| 2020-06-04 10:54:06 | 1) SUBMIT A SET OF SIGNED AND SEALED CIVIL DRAWINGS FOR |
| | REVIEW. THE CIVIL DRAWINGS SHALL SHOW THE GAS, SANITARY |
| | AND STORM SYSTEMS ON THE PLANS. WPB AMEND. TO FBC |
| | SEC.107.2..1. |
| | THE FOLLOWING COMMENTS #2 THROUGH #6 ALL REFER TO SHT. |
| | CD-21: |
| | 2) THE DETAILS FOR THE REINFORCEMENT FOR THE GRAB BARS |
| | SHOW THE BOTTOM OF THE REINFORCEMENT AT 30 INCHES |
| | MAXIMUM BUT THE FAIR HOUSING GUIDELINES SHOW 32 INCHES |
| | MAX. CLARIFY.REVISE ALL DETAILS AS NEEDED. |
| | 3) DETAIL #3 - SHOW THE LENGTH OF THE REINFORCEMENT FOR |
| | THE GRAB BAR. A MINIMUM OF 24 INCHES IS REQUIRED PER |
| | THE FHA GUIDELINES. |
| | 4) DETAIL #5 - SHOW THE MAXIMUM HEIGHT DIMENSION FOR |
| | THE REINFORCEMENT FOR THE GRAB BAR.COMPLY WITH THE FAIR |
| | HOUSING ACT GUIDELINES. |
| | 5) DETAIL #14 - SHOW THE REQUIRED CLEAR FLOOR SPACE FOR |
| | THE PERPENDICULAR APPROACHTO THE TUB. COMPLY WITH FHA |
| | GUIDELINES. |
| | 6) DETAIL #16 - THERE IS A NOTE BY THE SHOWER DIAGRAM |
| | THAT REFERS TO A 23 INCH BY 60 INCH ROLL IN SHOWER. |
| | CLARIFY.SHOWERS SHALL BE A MINIMUM OF 30 INCHES IN |
| | WIDTH.FBC-PLUMBING SEC.417.4. |
| | 7) SHT. CD-22 - THE PLAN IS LABELED AS "COMMON AND |
| | PUBLIC AREAS" BUT THE PLAN REFLECTS WHAT APPEARS TO BE |
| | THE INTERIOR OF THE UNITS. CLARIFY. |
| | 8) SHT. CD-23 - DETAIL #14 - THE END OF THE "L" SHAPED |
| | SEAT SHALL BE 23 INCHES MAXIMUM FROM THE SEAT WALL PER |
| | ANSI A117.1 - 1986.. THE DETAIL SHOWS 23-24 INCHES. |
| | CLARIFY. |
| | 9) SHT. CD-23 - DETAIL #11 - THE DETAIL SHOWS WHAT |
| | APPEARS TO BE TWO DIFFERENT HEIGHT DIMENSIONS FOR THE |
| | BREAK ROOM SINK. ONE SHOWS 36 INCHES AND ONE SHOWS 34 |
| | INCHES. THE MAXIMUM HEIGHT IS 34 INCHES. CLARIFY. |
| | 10) SHT. CD-23 - DETAIL #15 - THE MAXIMUM HEIGHT TO THE |
| | BOTTOM OF A URINAL SCREEN IS 12 INCHES . THE DETAIL |
| | SHOWS 13 1/2 INCHES.FBC-PLUMBING SEC.405.3.5. |
| | 11)SHT. CD-23 - DETAIL #16 - SHOWS A VERTICAL GRAB |
| | BAR.GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION PER ANSI A117.1 SEC. 4.16. THERE IS NO |
| | EXCEPTION FOR VERTICAL GRAB BARS. |
| | 12) SHT. A3-01 - DETAIL #1 - SHOW THE REQUIRED 30 |
| | INCHES BY 48 INCHES MANEUVERING SPACE LOCATED OUSIDE |
| | THE SWING OF THE DOOR PER FHA GUIDELINES. |
| | 13) SHT. A3-02 - DEATIL #1- SHOW THE REQUIRED 30 INCHES |
| | BY 48 INCHES MANEUVERING SPACE LOCATED OUSIDE THE SWING |
| | OF THE DOOR PER FHA GUIDELINES. |
| | 14) SHT. A3-08 - DETAIL #1 - SHOW THE LENGTH OF THE |
| | SHOWER WALL NEXT TO THE WATER CLOSET. THIS WALL CANNOT |
| | EXCEED 24 INCHES PER FHA GUIDELINES. |
| | 15) SHT.A3-09 - DETAIL #1 - SHOW THE LENGTH OF THE |
| | SHOWER WALL NEXT TO THE WATER CLOSET. THIS WALL CANNOT |
| | EXCEED 24 INCHES PER FHA GUIDELINES. |
| | 16) SUBMIT DETAILS ON THE "MOVEABLE ISLAND" IN THE |
| | KITCHEN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 17) SHT. A3-24 - SHOW THE REQUIRED 30 INCHES BY 48 |
| | INCHES MANEUVERING SPACE LOCATED OUSIDE THE SWING OF |
| | THE DOOR PER FHA GUIDELINES. |
| | 18) SHT. A3-24 - KEYED NOTE #13.08 NOTES THE WATER |
| | HEATER IS LOCATED IN THE CABINET ABOVE THE |
| | REFRIGERATOR. PROVIDE SPECIFICATIONS FOR THE WATER |
| | HEATER AND REQUIREMENTS FOR THE CLEARANCES FOR |
| | MAINTENANCE AND REPLACEMENT PER FBC-PLUMBING SEC. |
| | 502.5. |
| | 19) PLACE A NOTE ON THE PLANS THAT THE SHUTOFF VALVES |
| | FOR THE WASHING MACHINES WILL BE PROVIDED WITH ACCESS |
| | PER FBC-PLUMBING SEC.606.3.SEE SHT. A6-60. |
| | 20) CLEARLY SHOW ON THE UNIT PLANS THAT THE PARALLEL |
| | CLEAR FLOOR SPACE AT THE LAVATORIES IS CENTERED ON THE |
| | LAVATORIES. |
| | 21) SUBMIT DETAILS ON THE STORM DETENTION SYSTEM AS |
| | REFERENCED ON SHT. A5-03. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 22) SHT. A7-30 - PROVIDE THE DIMENSIONS OF THE SUMP |
| | PIT. |
| | 23) SHT.ID-0.00 - DETAIL #8 - CODE ANALYSIS LISTS THE |
| | TEXAS ACCESSIBILITY STANDARS. CLARIFY. |
| | 24) SHT. ID-0.01 - ACCESSIBLE AND USABLE PUBLIC AND |
| | COMMON AREAS SHALL COMPLY WITH ANSI A117.1 -1986 PER |
| | THE FHA GUIDELINES. |
| | 25) SHT. ID-0.01 - DETAIL #6 - HANDICAP TOILET AND |
| | BLOCKING DETAIL SHOWS A VERTICAL GRAB BAR WITH A NOTE |
| | STATING "VERTICAL GRAB BARS REQUIRED IN PUBLIC SPACES |
| | ONLY BY ANSI 604." THERE IS NO SUCH CODE SECTION IN |
| | ANSI A117.1 - 1986 AND THERE IS NO EXCEPTION FOR THE |
| | INSTALLATION OF GRAB BARS IN A VERTICAL POSITION IN THE |
| | FBC-ACCESS. REMOVE THIS NOTE FROM THE PLAN. |
| | 26) SHT. ID-0.001 - THE MAXIMUM HEIGHT TO THE BOTTOM OF |
| | THE BLOCKING FROM THE FINISH FLOOR IS 32 INCHES PER THE |
| | FAIR HOUSING GUIDELINES, NOT 30 INCHES AS SHOWN. |
| | 27) SHT. ID-0.01 - THE PLANS REFERENCE THE ADA. THE ADA |
| | IS NOT ENFORCED IN FLORIDA. THE FLORIDA BUILDING CODE- |
| | ACCESSIBILITY VOLUME IS THE GOVENING DOCUMENT. PLEASE |
| | REVISE THE NOTE. |
| | 28) SHT. ID-0.01 - DETAIL #6 - SINGLE USER COMPARTMENT |
| | SHALL HAVE 59 INCHES DEEP MINIMUM WITH A FLOOR MOUNTED |
| | WATER CLOSET BUT THE PLANS SHOW 56 INCHES. CLARIFY. |
| | 29) SHT. ID-2.01 - DETAIL #3 - SUBMIT A DIMENSION PLAN |
| | SHOWING THE LENGTH AND WIDTH OF THE TOILET ROOM.ALSO, |
| | THE DOOR SWINGS INTO THE CLEAR FLOOR SPACE FOR THE |
| | LAVATORY.SHOW THE SUUFICIENT MANEUVERING SPACE WITHIN |
| | THE BATHROOM FOR A PERSON USING A WHEELCHAIR TO ENTER |
| | AND CLOSE THE DOOR, USE THE FIXTURES, REOPEN THE DOOR, |
| | AND EXIT. REFER TO FIGURE 3 OF ANSI A117.1 - 1986, |
| | 30) SUBMIT THE TOTAL OCCUPANT LOAD FOR THE FITNESS |
| | CENTER, LOUNGE, POOL AND CLUBROOM. THE REQUIRED NUMBER |
| | OF SANNITARY FACILITIES IN THE MEN'S AND WOMEN'S |
| | RESTROOM SHALL COMPLY WITH FBC-PLUMBING TABLE 403.1 AND |
| | ALSO SEC.403.1.3. FOR POTTY PARITY. |
| | 31) SHT. ID - 3.02 - DETAIL #15 - REMOVE THE VERTICAL |
| | GRAB BAR. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION PER ANSI A117.1 - 1986 SEC. 4.16. THERE IS NO |
| | EXCEPTION FOR VERTICAL GRAB BARS. |
| | 32) SHT. P1-00A - PLACE RISER TAGS ON EACH RISER OF THE |
| | SANITARY SYSTEM AND PROVIDE MATCH LINES ON THE PLAN |
| | SHEETS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 33) SHT.P1- 00B - PROVIDE MATCH LINES ON THE PLANS FOR |
| | THE CONTINUATION OF DRAIN LINES AND PLACE RISER TAGS ON |
| | EACH RISER. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 34) A SAMPLING PORT IS REQUIRED ON THE OUTLET OF EACH |
| | INTERCEPTOR PER THE CITY OF WEST PALM BEACH STANDARD |
| | DRAWING GS-7.1. |
| | 35) THE GREASE RETENTION CAPACITY OF THE INTERCEPTOR |
| | SHALL BE A MINIMUM OF 500 LBS. PER 2017 FBC-PLUMBING |
| | SEC.1003.3.4.1, FOOTNOTE (A). |
| | 36) SUBMIT MANUFACTURER'S DETAILS FOR THE GREASE |
| | INTERCEPTORS.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 37) SHT. P1-02A - KEYNOTES #5 & #6 AT COLS. "C" & "E" |
| | POINT TO NOTHING.CLARIFY. ALSO, PROVIDE MATCH LINES ON |
| | THE PLANS. |
| | 38) SHT. P1-03A.1 - TAG ALL RISERS, PROVIDE MATCH LINES |
| | ON THE PLANS. KEYNOTE #6 INDICATES AN 1 1/2 INCH COLD |
| | WATER LINE BUT THE PLAN SHOWS 1 1/4 INCH WATER LINE. |
| | CLARIFY. |
| | 39) SHT. P1-03A.2 - TAG ALL RISERS, PROVIDE MATCH LINES |
| | ON THE PLANS. KEYNOTE #6 INDICATES AN 1 1/2 INCH COLD |
| | WATER LINE BUT THE PLAN SHOWS 1 1/4 INCH WATER LINE. |
| | CLARIFY. |
| | 40) SHT. P1-03B.1 - TAG ALL RISERS, PROVIDE MATCH LINES |
| | ON THE PLANS. KEYNOTE #6 INDICATES AN 1 1/2 INCH COLD |
| | WATER LINE BUT THE PLAN SHOWS 1 1/4 INCH WATER LINE. |
| | CLARIFY. |
| | 41) SHT. P1-03B.2 - TAG ALL RISERS, PROVIDE MATCH LINES |
| | ON THE PLANS. KEYNOTE #6 INDICATES AN 1 1/2 INCH COLD |
| | WATER LINE BUT THE PLAN SHOWS 1 1/4 INCH WATER LINE. |
| | CLARIFY. |
| | 42) PROVIDE MATCH LNES AND RISER TAGS FOR THE FOLLOWING |
| | PLAN SHEETS: P1-04A.1, P1-04A.2, P1-04B.1, P1-04B.2, |
| | P1-05A, P1-05A.1, P1-05B, P1-06A, P1-06B, P1-07A, |
| | P1-07B, P1-08A, P1-08B, P1-09A, P1-09B. |
| | 43) SUBMIT AN ELEVATION DETAIL OF THE RACKED TANKLESS |
| | WATER HEATERS. SHOW THE DISTANCE FROM THE BOTTOM OF THE |
| | TANKLESS WATER HEATERS TO THE FINISH ROOF SURFACE. |
| | CLEARANCES SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS AND 2017 FBC-FUEL GAS CODE. |
| | 44) SHT. P6-01 - FULL OPEN SHUTOFF VALVES ARE REQUIRED |
| | AT THE BASE OF EACH WATER RISER PER 2017 FBC-PLUMBING |
| | SEC.606.1. ACCESS SHALL BE PROVIDED FOR THE VALVES. |
| | 45) SHT.P3-18 - DRAINAGE RISER - DRAIN LINES ARE |
| | MISSING, VENTS GOING NOWHERE, WHERE DOES THE DRAIN FOR |
| | THE BATHTUB CONNECT? CLARIFY. |
| | 46) SHT.P3-20 - DRAINAGE RISER - A WATER CLOSET IS |
| | MISSING FROM THE DRAINAGE RISER. CLARIFY. |
| | 47) SHT. P4-01 - ISLAND SINK DETAIL - ACCESS IS |
| | REQUIRED THE CLEANOUT. FBC-PLUMBING SEC. 708.1.10. |
| | 48) SHT. P4-01 - THE THERMO MIXING VALVE DETAIL SHALL |
| | COMPLY WITH 2017 FBC-PLUMBING SEC.607.2.2. THE HOT |
| | WATER OR TEMPERED WATER RETURN LINE SHALL BE ROUTED TO |
| | THE COLD WATER INLET PIPE OF THE WATER HEATER AND THE |
| | COLD WATER INLET PIPE OR THE HOT WATER RETURN |
| | CONNECTION OF THE THERMOSTATIC MIXING VALVE. |
| | 49) SHT. P4-02 - INSTANTANEOUS WATER HEATER DETAIL - |
| | 3-WAY VALVES ARE NOT APPROVED PER THE 2017 FBC-PLUMBING |
| | SEC.606.2. |
| | 50) SHT. P4-02 - SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR THE OIL SMART PUMP SYSTEM. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 51) SHT. P5-01 - PLUMBING FIXTURE SCHEDULE - THE |
| | WASHING MACINE WASTE STACK SHALL BE A MINIMUM OF 3 INCH |
| | PER 2017 FBC-PLUMBING SEC.406.2. |
| | 52) SHT. P5-01 - DOMESTIC PUMP DETAIL - A LOW-PRESSURE |
| | CUTOFF IS REQUIRED ON THE PUMP PER 2017 FBC-PLUMBING |
| | SEC.606.5.5. |
| | 53) SHT. P6-01 - THE 3/4 INCH LINE FOR THE HOSE BIBB IN |
| | THE TRASH ROOM SHALL BE EQUIPPED WITH A SHUTOFF VALVE |
| | PER 2017 FBC-PLUMBING SEC.606.2. |
| | 54) SHT. P6-01 - SHOW THE TERMINATION POINTS OF ALL THE |
| | WATER SUPPLY LINES/ TAG ALL WATER RISERS FOR |
| | IDENTIFICATION AND SIZE ALL BRANCHES ON THE WATER |
| | RISER. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 55) SHT.P6-01 - SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR THE BOOSTER & RECIRCULATION PUMP.THE RECIRCULATION |
| | PUMP SHALL COMPLY WITH THE REQUIREMENTS OF FBC-PLUMBING |
| | SEC.607..2.1.2. |
| | 56) SHT. P6-02 - TAG ALL THE RISERS ON THE SANITARY |
| | RISER FOR IDENTIFICATION AND IDENTIFY THE FIXTURES. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 57) SHT.P6-04 - THE PUBLISHED ROOF DRAIN FLOW RATE, |
| | BASED ON THE HEAD OF WATER ABOVE THE ROOF DRAIN, SHALL |
| | BE USED TO SIZE THE STORM DRAINAGE SYSTEM IN ACCORDANCE |
| | WITH FBC-PLUMBING SECTION 1106, 1106.1, 1106.2.. SUBMIT |
| | GPM FLOW RATE CALCULATIONS FOR THE STORM DRAIANGE |
| | SYSTEM. CALCULATIONS SHALL INCLUDE PARAPET WALLS PER |
| | FBC-PLUMBING SEC.1106.4. |
| | 58) SHT. P6-04 - THERE ARE DRAINS SHOWN AS "FLOATING", |
| | AND NOT CONNECTED TO ANY PIPING. CLARIFY. |
| | 59) SHT. P6-04 - CLEANOUTS ARE REQUIRED IN THE STORM |
| | DRAINAGE SYSTEM OER FBC-PLUMBING SEC.1101.8. |
| | 60) SHT. P6-04 - SHOW THE TERMINATION POINT OF THE |
| | STORM DRAIN SYSTEM ON THE STORM SYSTEM RISER. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 61) SUBMIT A CONDENSATE RISER. THE SIZING SHALL COMPLY |
| | WITH FBC-PLUMBING SEC.314.2.2 & TABLE 314.2.2. |
| | 62) SHT. P1-01A STILLS HAS A NOTE REGARDING THE |
| | INSTALLATION OF AN AAV TO BE INSTALLED HIGH IN ROOM ON |
| | LEVEL 1. THE INSTALLATION OF AIR ADMITTANCE VALVES ARE |
| | NOT PERMITTED BELOW THE TOP FOUR BRANCH INTERVALS PER |
| | FBC-PLUMBING SEC.918.3.1. |
| | 63) SIZE THE WATER RISERS ON THE ENLARGED UNIT PLANS. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | TIM LARGE |