| 2020-04-24 19:11:34 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20011267 |
| | 4/24/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | BASED ON THE RESUBMITTED PLANS AND RESPONSE NARRATIVE, |
| | COMMENTS FROM THE 1ST REVIEW LISTED BELOW WILL BE |
| | MARKED AS "OK", "APPROVED WITH EXCEPTION" OR AS |
| | "DENIED" ACCORDINGLY. PLEASE COMPLY WITH ALL EXCEPTIONS |
| | AND COMMENTS. PLEASE NOTE THE NEW COMMENTS ATTACHED AT |
| | THE END OF THE REVIEW. |
| | |
| | 1) APPROVED WITH EXCEPTION- THE CALCULATIONS SHALL BE |
| | ELECTRONICALLY SIGNED AND SEALED BY THE ENGINEER- FL. |
| | STATUTE 471.025 AND SECTION 61G15-23.005 FAC. THE |
| | SIGNATURE AND SEAL MAY BE PLACED ON THE COVER SHEET OF |
| | THE CALCS. PLEASE SUBMIT THE ENTIRE PACKAGE AS A |
| | SEPARATE DOCUMENT APART FROM THE COMMENT RESPONSE |
| | DOCUMENT- SECTION 107.2.1 WPB. |
| | |
| | 2) OK. |
| | |
| | 3) DENIED- SHEET M5-01: PROVIDE BLOWER DOOR TESTING |
| | NOTE ON THE PLAN PER THE NARRATIVE RESPONSE. "BLOWER |
| | DOOR TESTING WILL BE CONDUCTED FOR EACH UNIT TYPE TO |
| | VERIFY THE INFILTRATION RATES MEET THE MINIMUM AIR |
| | CHANGE RATE REQUIRED FOR USE OF NATURAL VENTILATION". |
| | PROVIDE NATURAL VENTILATION CALCULATIONS FOR EACH |
| | APARTMENT MODEL- SECTION 402.2 FBC M. |
| | |
| | 4) DENIED: THE AREA OF THE 1ST FLOOR GARAGE BY THE |
| | TRANSFORMER ROOM APPEARS ISOLATED FROM THE FAN ON THE |
| | SOUTH WALL. PLEASE PLACE A NOTE THAT ON THE PLAN TO |
| | INDICATE AN EXHAUST VENTILATION TEST WILL BE PERFORMED |
| | TO INSURE THE EFFECTIVENESS OF THE SYSTEM- SECTIONS |
| | 403.3.1.2 & 403.3.1.5 FBC M.M-101A: |
| | |
| | 5) DENIED- SHEETS A1-01A & M1-01A: THE GARAGE FAN IS |
| | LOCATED IN A DRIVE AREA. PLEASE PROVIDE A MEANS OF |
| | PROTECTION FROM VEHICLE IMPACT SUCH AS CURBING OR |
| | BOLLARDS- SECTIONS 303.4 AND 304.6 FBC M. |
| | |
| | 6) OK- DEFERRED SUBMITTALS ACCEPTABLE FOR THE GARAGE CO |
| | AND NO2 SENSORS. |
| | |
| | 7) DENIED- SHEET M-101.A: A) FIRE DAMPER MISSING AT THE |
| | MAKEUP AIR DUCT PENETRATION OF THE FIRE-RATED PUMP ROOM |
| | WALL- SECTION 607.5.2 FBC M. B) THE MAKEUP AIR INLET |
| | OPENING CANNOT BE LOCATED ABOVE THE DRIVEWAY PER |
| | SECTIONS 510.6.5 AND 401.4 FBC M. A MINIMUM 10' |
| | HORIZONTAL CLEARANCE IS REQUIRED. C) VERIFY THE |
| | UNDERSIDE OF THE MAKEUP AIR DUCT WILL BE A MINIMUM 8? |
| | ABOVE THE GARAGE FLOOR- SECTION 304.6. D) THE L-3 |
| | LOUVER SHALL BE AMCA 550 RATED IN ACCORDANCE WITH |
| | SECTION 401.5 FBC M. SUBMIT MANUFACTURER?S |
| | SPECIFICATIONS FOR THE GREENHECK EHH-501X TO VERIFY |
| | COMPLIANCE. |
| | |
| | 8) OK. |
| | |
| | 9) DENIED- M1-01A: THE NOTE ON THE PLAN DOES NOT |
| | INCLUDE THE REQUIRED 10' EXHAUST TERMINATION CLEARANCE |
| | TO OPERABLE OPENINGS INTO THE BUILDING. A) THE L-4 |
| | LOUVER SHALL BE AMCA 550 RATED IN ACCORDANCE WITH |
| | SECTION 501.3.2 FBC M. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE GREENHECK EHH-501X TO VERIFY |
| | COMPLIANCE. |
| | |
| | 10, 11, 12) APPROVED WITH EXCEPTION- PLEASE PLACE A |
| | NOTE ON SHEET M0 INDICATING SEPARATE PERMITS AND PLANS |
| | WILL BE SUBMITTED FOR: A) FIRE PUMP. B) DIESEL FUEL |
| | TANK. C) FUEL PIPING. PLEASE SUBMIT THE CLARKE PUMP |
| | ROOM VENTILATION CALCULATOR AS A SEPARATE DOCUMENT |
| | APART FROM THE COMMENT RESPONSES- SECTION 107.2.1 WPB. |
| | |
| | 13) DENIED- M1-01A: FIRE DAMPER MISSING FOR THE TRASH |
| | EXHAUST DUCT PENETRATING THE FIRE-RATED TRASH ROOM |
| | WALL- SECTION 607.5.2 FBC M. |
| | |
| | 14) DENIED- M1-01A: SHOW THE LOCATIONS OF THE GRAVITY |
| | DAMPERS AND PROVIDE A NOTE ON THE PLAN INDICATING THE |
| | DAMPERS WILL BE AMCA 500D RATED PER SECTION C403.2.4.3 |
| | FBC EC. THE DAMPERS MAY BE ADDED TO THE LIST OF |
| | DEFERRED SUBMITTALS FOR THE PROJECT. A) THE L-5 O/A |
| | INTAKE LOUVER SHALL BE AMCA 550 RATED IN ACCORDANCE |
| | WITH SECTION 401.5 FBC M. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE GREENHECK EHH-501X TO VERIFY |
| | COMPLIANCE. |
| | |
| | 15) DENIED- M1-01A: AIRFLOW PERFORMANCE DATA FOR THE |
| | DAIKIN 5-TON AIR HANDLERS INDICATE THE BLOWERS CAN |
| | PRODUCE OVER 2000 CFMS DEPENDING ON THE SETTING OF THE |
| | BLOWER AND EXTERNAL STATIC PRESSURE WHICH CAN BE |
| | ADJUSTED TO PRODUCE AS MUCH AS 2340 CFMS OF SUPPLY AIR. |
| | PLEASE PROVIDE THE DUCT SMOKE DETECTORS IN THE SUPPLY |
| | AIR SYSTEMS AHU 3 & 4- SECTION 606.2.1 FBC M. |
| | |
| | 16) OK. |
| | |
| | 17) DENIED- M1-01A & B: THE EXHAUST TERMINATION |
| | LOCATION FOR THE GREASE DUCTS ARE SHOWN TO BE WITHIN |
| | THE REQUIRED 10' CLEARANCE TO THE PROPERTY LINES- |
| | SECTION 506.3.13.3 FBC M. THE EXHAUST TERMINATION |
| | LOCATION FOR SUITE 100 IS NOT SHOWN- SECTION 107.2.1 |
| | WPB. |
| | |
| | 18) APPROVED WITH EXCEPTION- M1-01A & B & M0: PLEASE |
| | PROVIDE A MASTER LIST OF ALL SEPARATELY PERMITTED |
| | SYSTEMS AND TENANT SPACES ON THE M0 PLAN, AND ADD THE |
| | KITCHEN EXHAUST AND FIRE SUPPRESSION SYSTEMS, AND WALK |
| | IN COOLERS AND FREEZERS TO THE LIST- SECTION 107.2.1 |
| | WPB. |
| | |
| | 19) OK. |
| | |
| | 20) DENIED- M1-01B: THE LIFE SAFETY DOES NOT INDICATE |
| | THAT THE COMMON WALLS SEPARATING THE PET |
| | SPA/TRANSFORMER ROOM ARE FIRE-RESISTANT RATED- TABLE |
| | 508.4 FBC B. |
| | |
| | 21) DENIED- M1-01B & M1-02B: THE INSTALLATION OF THE |
| | OUTDOOR CONDENSERS ON THE INTERIOR OF THE BUILDING WILL |
| | REQUIRE APPROVAL BY SUBMITTAL OF A MANUFACTURER'S |
| | LETTER OR INSTALLATION GUIDELINES CONFIRMING THE |
| | INSTALLATION IS APPROVED IN ACCORDANCE WITH THE LISTING |
| | AND LABELING OF THE PRODUCT- SECTION 304.1 FBC M. |
| | |
| | 22, 24, 25) APPROVED WITH EXCEPTION- M1-03B & M0: THE |
| | ENGINEER IS REQUESTING THE POOL EQUIPMENT ROOM AND ALL |
| | ASSOCIATED EQUIPMENT AND APPLIANCES, VENTILATION |
| | SYSTEM, STORAGE OF MATERIALS TO BE UNDER SEPARATE |
| | PERMIT. PLEASE PLACE A NOTE ON THE PLAN AND ADD ALL |
| | ITEMS TO THE MASTER LIST OF ALL SEPARATELY PERMITTED |
| | SYSTEMS ON THE M0 PLAN- SECTION 107.2.1 WPB. |
| | |
| | 26) OK |
| | |
| | 27) DENIED- 2ND REQUEST M1-05A: FIRE DAMPERS ARE |
| | MISSING FOR THE AHU-5 & 6 SUPPLY, RETURN, AND O/A DUCTS |
| | PENETRATING THE FIRE-RATED MECHANICAL ROOM WALLS- |
| | SECTION 607.5.2 FBC M. |
| | |
| | 28) DENIED 2ND REQUEST M1-05A: DUCT SMOKE DETECTORS ARE |
| | REQUIRED IN THE SUPPLY AIR SYSTEMS OF THE 5-TON AHU 5 & |
| | 6 SYSTEMS PER SECTION 606.2.1 FBC M. PLEASE NOTE THAT |
| | AN EXEMPTION CAN BE APPLIED IF THE MANUFACTURER'S |
| | SPECIFICATIONS INDICATE THE SYSTEMS ARE NOT CAPABLE OF |
| | PRODUCING OVER 2000 CFMS OF SUPPLY AIR. |
| | |
| | 29) DENIED- M-105A: SHOW THE LOCATIONS OF THE O/A |
| | GRAVITY DAMPERS AND PROVIDE A NOTE ON THE PLAN |
| | INDICATING THE DAMPERS WILL BE AMCA 500D RATED PER |
| | SECTION C403.2.4.3 FBC EC. THE DAMPERS MAY BE ADDED TO |
| | THE LIST OF DEFERRED SUBMITTALS FOR THE PROJECT. |
| | A) THE AD-7 RETURN GRILL CANNOT BE USED FOR O/A INTAKE- |
| | SEE SECTION 401.5 FBC M. |
| | |
| | 30) OK. |
| | |
| | 31) DENIED M-301 THROUGH M-305: REQUIRED EXHAUST |
| | VENTILATION FOR THE KITCHENS NOT SHOWN- SECTION AND |
| | TABLE 403.3.2.3 FBC M. RECIRCULATING-TYPE DOMESTIC |
| | KITCHEN EXHAUST HOODS ARE ALLOWED PER SECTION 505.1 |
| | EXCEPTION 1 FBC M. IF THIS IS THE INTENTION PLEASE |
| | PLACE A NOTE ON THE PLANS AND ADD THE HOODS TO THE |
| | DEFERRED SUBMITTALS LIST. |
| | |
| | 32) DENIED M-301 THROUGH M-305: A) PLEASE PLACE A NOTE |
| | TO INDICATE THAT DRYER EXHAUST DUCTS SHALL NOT RUN |
| | THROUGH THE RETURN PLENUMS. IT APPEARS THAT THIS IS THE |
| | CASE ON SHEET M3-02- UNITS A2D, A3, A4, B1 AND ON SHEET |
| | M3.03- UNIT B2. B) M3-01: IT APPEARS THAT THE FLOOR |
| | PLAN DRAWINGS FOR UNITS A2 AND A2.1 ARE CUT OFF. C) |
| | M3-03: IT APPEARS THAT THE DRYER EXHAUST DUCT FOR UNIT |
| | B2A IS RUNNING THROUGH AN ADJACENT APARTMENT. D) PLEASE |
| | ADD A NOTE TO INDICATE THE TOILET AND DRYER EXHAUST |
| | TERMINATIONS SHALL BE LOCATED A MINIMUM OF 3' TO |
| | OPERABLE OPENINGS INTO THE BUILDING- SECTION 501.3.1 |
| | (3) FBC M. |
| | |
| | 33) OK. |
| | 34) OK. |
| | 35) OK. |
| | 36) OK. |
| | 37) OK. |
| | 38) OK. |
| | |
| | 39) APPROVED WITH EXCEPTION: PLEASE SUBMIT THE |
| | COMMISSIONING PLAN AS A SEPARATE DOCUMENT APART FROM |
| | THE COMMENT RESPONSE DOCUMENT. PLACE A NOTE ON SHEET M0 |
| | INDICATING COMPLIANCE WITH SECTION C104.2.6 FINAL |
| | INSPECTION: |
| | THE BUILDING SHALL HAVE A FINAL INSPECTION AND SHALL |
| | NOT BE OCCUPIED UNTIL APPROVED. THE FINAL INSPECTION |
| | SHALL INCLUDE VERIFICATION OF THE INSTALLATION AND |
| | PROPER OPERATION OF ALL REQUIRED BUILDING CONTROLS, AND |
| | DOCUMENTATION VERIFYING ACTIVITIES ASSOCIATED WITH |
| | REQUIRED BUILDING COMMISSIONING HAVE BEEN CONDUCTED AND |
| | FINDINGS OF NONCOMPLIANCE CORRECTED. BUILDINGS, OR |
| | PORTIONS THEREOF, SHALL NOT BE CONSIDERED FOR A FINAL |
| | INSPECTION UNTIL THE CODE OFFICIAL HAS RECEIVED A |
| | LETTER OF TRANSMITTAL FROM THE BUILDING OWNER |
| | ACKNOWLEDGING THAT THE BUILDING OWNER HAS RECEIVED THE |
| | PRELIMINARY COMMISSIONING REPORT AS REQUIRED IN SECTION |
| | C408.2.4. |
| | |
| | 40) APPROVED WITH EXCEPTION: PLEASE PROVIDE A MASTER |
| | LIST OF DEFERRED SUBMITTALS SHEET M0. DEFERRED |
| | SUBMITTALS: REQUIRED SUBMITTALS LISTED BELOW SHALL HAVE |
| | SHOP DRAWING STAMPS BY THE EOR AND EITHER BE SUBMITTED |
| | TO THE BUILDING DEPARTMENT, OR BE IN THE FIELD AT TIME |
| | OF INSPECTION. PLEASE INCLUDE: |
| | A) FIRE DAMPERS AND FIRE/SMOKE DAMPERS. |
| | B) MOTORIZED AND GRAVITY DAMPERS |
| | C) DUCT SMOKE DETECTORS |
| | D) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES |
| | INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT |
| | APPROVALS AND/OR MIAMI-DADE NOA'S |
| | F) AC STAND NOA'S OR FL. PRODUCT APPROVALS |
| | G) C0, N02, & CO2 SENSORS |
| | H) CLOTHES DRYERS |
| | I) X-VENT BATHROOM AND DRYER EXHAUST WALL CAPS |
| | J) COOKING APPLIANCES |
| | K) SIGNED AND SEALED SITE-SPECIFIC WIND LOAD |
| | ENGINEERING FOR INSTALLATION OF ALL ROOF TOP MECHANICAL |
| | EQUIPMENT. |
| | L) O/A DAMPERS. |
| | |
| | NEW COMMENTS. |
| | |
| | 1) SHEET M1-01A: POSITIVE PRESSURIZATION MUST BE |
| | PROVIDED AND MAINTAINED IN THE BIKE STORAGE ROOM |
| | ADJACENT TO THE ENCLOSED GARAGE. PLEASE SEE SECTION 202 |
| | FOR DEFINITION OF OCCUPIED SPACE AND SECTION 404.3 FBC |
| | M AND PROVIDE A SYSTEM FOR THE ROOM THAT MEETS |
| | COMPLIANCE |
| | |
| | 2) M1-04A: CLARIFY HOW THE JANITOR'S CLOSET WILL BE |
| | VENTILATED AND INDICATE HOW MAKEUP AIR IS BEING |
| | PROVIDED TO THE RESTROOMS AND TO THE CLOSET- SECTION |
| | 107.2.1 WPB. A) PROVIDE THE SEQUENCE OF OPERATION FOR |
| | THE FANS- SECTION 401.3 AND TABLE 403.3.1.1 FBC M. |
| | |
| | 3) M1-05A & M5-01: AHU-7 IS MISLABELED AS A SYSTEM |
| | SERVING THE LOUNGE- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |