Plan Review Notes
Plan Review Notes For Permit 20011267
Permit Number 20011267
Review Stop B
Sequence Number 2
Notes
Date Text
2020-05-11 14:38:13PLAN REVIEW COMMENTS
 THRESHOLD BUILDING
 8 STORY APARTMENT BUILDING (MIXED USE M, S-2, R-2, A-3
 AND B)
 CONST. TYPE 1-A, SPRINKLERED
 170 MPH, EXPOSURE "D"
 FLOOD ZONE "X"
 625 S. OLIVE AVE.
 PERMIT #20011267
  
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVISO. WILL COMPLY WITH AIPP BEFORE RECEIVING C.O.
  
 2) PARTIALLY COMPLIED. AT A MINIMUM ALL STRUCTURAL
 PLANS THAT ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ENGINEER OF RECORD ARE REQUIRED TO HAVE THE THRESHOLD
 BUILDING STATEMENT. A COMPLETE SET OF THRESHOLD
 DOCUMENTS IS REQUIRED. THE CONTRACTOR'S AND OWNER'S
 NOTARIZED THRESHOLD DOCUMENTS WERE NOT SUBMITTED. THE
 CONTRACTOR, KAST CONSTRUCTION, HAS DONE SIMILAR
 PROJECTS IN THIS JURISDICTION SO A JOB SUMMARY IS NOT
 REQUIRED. A RESUME OF THE SPECIAL INSPECTOR'S PREVIOUS
 INSPECTION EXPERIENCE WAS NOT SUBMITTED. THE THRESHOLD
 BUILDING COMPLIANCE STATEMENT IS REQUIRED ON ALL OF THE
 STRUCTURAL SHEETS, INCLUDING SCHEDULES AND DETAILS.
 THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE CURRENT ( OCTOBER
 2018 ) CITY GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING THRESHOLD/SPECIAL INSPECTORS AND RESIDENT
 INSPECTORS.
  
 3) COMPLIED. LETTER FROM GEOTECHNICAL ENGINEER RE:
 INCREASE SOIL CAPACITY TO 8,000 PSF WAS SUBMITTED WITH
 FOUNDATION ONLY PERMIT, #20020004.
  
 4) COMPLIED. MOT AND CONSTRUCTION SAFEGUARD PLAN
 SUBMITTED WITH FOUNDATION ONLY PERMIT, #20020004.
  
 5) COMPLIED. ONE OF THE ELEVATORS IS SHOWN TO COMPLY
 WITH FBC 3002.4.
  
 6) COMPLIED. THE TRASH CHUTE DISCHARGE ROOM HAS BEEN
 GIVEN A 2 HOUR FIRE RATING.
  
 7) PARTICALLY COMPLIED. THE EXIT PASSAGEWAY AT STAIR 01
 WAS RELABELED AS AN EXIT PASSAGEWAY. PLEASE ADD A NOTE
 STATING THAT PENETRATIONS INTO OR THROUGH AN EXIT
 PASSAGEWAY ARE PROHIBITED EXCEPT FOR EQUIPMENT AND
 OTHER ITEMS SERVING THE EXIT PASSAGEWAY IN ACCORDANCE
 WITH FBC 1024.6. ON SHEET A1-0 THE NOTE CALLING THIS AN
 EGRESS AND MOVE IN CORRIDOR NEEDS TO BE REPLACED WITH
 THE EXIT PASSAGEWAY LABEL AND ITS NOTES.
  
 8) COMPLIED. PROVIDE A SITE PLAN WITH ELEVATIONS SHOWN
 IN NAVD 88. THERE WAS ONE WITH THE FOUNDATION PLAN, BUT
 IT APPEARS TO BE MISSING FROM THESE DOCUMENTS. FBC
 107.2.1.2
 PLEASE REVIEW THE ELEVATIONS OF THE GRADE AROUND THE
 EXTERIOR OF THE BUILDING AND COMPARE THEM WITH THE
 FLOOR ELEVATION (11.97') OF THE BUILDING TO MAKE SURE
 THAT THE EXITS DISCHARGE AT GRADE AND THE ELEVATIONS
 AND SLOPES OF LANDINGS AND WALK WAYS WILL MEET THE
 RUNNING SLOPE AND CROSS SLOPE REQUIREMENTS OF THE
 FLORIDA ACCESSIBILITY CODE SECTION 403.
  
 9) NOT COMPLIED. THE ORIENTATIONS DO NOT APPEAR TO BE
 CORRECT. AR-01 IS AT THE SOUTH OF THE BUILDING LOOKING
 WEST. AR-02 IS AT THE NORTH OF THE BUILDING LOOKING
 WEST. AR-03 IS AT THE NORTH OF THE BUILDING LOOKING
 EAST. AR-04 IS AT THE SOUTH OF THE BUILDING LOOKING
 EAST. THE AR-RENDERINGS APPEAR TO BE MISLABELED. PLEASE
 CLARIFY. FBC 107.2.1
  
 10) NOT APPLICABLE. FBC TABLE 602 REQUIRES MERCANTILE
 OCCUPANCIES TO HAVE 2 HOUR FIRE RESISTANCE RATED
 EXTERIOR WALLS FOR LESS THAN 10 FT OF FIRE SEPARATION
 DISTANCE. THIS IS NOT REFLECTED IN THE CODE DATA ON
 SHEET CD-1. HOWEVER, THIS DOES NOT APPEAR TO BE AN
 ISSUE FOR YOUR PROJECT.
  
 11) COMPLIED. HOWEVER, THE WIND VELOCITY FOR THIS
 PROJECT IS 170 MPH NOT 180 MPH. CHANGED FROM BROWARD
 COUNTY TO PALM BEACH COUNTY.
  
 12) COMPLIED. THE RED DASHED CIRCLES WERE REMOVED.
  
 13) NO RESPONSE LETTER WAS SUBMITTED TO ADDRESS THIS
 QUESTION. THERE IS A STAIR #04 SHOWN ON THE PLANS
 BETWEEN THE 2ND AND 3RD LEVELS OF THE PARKING GARAGE
 WITH A NOTE (WHICH IS MISLABELED AS STAIR 03 ON CD-02)
 THAT IT IS TO PREVENT A DEAD END CONDITION AT LEVEL 3.
 PLEASE CLARIFY.
  
 14) COMPLIED. THE COMMERCIAL AREAS ON THE GROUND FLOOR
 USED A-2 TO DETERMINE OCCUPANT LOADS.
  
 15) COMPLIED. THE COVERED OUTDOOR RESTAURANT SEATING
 RELABELED AS A-2.
  
 16) COMPLIED. ELEVATOR 1 IS SHOWN TO MEET STRETCHER
 REQUIREMENT.
  
 17) NO RESPOSE LETTER ADDRESSING COMMENT WAS SUBMITTED.
 ADD A NOTE ON THE GROUND FLOOR PLANS WITH A SHADED AREA
 TO STATE THAT A MINIMUM OVERHEAD CLEARANCE OF 8' -2" IS
 REQUIRED IN THAT AREA. VERIFY THE REQUIRED VERTICAL
 CLEARANCE OF 98 INCHES FOR THE VAN PARKING SPACE,
 ACCESS AISLE AND VEHICULAR ROUTE SERVING IT AS REQUIRED
 BY FBC ACCESSIBILITY SECTION 502.5.
  
 18) NOT COMPLIED. THE PARKING TABLE ON A1-01 WAS
 CORRECTED, BUT NOT THE ONE ON GN-00. THE PARKING DATA
 ON SHEET GN-00 HAS 20 COMMERCIAL SPACES AND 183
 RESIDENTIAL SPACES. TABLE 208.2 IN THE FBC
 ACCESSIBILITY REQUIRES A MINIMUM OF 1 ACCESSIBLE
 PARKING SPACE WHEN THE TOTAL NUMBER OF SPACES PROVIDED
 IS 1 TO 25. THE FAIR HOUSING GUIDELINES REQUIRE AT
 LEAST 2 PERCENT OF THE COVERED RESIDENTIAL UNITS TO
 HAVE ACCESSIBLE PARKING WHICH IS 4 SPACES. THIS PROJECT
 IS REQUIRED TO HAVE A MINIMUM OF 5 ACCESSIBLE PARKING
 SPACES. THE PLANS SHOW ONLY 4 ACCESSIBLE SPACES.
 SECTION 208.2.4 REQUIRES AT LEAST ONE VAN PARKING SPACE
 COMPLYING WITH SECTION 502 FOR EVERY SIX OR FRACTION OF
 SIX REQUIRED ACCESSIBLE SPACES.
  
 19) SEE COMMENT #7.
  
 20) COMPLIED. THE EXIT DOOR SIZE AND CALCULATIONS ARE
 NOT PROVIDED FOR THE EXIT DISCHARGE DOOR AT THE EXIT
 PASSAGEWAY FOR STAIR #01 ON SHEET CD-01.
  
 21) COMPLIED. ON SHEET CD-04, DEAD END PATH A IS NOT
 IDENTIFIED. FBC 107.2.1
  
 22) COMPLIED. A PORTION OF PATH B IS MISSING ON THE
 DRAWING. FBC 107.2.1
  
 23) COMPLIED. TRAVEL DISTANCE WAS CORRECTED.
  
 24) COMPLIED. SHOW THE TRAVEL PATHS FROM THE POOL
 DECK/POOL AREA TO THE EXITS. FBC 1017.3
  
 25) COMPLIED. THE NUMBER OF OCCUPANTS THAT WILL BE
 USING EACH OF EXITS. FBC SECTION 1006 AND FBC 107.2.1.2
  
 26) COMPLIED. THE OCCUPANT LOADS ARE TOTALS AND THE
 DISPERSION OF OCCUPANTS TO EACH OF THE EXITS IS NOT
 SHOWN ON THE PLANS. SHOW THE NUMBER OF OCCUPANTS FOR
 EACH ROOM OR AREA AND WHICH EXIT THEY WILL USE. FBC
 107.2.1
  
 27) COMPLIED. SHOW THE EGRESS PATHS AND EXIT DOORS FOR
 THE OUTDOOR TERRACE, CLUBROOM, FITNESS ROOM AND AMENITY
 DECK SHOWN ON SHEET CD-04. FBC 1007
  
 28) COMPLIED. THE EXIT DOOR TO STAIR #03 FROM THE POOL
 DECK ON LEVEL 4 IS SPECIFIED WITH A WITH A 19 INCH
 CLEAR WIDTH. FBC 1010.1.1 REQUIRES A MINIMUM CLEAR
 OPENING WIDTH OF 32 INCHES. THE SIZES FOR THE DOORS TO
 THIS STAIR ARE NOT PROVIDED ON LEVELS 2 AND 3. FBC
 107.2.1
  
 29) NOT COMPLIED. ON SHEET CD-02, THE EXIT DOOR TO
 STAIR 01 HAS INCORRECT AND MISSING INFORMATION. FBC
 107.2.1
  
 30) COMPLIED. SHOW THE EXIT PATHS OF TRAVEL AND TRAVEL
 DISTANCES FOR EACH LEVEL OF THE GARAGE. FBC 1006
  
 31) COMPLIED. THE FIRST LEVEL OF THE PARKING GARAGE IS
 ENCLOSED WITH MECHANICAL VENTILATION REQUIRED. THE
 SECOND AND THIRD LEVELS ARE AN OPEN GARAGE. FBC TABLE
 705.8 FOOTNOTE "G" ALLOWS UNLIMITED OPENINGS IN OPEN
 PARKING STRUCTURES WHICH APPLIES TO LEVEL 2 AND 3 OF
 THE GARAGE. THE WEST ELEVATION IS 10'-1" FROM THE
 PROPERTY LINE WHICH IS ALSO THE FIRE SEPARATION
 DISTANCE. TABLE 705.8 ALLOWS A SPRINKLERED BUILDING
 THAT HAS 10 FEET TO 15 FEET OF FIRE SEPARATION DISTANCE
 TO HAVE 45 PERCENT OF THE WALL AREA OF EACH STORY TO BE
 OPEN. PLEASE PROVIDE THE CALCULATIONS FOR THE ALLOWABLE
 OPEN AREA OF EACH OF STORIES OTHER THAN THE OPEN LEVELS
 OF THE PARKING GARAGE FOR THE WEST ELEVATION AND THE
 PORTION OF THE SOUTH ELEVATION THAT IS 10' 1-7/8" FROM
 THE PROPERTY LINE TO SHOW COMPLIANCE WITH FBC 705.8.
  
 32) NOT COMPLIED. THE HANDRAIL EXTENSION AT THE BOTTOM
 OF STAIRS ARE REQUIRED TO EXTEND AT THE SLOPE OF THE
 STAIR FLIGHT FOR A HORIZONTAL DISTANCE AT LEAST EQUAL
 TO ONE TREAD DEPTH BEYOND THE LAST RISER NOSING. SEE
 FBC ACCESSIBILITY SECTION 505.10.3. IT IS SHOWN WITH A
 HORIZONTAL EXTENSION ON THE STAIR SECTION ON SHEETS
 A7-01, A7-03
  
 33) COMPLIED. FBC 913.2.1 REQUIRES THE FIRE PUMP ROOM
 TO BE SEPARATED FROM ALL OTHER AREAS OF THE BUILDING BY
 2-HOUR FIRE BARRIERS.
  
 34) COMPLIED. THE TRASH CHUTE DISCHARGE ROOM HAS A 2
 HOUR FIRE RATING.
  
 35) NOT COMPLIED. HANDRAIL IS SHOWN WITH A HORIZONTAL
 EXTENSION RATHER THAN EXTENDING AT THE SLOPE OF THE
 STAIRS. WITH A STAIR NUMBER FOUR ON SHEET A7-04 DOES
 NOT HAVE THE REQUIRED HANDRAIL EXTENSION AT THE BOTTOM
 OF STAIRS. HANDRAILS ARE REQUIRED TO EXTEND AT THE
 SLOPE OF THE STAIR FLIGHT FOR A HORIZONTAL DISTANCE AT
 LEAST EQUAL TO ONE TREAD DEPTH BEYOND THE LAST RISER
 NOSING. SEE FBC ACCESSIBILITY SECTION 505.10.3.
  
 36) COMPLIED. PROVIDE AREA TABULATIONS FOR THE ENTIRE
 BUILDING. FBC 107.2.1.2
  
 37) NOT COMPLIED. REQUEST TO DEFER HAS NOT BEEN
 RECEIVED. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE
 DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE
 SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT
 BEFORE THEY CAN BE INSTALLED.
  
 38) NOT COMPLIED. REQUEST TO DEFER HAS NOT BEEN
 RECEIVED. FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 39) NOT COMPLIED. SHOW COMPLIANCE FBC ACCESSIBILITY
 SECTION 242 FOR ACCESSIBLE ENTRY INTO THE POOL OR
 SPECIFY ON THE PLANS WHY IT IS NOT REQUIRED. COMMUNITY
 POOLS THAT ARE ASSOCIATED WITH A PRIVATE RESIDENTIAL
 COMMUNITY THAT DO NOT RECEIVE GOVERNMENTAL FINANCIAL
 ASSISTANCE OR SPONSORSHIP AND ARE LIMITED TO THE
 EXCLUSIVE OF RESIDENTS AND THEIR GUESTS ARE NOT COVERED
 BY THE ADA ACCESSIBILITY REQUIREMENTS, INCLUDING
 PROVISIONS FOR POOL LIFTS OR SLOPED ENTRIES. IF A
 SWIMMING POOL LOCATED IN A RESIDENTIAL COMMUNITY IS
 MADE AVAILABLE TO THE PUBLIC FOR RENTAL OR USE IT IS
 REQUIRED TO COMPLY WITH TITLE II OF THE ADA. SPECIFY ON
 THE PLANS THE FORMER OR SHOW COMPLIANCE WITH THE LATTER
 STATEMENTS. SEE DECLARATORY STATEMENT, DS 2013-011.
  
 40) NOT COMPLIED. SEPARATE PERMITS, REVIEWS AND FEES
 ARE REQUIRED FOR SOME ITEMS THAT MAY HAVE BEEN INCLUDED
 IN THE VALUE FOR THIS PROJECT. ITEMS SUCH AS FIRE
 ALARM, FIRE SPRINKLER, LOW VOLTAGE, LANDSCAPING,
 IRRIGATION AND ALL ITEMS OTHER THAN BUILDING,
 MECHANICAL, ELECTRIC AND PLUMBING. PLEASE PROVIDE A
 COST BREAKDOWN SO THAT WE CAN DEDUCT THESE ITEMS FROM
 THE PERMIT VALUE SO THAT YOU WILL NOT BE CHARGED TWICE
 FOR THE SAME ITEM.
  
 41) COMPLIED. THE REST./RETAIL AREAS ON THE GROUND
 FLOOR HAVE DOORS THAT OPEN INTO THE PARKING GARAGE. IT
 APPEARS THAT THESE ARE MEANT TO BE REQUIRED EXITS.
 TABLE 508.4 REQUIRES A ONE HOUR FIRE SEPARATION BETWEEN
 S-2 AND M OR B OCCUPANCIES IN A SPRINKLERED BUILDING.
 IF THESE ARE REQUIRED EXITS THEY WILL BE REQUIRED TO BE
 CONNECTED TO A ONE HOUR RATED CORRIDOR SEPARATING THEM
 FROM THE PARKING GARAGE AND DISCHARGING TO THE EXTERIOR
 OF THE BUILDING.
  
 42) NEW COMMENT. WIND VELOCITY IS SPECIFIED AS 180 MPH
 ON CD 01- CD06 PLANS IN BUILDING CODE DATA UNDER RISK
 CATEGORY. THE STRUCTURAL PLANS SPECIFY A 175 MPH VULT
 WINDSPEED. THE ACTUAL VULT WINDSPEED FOR WEST PALM
 BEACH IS 170 MPH. CITY AMENDMENTS SECTION 120. PLEASE
 COORDINATE.
  
 43) THE DIAGONAL DISTANCE FOR SUITE 300 ON THE GROUND
 LEVEL DID NOT USE THE MAXIMUM OVERALL DIAGONAL
 DIMENSION OF THE AREA TO DETERMINE EXIT SEPARATION
 DISTANCE. PLEASE CORRECT. FBC 1007.1.1
  
 44) THE 1/3 OF THE DIAGONAL DISTANCE IN THE LEASING
 AREA IS INCORRECT. ONE THIRD OF 80'-4" IS 26'-9 ". FBC
 107.2.1
  
 45) THE EXIT TRAVEL DISTANCE FOR PATH A AT LEVEL 01
 SHOULD BE FROM THE MOST REMOTE POINT TO THE NEAREST
 EXIT. IT APPEARS THAT THE NORTHWEST CORNER OF THE BIKE
 STORAGE AREA WOULD BE THE MOST REMOTE POINT. FBC 1017.3
  
 46) PLEASE PROVIDE A RESPONSE LETTER ADDRESSING HOW
 EACH OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  