| 2020-05-18 11:19:17 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5.CORRECTED. |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | 9. CORRECTED. |
| | 10. CORRECTED. |
| | 11. CORRECTED. |
| | 12. SHEET E2-04 SHOWS LIGHTING BEING INSTALLED WITHIN 5 |
| | FEET OF THE POOL. WHAT IS THE HEIGHT OF THESE FIXTURES? |
| | LIGHTING SHALL NOT BE INSTALLED AT A HEIGHT LESS THAN |
| | 12 FEET WHEN WITHIN 5 FEET OF THE INSIDE WALL OF THE |
| | POOL. PROVIDE CLARIFICATION AND/OR CORRECTION. NEC |
| | 680.22(B)(1) (RESPONSE INDICATES THAT THE LIGHT |
| | FIXTURES WILL BE INSTALLED AT A HEIGHT ABOVE POOL DECK |
| | OF AT LEAST 7 FEET. THIS IS NOT CODE COMPLIANT, A |
| | MINIMUM OF 12 FEET IS REQUIRED. PROVIDE CLARIFICATION |
| | AND/OR CORRECTION.) |
| | 13. CORRECTED. |
| | 14. CORRECTED. |
| | 15. CORRECTED. |
| | 16. CORRECTED. |
| | 17. FOR POOL ROOM EQUIPMENT, PROVIDE ENCLOSURE TYPES |
| | DESIGNED TO PROTECT AGAINST CORROSIVE ENVIRONMENTS. NEC |
| | TABLE 110.28 (DUE TO THE CORROSIVE ENVIRONMENTS OF THE |
| | POOL EQUIPMENT ROOM, A MINIMUM OF NEMA 3X IS REQUIRED. |
| | PROVIDE CORRECTION.) |
| | 18. CORRECTED. |
| | 19. CORRECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |