Plan Review Notes
Plan Review Notes For Permit 20011267
Permit Number 20011267
Review Stop E
Sequence Number 2
Notes
Date Text
2020-05-18 11:19:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5.CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. SHEET E2-04 SHOWS LIGHTING BEING INSTALLED WITHIN 5
 FEET OF THE POOL. WHAT IS THE HEIGHT OF THESE FIXTURES?
 LIGHTING SHALL NOT BE INSTALLED AT A HEIGHT LESS THAN
 12 FEET WHEN WITHIN 5 FEET OF THE INSIDE WALL OF THE
 POOL. PROVIDE CLARIFICATION AND/OR CORRECTION. NEC
 680.22(B)(1) (RESPONSE INDICATES THAT THE LIGHT
 FIXTURES WILL BE INSTALLED AT A HEIGHT ABOVE POOL DECK
 OF AT LEAST 7 FEET. THIS IS NOT CODE COMPLIANT, A
 MINIMUM OF 12 FEET IS REQUIRED. PROVIDE CLARIFICATION
 AND/OR CORRECTION.)
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
 16. CORRECTED.
 17. FOR POOL ROOM EQUIPMENT, PROVIDE ENCLOSURE TYPES
 DESIGNED TO PROTECT AGAINST CORROSIVE ENVIRONMENTS. NEC
 TABLE 110.28 (DUE TO THE CORROSIVE ENVIRONMENTS OF THE
 POOL EQUIPMENT ROOM, A MINIMUM OF NEMA 3X IS REQUIRED.
 PROVIDE CORRECTION.)
 18. CORRECTED.
 19. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  