARIFY.SHOWERS SHALL BE A MINIMUM OF 30 INCHES IN
 WIDTH.FBC-PLUMBING SEC.417.4.
 7) SHT. CD-22 - THE PLAN IS LABELED AS "COMMON AND
 PUBLIC AREAS" BUT THE PLAN REFLECTS WHAT APPEARS TO BE
 THE INTERIOR OF THE UNITS. CLARIFY.
 8) SHT. CD-23 - DETAIL #14 - THE END OF THE "L" SHAPED
 SEAT SHALL BE 23 INCHES MAXIMUM FROM THE SEAT WALL PER
 ANSI A117.1 - 1986.. THE DETAIL SHOWS 23-24 INCHES.
 CLARIFY.
 9) SHT. CD-23 - DETAIL #11 - THE DETAIL SHOWS WHAT
 APPEARS TO BE TWO DIFFERENT HEIGHT DIMENSIONS FOR THE
 BREAK ROOM SINK. ONE SHOWS 36 INCHES AND ONE SHOWS 34
 INCHES. THE MAXIMUM HEIGHT IS 34 INCHES. CLARIFY.
 10) SHT. CD-23 - DETAIL #15 - THE MAXIMUM HEIGHT TO THE
 BOTTOM OF A URINAL SCREEN IS 12 INCHES . THE DETAIL
 SHOWS 13 1/2 INCHES.FBC-PLUMBING SEC.405.3.5.
 11)SHT. CD-23 - DETAIL #16 - SHOWS A VERTICAL GRAB
 BAR.GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION PER ANSI A117.1 SEC. 4.16. THERE IS NO
 EXCEPTION FOR VERTICAL GRAB BARS.
 12) SHT. A3-01 - DETAIL #1 - SHOW THE REQUIRED 30
 INCHES BY 48 INCHES MANEUVERING SPACE LOCATED OUSIDE
 THE SWING OF THE DOOR PER FHA GUIDELINES.
 13) SHT. A3-02 - DEATIL #1- SHOW THE REQUIRED 30 INCHES
 BY 48 INCHES MANEUVERING SPACE LOCATED OUSIDE THE SWING
 OF THE DOOR PER FHA GUIDELINES.
 14) SHT. A3-08 - DETAIL #1 - SHOW THE LENGTH OF THE
 SHOWER WALL NEXT TO THE WATER CLOSET. THIS WALL CANNOT
 EXCEED 24 INCHES PER FHA GUIDELINES.
 15) SHT.A3-09 - DETAIL #1 - SHOW THE LENGTH OF THE
 SHOWER WALL NEXT TO THE WATER CLOSET. THIS WALL CANNOT
 EXCEED 24 INCHES PER FHA GUIDELINES.
 16) SUBMIT DETAILS ON THE "MOVEABLE ISLAND" IN THE
 KITCHEN. WPB AMEND. TO FBC SEC. 107.2.1.
 17) SHT. A3-24 - SHOW THE REQUIRED 30 INCHES BY 48
 INCHES MANEUVERING SPACE LOCATED OUSIDE THE SWING OF
 THE DOOR PER FHA GUIDELINES.
 18) SHT. A3-24 - KEYED NOTE #13.08 NOTES THE WATER
 HEATER IS LOCATED IN THE CABINET ABOVE THE
 REFRIGERATOR. PROVIDE SPECIFICATIONS FOR THE WATER
 HEATER AND REQUIREMENTS FOR THE CLEARANCES FOR
 MAINTENANCE AND REPLACEMENT PER FBC-PLUMBING SEC.
 502.5.
 19) PLACE A NOTE ON THE PLANS THAT THE SHUTOFF VALVES
 FOR THE WASHING MACHINES WILL BE PROVIDED WITH ACCESS
 PER FBC-PLUMBING SEC.606.3.SEE SHT. A6-60.
 20) CLEARLY SHOW ON THE UNIT PLANS THAT THE PARALLEL
 CLEAR FLOOR SPACE AT THE LAVATORIES IS CENTERED ON THE
 LAVATORIES.
 21) SUBMIT DETAILS ON THE STORM DETENTION SYSTEM AS
 REFERENCED ON SHT. A5-03. WPB AMEND. TO FBC SEC.
 107.2.1.
 22) SHT. A7-30 - PROVIDE THE DIMENSIONS OF THE SUMP
 PIT.
 23) SHT.ID-0.00 - DETAIL #8 - CODE ANALYSIS LISTS THE
 TEXAS ACCESSIBILITY STANDARS. CLARIFY.
 24) SHT. ID-0.01 - ACCESSIBLE AND USABLE PUBLIC AND
 COMMON AREAS SHALL COMPLY WITH ANSI A117.1 -1986 PER
 THE FHA GUIDELINES.
 25) SHT. ID-0.01 - DETAIL #6 - HANDICAP TOILET AND
 BLOCKING DETAIL SHOWS A VERTICAL GRAB BAR WITH A NOTE
 STATING "VERTICAL GRAB BARS REQUIRED IN PUBLIC SPACES
 ONLY BY ANSI 604." THERE IS NO SUCH CODE SECTION IN
 ANSI A117.1 - 1986 AND THERE IS NO EXCEPTION FOR THE
 INSTALLATION OF GRAB BARS IN A VERTICAL POSITION IN THE
 FBC-ACCESS. REMOVE THIS NOTE FROM THE PLAN.
 26) SHT. ID-0.001 - THE MAXIMUM HEIGHT TO THE BOTTOM OF
 THE BLOCKING FROM THE FINISH FLOOR IS 32 INCHES PER THE
 FAIR HOUSING GUIDELINES, NOT 30 INCHES AS SHOWN.
 27) SHT. ID-0.01 - THE PLANS REFERENCE THE ADA. THE ADA
 IS NOT ENFORCED IN FLORIDA. THE FLORIDA BUILDING CODE-
 ACCESSIBILITY VOLUME IS THE GOVENING DOCUMENT. PLEASE
 REVISE THE NOTE.
 28) SHT. ID-0.01 - DETAIL #6 - SINGLE USER COMPARTMENT
 SHALL HAVE 59 INCHES DEEP MINIMUM WITH A FLOOR MOUNTED
 WATER CLOSET BUT THE PLANS SHOW 56 INCHES. CLARIFY.
 29) SHT. ID-2.01 - DETAIL #3 - SUBMIT A DIMENSION PLAN
 SHOWING THE LENGTH AND WIDTH OF THE TOILET ROOM.ALSO,
 THE DOOR SWINGS INTO THE CLEAR FLOOR SPACE FOR THE
 LAVATORY.SHOW THE SUUFICIENT MANEUVERING SPACE WITHIN
 THE BATHROOM FOR A PERSON USING A WHEELCHAIR TO ENTER
 AND CLOSE THE DOOR, USE THE FIXTURES, REOPEN THE DOOR,
 AND EXIT. REFER TO FIGURE 3 OF ANSI A117.1 - 1986,
 30) SUBMIT THE TOTAL OCCUPANT LOAD FOR THE FITNESS
 CENTER, LOUNGE, POOL AND CLUBROOM. THE REQUIRED NUMBER
 OF SANNITARY FACILITIES IN THE MEN'S AND WOMEN'S
 RESTROOM SHALL COMPLY WITH FBC-PLUMBING TABLE 403.1 AND
 ALSO SEC.403.1.3. FOR POTTY PARITY.
 31) SHT. ID - 3.02 - DETAIL #15 - REMOVE THE VERTICAL
 GRAB BAR. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION PER ANSI A117.1 - 1986 SEC. 4.16. THERE IS NO
 EXCEPTION FOR VERTICAL GRAB BARS.
 32) SHT. P1-00A - PLACE RISER TAGS ON EACH RISER OF THE
 SANITARY SYSTEM AND PROVIDE MATCH LINES ON THE PLAN
 SHEETS. WPB AMEND. TO FBC SEC. 107.2.1.
 33) SHT.P1- 00B - PROVIDE MATCH LINES ON THE PLANS FOR
 THE CONTINUATION OF DRAIN LINES AND PLACE RISER TAGS ON
 EACH RISER. WPB AMEND. TO FBC SEC. 107.2.1.
 34) A SAMPLING PORT IS REQUIRED ON THE OUTLET OF EACH
 INTERCEPTOR PER THE CITY OF WEST PALM BEACH STANDARD
 DRAWING GS-7.1.
 35) THE GREASE RETENTION CAPACITY OF THE INTERCEPTOR
 SHALL BE A MINIMUM OF 500 LBS. PER 2017 FBC-PLUMBING
 SEC.1003.3.4.1, FOOTNOTE (A).
 36) SUBMIT MANUFACTURER'S DETAILS FOR THE GREASE
 INTERCEPTORS.WPB AMEND. TO FBC SEC. 107.2.1.
 37) SHT. P1-02A - KEYNOTES #5 & #6 AT COLS. "C" & "E"
 POINT TO NOTHING.CLARIFY. ALSO, PROVIDE MATCH LINES ON
 THE PLANS.
 38) SHT. P1-03A.1 - TAG ALL RISERS, PROVIDE MATCH LINES
 ON THE PLANS. KEYNOTE #6 INDICATES AN 1 1/2 INCH COLD
 WATER LINE BUT THE PLAN SHOWS 1 1/4 INCH WATER LINE.
 CLARIFY.
 39) SHT. P1-03A.2 - TAG ALL RISERS, PROVIDE MATCH LINES
 ON THE PLANS. KEYNOTE #6 INDICATES AN 1 1/2 INCH COLD
 WATER LINE BUT THE PLAN SHOWS 1 1/4 INCH WATER LINE.
 CLARIFY.
 40) SHT. P1-03B.1 - TAG ALL RISERS, PROVIDE MATCH LINES
 ON THE PLANS. KEYNOTE #6 INDICATES AN 1 1/2 INCH COLD
 WATER LINE BUT THE PLAN SHOWS 1 1/4 INCH WATER LINE.
 CLARIFY.
 41) SHT. P1-03B.2 - TAG ALL RISERS, PROVIDE MATCH LINES
 ON THE PLANS. KEYNOTE #6 INDICATES AN 1 1/2 INCH COLD
 WATER LINE BUT THE PLAN SHOWS 1 1/4 INCH WATER LINE.
 CLARIFY.
 42) PROVIDE MATCH LNES AND RISER TAGS FOR THE FOLLOWING
 PLAN SHEETS: P1-04A.1, P1-04A.2, P1-04B.1, P1-04B.2,
 P1-05A, P1-05A.1, P1-05B, P1-06A, P1-06B, P1-07A,
 P1-07B, P1-08A, P1-08B, P1-09A, P1-09B.
 43) SUBMIT AN ELEVATION DETAIL OF THE RACKED TANKLESS
 WATER HEATERS. SHOW THE DISTANCE FROM THE BOTTOM OF THE
 TANKLESS WATER HEATERS TO THE FINISH ROOF SURFACE.
 CLEARANCES SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AND 2017 FBC-FUEL GAS CODE.
 44) SHT. P6-01 - FULL OPEN SHUTOFF VALVES ARE REQUIRED
 AT THE BASE OF EACH WATER RISER PER 2017 FBC-PLUMBING
 SEC.606.1. ACCESS SHALL BE PROVIDED FOR THE VALVES.
 45) SHT.P3-18 - DRAINAGE RISER - DRAIN LINES ARE
 MISSING, VENTS GOING NOWHERE, WHERE DOES THE DRAIN FOR
 THE BATHTUB CONNECT? CLARIFY.
 46) SHT.P3-20 - DRAINAGE RISER - A WATER CLOSET IS
 MISSING FROM THE DRAINAGE RISER. CLARIFY.
 47) SHT. P4-01 - ISLAND SINK DETAIL - ACCESS IS
 REQUIRED THE CLEANOUT. FBC-PLUMBING SEC. 708.1.10.
 48) SHT. P4-01 - THE THERMO MIXING VALVE DETAIL SHALL
 COMPLY WITH 2017 FBC-PLUMBING SEC.607.2.2. THE HOT
 WATER OR TEMPERED WATER RETURN LINE SHALL BE ROUTED TO
 THE COLD WATER INLET PIPE OF THE WATER HEATER AND THE
 COLD WATER INLET PIPE OR THE HOT WATER RETURN
 CONNECTION OF THE THERMOSTATIC MIXING VALVE.
 49) SHT. P4-02 - INSTANTANEOUS WATER HEATER DETAIL -
 3-WAY VALVES ARE NOT APPROVED PER THE 2017 FBC-PLUMBING
 SEC.606.2.
 50) SHT. P4-02 - SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE OIL SMART PUMP SYSTEM. WPB AMEND. TO FBC SEC.
 107.2.1.
 51) SHT. P5-01 - PLUMBING FIXTURE SCHEDULE - THE
 WASHING MACINE WASTE STACK SHALL BE A MINIMUM OF 3 INCH
 PER 2017 FBC-PLUMBING SEC.406.2.
 52) SHT. P5-01 - DOMESTIC PUMP DETAIL - A LOW-PRESSURE
 CUTOFF IS REQUIRED ON THE PUMP PER 2017 FBC-PLUMBING
 SEC.606.5.5.
 53) SHT. P6-01 - THE 3/4 INCH LINE FOR THE HOSE BIBB IN
 THE TRASH ROOM SHALL BE EQUIPPED WITH A SHUTOFF VALVE
 PER 2017 FBC-PLUMBING SEC.606.2.
 54) SHT. P6-01 - SHOW THE TERMINATION POINTS OF ALL THE
 WATER SUPPLY LINES/ TAG ALL WATER RISERS FOR
 IDENTIFICATION AND SIZE ALL BRANCHES ON THE WATER
 RISER. WPB AMEND. TO FBC SEC. 107.2.1.
 55) SHT.P6-01 - SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE BOOSTER & RECIRCULATION PUMP.THE RECIRCULATION
 PUMP SHALL COMPLY WITH THE REQUIREMENTS OF FBC-PLUMBING
 SEC.607..2.1.2.
 56) SHT. P6-02 - TAG ALL THE RISERS ON THE SANITARY
 RISER FOR IDENTIFICATION AND IDENTIFY THE FIXTURES. WPB
 AMEND. TO FBC SEC. 107.2.1.
 57) SHT.P6-04 - THE PUBLISHED ROOF DRAIN FLOW RATE,
 BASED ON THE HEAD OF WATER ABOVE THE ROOF DRAIN, SHALL
 BE USED TO SIZE THE STORM DRAINAGE SYSTEM IN ACCORDANCE
 WITH FBC-PLUMBING SECTION 1106, 1106.1, 1106.2.. SUBMIT
 GPM FLOW RATE CALCULATIONS FOR THE STORM DRAIANGE
 SYSTEM. CALCULATIONS SHALL INCLUDE PARAPET WALLS PER
 FBC-PLUMBING SEC.1106.4.
 58) SHT. P6-04 - THERE ARE DRAINS SHOWN AS "FLOATING",
 AND NOT CONNECTED TO ANY PIPING. CLARIFY.
 59) SHT. P6-04 - CLEANOUTS ARE REQUIRED IN THE STORM
 DRAINAGE SYSTEM OER FBC-PLUMBING SEC.1101.8.
 60) SHT. P6-04 - SHOW THE TERMINATION POINT OF THE
 STORM DRAIN SYSTEM ON THE STORM SYSTEM RISER. WPB
 AMEND. TO FBC SEC. 107.2.1.
 61) SUBMIT A CONDENSATE RISER. THE SIZING SHALL COMPLY
 WITH FBC-PLUMBING SEC.314.2.2 & TABLE 314.2.2.
 62) SHT. P1-01A STILLS HAS A NOTE REGARDING THE
 INSTALLATION OF AN AAV TO BE INSTALLED HIGH IN ROOM ON
 LEVEL 1. THE INSTALLATION OF AIR ADMITTANCE VALVES ARE
 NOT PERMITTED BELOW THE TOP FOUR BRANCH INTERVALS PER
 FBC-PLUMBING SEC.918.3.1.
 63) SIZE THE WATER RISERS ON THE ENLARGED UNIT PLANS.
 WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW