| Plan Review Notes For Permit 20011267 |
| Permit Number |
20011267 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-06-12 08:18:58 | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE GAS PRESSURE | | | REGULATORS.REGULATORS INSTALLED ON THE EXTERIOR OF THE | | | BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION.2017 FBC-FUEL GAS SEC.410.1. | | | 2) SHT. P4-01 - TYPICAL DIRT LEG DETAIL - UPFEED TO | | | EQUIPMENT DIAGRAM - THE DRAWING IS INCOMPLETE. | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS | | | EQUIPMENT. FBC-FUEL GAS SEC.301.3. |
|