| 2020-05-11 14:38:13 | PLAN REVIEW COMMENTS |
| | THRESHOLD BUILDING |
| | 8 STORY APARTMENT BUILDING (MIXED USE M, S-2, R-2, A-3 |
| | AND B) |
| | CONST. TYPE 1-A, SPRINKLERED |
| | 170 MPH, EXPOSURE "D" |
| | FLOOD ZONE "X" |
| | 625 S. OLIVE AVE. |
| | PERMIT #20011267 |
| | |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) PROVISO. WILL COMPLY WITH AIPP BEFORE RECEIVING C.O. |
| | |
| | 2) PARTIALLY COMPLIED. AT A MINIMUM ALL STRUCTURAL |
| | PLANS THAT ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ENGINEER OF RECORD ARE REQUIRED TO HAVE THE THRESHOLD |
| | BUILDING STATEMENT. A COMPLETE SET OF THRESHOLD |
| | DOCUMENTS IS REQUIRED. THE CONTRACTOR'S AND OWNER'S |
| | NOTARIZED THRESHOLD DOCUMENTS WERE NOT SUBMITTED. THE |
| | CONTRACTOR, KAST CONSTRUCTION, HAS DONE SIMILAR |
| | PROJECTS IN THIS JURISDICTION SO A JOB SUMMARY IS NOT |
| | REQUIRED. A RESUME OF THE SPECIAL INSPECTOR'S PREVIOUS |
| | INSPECTION EXPERIENCE WAS NOT SUBMITTED. THE THRESHOLD |
| | BUILDING COMPLIANCE STATEMENT IS REQUIRED ON ALL OF THE |
| | STRUCTURAL SHEETS, INCLUDING SCHEDULES AND DETAILS. |
| | THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION |
| | PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) |
| | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED |
| | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED |
| | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. |
| | C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT |
| | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. |
| | F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE. |
| | G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR |
| | THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS |
| | REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, |
| | APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND |
| | CEILINGS. |
| | J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL |
| | BE HAPPY TO SEND YOU A COPY OF THE CURRENT ( OCTOBER |
| | 2018 ) CITY GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING THRESHOLD/SPECIAL INSPECTORS AND RESIDENT |
| | INSPECTORS. |
| | |
| | 3) COMPLIED. LETTER FROM GEOTECHNICAL ENGINEER RE: |
| | INCREASE SOIL CAPACITY TO 8,000 PSF WAS SUBMITTED WITH |
| | FOUNDATION ONLY PERMIT, #20020004. |
| | |
| | 4) COMPLIED. MOT AND CONSTRUCTION SAFEGUARD PLAN |
| | SUBMITTED WITH FOUNDATION ONLY PERMIT, #20020004. |
| | |
| | 5) COMPLIED. ONE OF THE ELEVATORS IS SHOWN TO COMPLY |
| | WITH FBC 3002.4. |
| | |
| | 6) COMPLIED. THE TRASH CHUTE DISCHARGE ROOM HAS BEEN |
| | GIVEN A 2 HOUR FIRE RATING. |
| | |
| | 7) PARTICALLY COMPLIED. THE EXIT PASSAGEWAY AT STAIR 01 |
| | WAS RELABELED AS AN EXIT PASSAGEWAY. PLEASE ADD A NOTE |
| | STATING THAT PENETRATIONS INTO OR THROUGH AN EXIT |
| | PASSAGEWAY ARE PROHIBITED EXCEPT FOR EQUIPMENT AND |
| | OTHER ITEMS SERVING THE EXIT PASSAGEWAY IN ACCORDANCE |
| | WITH FBC 1024.6. ON SHEET A1-0 THE NOTE CALLING THIS AN |
| | EGRESS AND MOVE IN CORRIDOR NEEDS TO BE REPLACED WITH |
| | THE EXIT PASSAGEWAY LABEL AND ITS NOTES. |
| | |
| | 8) COMPLIED. PROVIDE A SITE PLAN WITH ELEVATIONS SHOWN |
| | IN NAVD 88. THERE WAS ONE WITH THE FOUNDATION PLAN, BUT |
| | IT APPEARS TO BE MISSING FROM THESE DOCUMENTS. FBC |
| | 107.2.1.2 |
| | PLEASE REVIEW THE ELEVATIONS OF THE GRADE AROUND THE |
| | EXTERIOR OF THE BUILDING AND COMPARE THEM WITH THE |
| | FLOOR ELEVATION (11.97') OF THE BUILDING TO MAKE SURE |
| | THAT THE EXITS DISCHARGE AT GRADE AND THE ELEVATIONS |
| | AND SLOPES OF LANDINGS AND WALK WAYS WILL MEET THE |
| | RUNNING SLOPE AND CROSS SLOPE REQUIREMENTS OF THE |
| | FLORIDA ACCESSIBILITY CODE SECTION 403. |
| | |
| | 9) NOT COMPLIED. THE ORIENTATIONS DO NOT APPEAR TO BE |
| | CORRECT. AR-01 IS AT THE SOUTH OF THE BUILDING LOOKING |
| | WEST. AR-02 IS AT THE NORTH OF THE BUILDING LOOKING |
| | WEST. AR-03 IS AT THE NORTH OF THE BUILDING LOOKING |
| | EAST. AR-04 IS AT THE SOUTH OF THE BUILDING LOOKING |
| | EAST. THE AR-RENDERINGS APPEAR TO BE MISLABELED. PLEASE |
| | CLARIFY. FBC 107.2.1 |
| | |
| | 10) NOT APPLICABLE. FBC TABLE 602 REQUIRES MERCANTILE |
| | OCCUPANCIES TO HAVE 2 HOUR FIRE RESISTANCE RATED |
| | EXTERIOR WALLS FOR LESS THAN 10 FT OF FIRE SEPARATION |
| | DISTANCE. THIS IS NOT REFLECTED IN THE CODE DATA ON |
| | SHEET CD-1. HOWEVER, THIS DOES NOT APPEAR TO BE AN |
| | ISSUE FOR YOUR PROJECT. |
| | |
| | 11) COMPLIED. HOWEVER, THE WIND VELOCITY FOR THIS |
| | PROJECT IS 170 MPH NOT 180 MPH. CHANGED FROM BROWARD |
| | COUNTY TO PALM BEACH COUNTY. |
| | |
| | 12) COMPLIED. THE RED DASHED CIRCLES WERE REMOVED. |
| | |
| | 13) NO RESPONSE LETTER WAS SUBMITTED TO ADDRESS THIS |
| | QUESTION. THERE IS A STAIR #04 SHOWN ON THE PLANS |
| | BETWEEN THE 2ND AND 3RD LEVELS OF THE PARKING GARAGE |
| | WITH A NOTE (WHICH IS MISLABELED AS STAIR 03 ON CD-02) |
| | THAT IT IS TO PREVENT A DEAD END CONDITION AT LEVEL 3. |
| | PLEASE CLARIFY. |
| | |
| | 14) COMPLIED. THE COMMERCIAL AREAS ON THE GROUND FLOOR |
| | USED A-2 TO DETERMINE OCCUPANT LOADS. |
| | |
| | 15) COMPLIED. THE COVERED OUTDOOR RESTAURANT SEATING |
| | RELABELED AS A-2. |
| | |
| | 16) COMPLIED. ELEVATOR 1 IS SHOWN TO MEET STRETCHER |
| | REQUIREMENT. |
| | |
| | 17) NO RESPOSE LETTER ADDRESSING COMMENT WAS SUBMITTED. |
| | ADD A NOTE ON THE GROUND FLOOR PLANS WITH A SHADED AREA |
| | TO STATE THAT A MINIMUM OVERHEAD CLEARANCE OF 8' -2" IS |
| | REQUIRED IN THAT AREA. VERIFY THE REQUIRED VERTICAL |
| | CLEARANCE OF 98 INCHES FOR THE VAN PARKING SPACE, |
| | ACCESS AISLE AND VEHICULAR ROUTE SERVING IT AS REQUIRED |
| | BY FBC ACCESSIBILITY SECTION 502.5. |
| | |
| | 18) NOT COMPLIED. THE PARKING TABLE ON A1-01 WAS |
| | CORRECTED, BUT NOT THE ONE ON GN-00. THE PARKING DATA |
| | ON SHEET GN-00 HAS 20 COMMERCIAL SPACES AND 183 |
| | RESIDENTIAL SPACES. TABLE 208.2 IN THE FBC |
| | ACCESSIBILITY REQUIRES A MINIMUM OF 1 ACCESSIBLE |
| | PARKING SPACE WHEN THE TOTAL NUMBER OF SPACES PROVIDED |
| | IS 1 TO 25. THE FAIR HOUSING GUIDELINES REQUIRE AT |
| | LEAST 2 PERCENT OF THE COVERED RESIDENTIAL UNITS TO |
| | HAVE ACCESSIBLE PARKING WHICH IS 4 SPACES. THIS PROJECT |
| | IS REQUIRED TO HAVE A MINIMUM OF 5 ACCESSIBLE PARKING |
| | SPACES. THE PLANS SHOW ONLY 4 ACCESSIBLE SPACES. |
| | SECTION 208.2.4 REQUIRES AT LEAST ONE VAN PARKING SPACE |
| | COMPLYING WITH SECTION 502 FOR EVERY SIX OR FRACTION OF |
| | SIX REQUIRED ACCESSIBLE SPACES. |
| | |
| | 19) SEE COMMENT #7. |
| | |
| | 20) COMPLIED. THE EXIT DOOR SIZE AND CALCULATIONS ARE |
| | NOT PROVIDED FOR THE EXIT DISCHARGE DOOR AT THE EXIT |
| | PASSAGEWAY FOR STAIR #01 ON SHEET CD-01. |
| | |
| | 21) COMPLIED. ON SHEET CD-04, DEAD END PATH A IS NOT |
| | IDENTIFIED. FBC 107.2.1 |
| | |
| | 22) COMPLIED. A PORTION OF PATH B IS MISSING ON THE |
| | DRAWING. FBC 107.2.1 |
| | |
| | 23) COMPLIED. TRAVEL DISTANCE WAS CORRECTED. |
| | |
| | 24) COMPLIED. SHOW THE TRAVEL PATHS FROM THE POOL |
| | DECK/POOL AREA TO THE EXITS. FBC 1017.3 |
| | |
| | 25) COMPLIED. THE NUMBER OF OCCUPANTS THAT WILL BE |
| | USING EACH OF EXITS. FBC SECTION 1006 AND FBC 107.2.1.2 |
| | |
| | 26) COMPLIED. THE OCCUPANT LOADS ARE TOTALS AND THE |
| | DISPERSION OF OCCUPANTS TO EACH OF THE EXITS IS NOT |
| | SHOWN ON THE PLANS. SHOW THE NUMBER OF OCCUPANTS FOR |
| | EACH ROOM OR AREA AND WHICH EXIT THEY WILL USE. FBC |
| | 107.2.1 |
| | |
| | 27) COMPLIED. SHOW THE EGRESS PATHS AND EXIT DOORS FOR |
| | THE OUTDOOR TERRACE, CLUBROOM, FITNESS ROOM AND AMENITY |
| | DECK SHOWN ON SHEET CD-04. FBC 1007 |
| | |
| | 28) COMPLIED. THE EXIT DOOR TO STAIR #03 FROM THE POOL |
| | DECK ON LEVEL 4 IS SPECIFIED WITH A WITH A 19 INCH |
| | CLEAR WIDTH. FBC 1010.1.1 REQUIRES A MINIMUM CLEAR |
| | OPENING WIDTH OF 32 INCHES. THE SIZES FOR THE DOORS TO |
| | THIS STAIR ARE NOT PROVIDED ON LEVELS 2 AND 3. FBC |
| | 107.2.1 |
| | |
| | 29) NOT COMPLIED. ON SHEET CD-02, THE EXIT DOOR TO |
| | STAIR 01 HAS INCORRECT AND MISSING INFORMATION. FBC |
| | 107.2.1 |
| | |
| | 30) COMPLIED. SHOW THE EXIT PATHS OF TRAVEL AND TRAVEL |
| | DISTANCES FOR EACH LEVEL OF THE GARAGE. FBC 1006 |
| | |
| | 31) COMPLIED. THE FIRST LEVEL OF THE PARKING GARAGE IS |
| | ENCLOSED WITH MECHANICAL VENTILATION REQUIRED. THE |
| | SECOND AND THIRD LEVELS ARE AN OPEN GARAGE. FBC TABLE |
| | 705.8 FOOTNOTE "G" ALLOWS UNLIMITED OPENINGS IN OPEN |
| | PARKING STRUCTURES WHICH APPLIES TO LEVEL 2 AND 3 OF |
| | THE GARAGE. THE WEST ELEVATION IS 10'-1" FROM THE |
| | PROPERTY LINE WHICH IS ALSO THE FIRE SEPARATION |
| | DISTANCE. TABLE 705.8 ALLOWS A SPRINKLERED BUILDING |
| | THAT HAS 10 FEET TO 15 FEET OF FIRE SEPARATION DISTANCE |
| | TO HAVE 45 PERCENT OF THE WALL AREA OF EACH STORY TO BE |
| | OPEN. PLEASE PROVIDE THE CALCULATIONS FOR THE ALLOWABLE |
| | OPEN AREA OF EACH OF STORIES OTHER THAN THE OPEN LEVELS |
| | OF THE PARKING GARAGE FOR THE WEST ELEVATION AND THE |
| | PORTION OF THE SOUTH ELEVATION THAT IS 10' 1-7/8" FROM |
| | THE PROPERTY LINE TO SHOW COMPLIANCE WITH FBC 705.8. |
| | |
| | 32) NOT COMPLIED. THE HANDRAIL EXTENSION AT THE BOTTOM |
| | OF STAIRS ARE REQUIRED TO EXTEND AT THE SLOPE OF THE |
| | STAIR FLIGHT FOR A HORIZONTAL DISTANCE AT LEAST EQUAL |
| | TO ONE TREAD DEPTH BEYOND THE LAST RISER NOSING. SEE |
| | FBC ACCESSIBILITY SECTION 505.10.3. IT IS SHOWN WITH A |
| | HORIZONTAL EXTENSION ON THE STAIR SECTION ON SHEETS |
| | A7-01, A7-03 |
| | |
| | 33) COMPLIED. FBC 913.2.1 REQUIRES THE FIRE PUMP ROOM |
| | TO BE SEPARATED FROM ALL OTHER AREAS OF THE BUILDING BY |
| | 2-HOUR FIRE BARRIERS. |
| | |
| | 34) COMPLIED. THE TRASH CHUTE DISCHARGE ROOM HAS A 2 |
| | HOUR FIRE RATING. |
| | |
| | 35) NOT COMPLIED. HANDRAIL IS SHOWN WITH A HORIZONTAL |
| | EXTENSION RATHER THAN EXTENDING AT THE SLOPE OF THE |
| | STAIRS. WITH A STAIR NUMBER FOUR ON SHEET A7-04 DOES |
| | NOT HAVE THE REQUIRED HANDRAIL EXTENSION AT THE BOTTOM |
| | OF STAIRS. HANDRAILS ARE REQUIRED TO EXTEND AT THE |
| | SLOPE OF THE STAIR FLIGHT FOR A HORIZONTAL DISTANCE AT |
| | LEAST EQUAL TO ONE TREAD DEPTH BEYOND THE LAST RISER |
| | NOSING. SEE FBC ACCESSIBILITY SECTION 505.10.3. |
| | |
| | 36) COMPLIED. PROVIDE AREA TABULATIONS FOR THE ENTIRE |
| | BUILDING. FBC 107.2.1.2 |
| | |
| | 37) NOT COMPLIED. REQUEST TO DEFER HAS NOT BEEN |
| | RECEIVED. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT |
| | APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL |
| | MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE |
| | DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE |
| | SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT |
| | BEFORE THEY CAN BE INSTALLED. |
| | |
| | 38) NOT COMPLIED. REQUEST TO DEFER HAS NOT BEEN |
| | RECEIVED. FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 39) NOT COMPLIED. SHOW COMPLIANCE FBC ACCESSIBILITY |
| | SECTION 242 FOR ACCESSIBLE ENTRY INTO THE POOL OR |
| | SPECIFY ON THE PLANS WHY IT IS NOT REQUIRED. COMMUNITY |
| | POOLS THAT ARE ASSOCIATED WITH A PRIVATE RESIDENTIAL |
| | COMMUNITY THAT DO NOT RECEIVE GOVERNMENTAL FINANCIAL |
| | ASSISTANCE OR SPONSORSHIP AND ARE LIMITED TO THE |
| | EXCLUSIVE OF RESIDENTS AND THEIR GUESTS ARE NOT COVERED |
| | BY THE ADA ACCESSIBILITY REQUIREMENTS, INCLUDING |
| | PROVISIONS FOR POOL LIFTS OR SLOPED ENTRIES. IF A |
| | SWIMMING POOL LOCATED IN A RESIDENTIAL COMMUNITY IS |
| | MADE AVAILABLE TO THE PUBLIC FOR RENTAL OR USE IT IS |
| | REQUIRED TO COMPLY WITH TITLE II OF THE ADA. SPECIFY ON |
| | THE PLANS THE FORMER OR SHOW COMPLIANCE WITH THE LATTER |
| | STATEMENTS. SEE DECLARATORY STATEMENT, DS 2013-011. |
| | |
| | 40) NOT COMPLIED. SEPARATE PERMITS, REVIEWS AND FEES |
| | ARE REQUIRED FOR SOME ITEMS THAT MAY HAVE BEEN INCLUDED |
| | IN THE VALUE FOR THIS PROJECT. ITEMS SUCH AS FIRE |
| | ALARM, FIRE SPRINKLER, LOW VOLTAGE, LANDSCAPING, |
| | IRRIGATION AND ALL ITEMS OTHER THAN BUILDING, |
| | MECHANICAL, ELECTRIC AND PLUMBING. PLEASE PROVIDE A |
| | COST BREAKDOWN SO THAT WE CAN DEDUCT THESE ITEMS FROM |
| | THE PERMIT VALUE SO THAT YOU WILL NOT BE CHARGED TWICE |
| | FOR THE SAME ITEM. |
| | |
| | 41) COMPLIED. THE REST./RETAIL AREAS ON THE GROUND |
| | FLOOR HAVE DOORS THAT OPEN INTO THE PARKING GARAGE. IT |
| | APPEARS THAT THESE ARE MEANT TO BE REQUIRED EXITS. |
| | TABLE 508.4 REQUIRES A ONE HOUR FIRE SEPARATION BETWEEN |
| | S-2 AND M OR B OCCUPANCIES IN A SPRINKLERED BUILDING. |
| | IF THESE ARE REQUIRED EXITS THEY WILL BE REQUIRED TO BE |
| | CONNECTED TO A ONE HOUR RATED CORRIDOR SEPARATING THEM |
| | FROM THE PARKING GARAGE AND DISCHARGING TO THE EXTERIOR |
| | OF THE BUILDING. |
| | |
| | 42) NEW COMMENT. WIND VELOCITY IS SPECIFIED AS 180 MPH |
| | ON CD 01- CD06 PLANS IN BUILDING CODE DATA UNDER RISK |
| | CATEGORY. THE STRUCTURAL PLANS SPECIFY A 175 MPH VULT |
| | WINDSPEED. THE ACTUAL VULT WINDSPEED FOR WEST PALM |
| | BEACH IS 170 MPH. CITY AMENDMENTS SECTION 120. PLEASE |
| | COORDINATE. |
| | |
| | 43) THE DIAGONAL DISTANCE FOR SUITE 300 ON THE GROUND |
| | LEVEL DID NOT USE THE MAXIMUM OVERALL DIAGONAL |
| | DIMENSION OF THE AREA TO DETERMINE EXIT SEPARATION |
| | DISTANCE. PLEASE CORRECT. FBC 1007.1.1 |
| | |
| | 44) THE 1/3 OF THE DIAGONAL DISTANCE IN THE LEASING |
| | AREA IS INCORRECT. ONE THIRD OF 80'-4" IS 26'-9 ". FBC |
| | 107.2.1 |
| | |
| | 45) THE EXIT TRAVEL DISTANCE FOR PATH A AT LEVEL 01 |
| | SHOULD BE FROM THE MOST REMOTE POINT TO THE NEAREST |
| | EXIT. IT APPEARS THAT THE NORTHWEST CORNER OF THE BIKE |
| | STORAGE AREA WOULD BE THE MOST REMOTE POINT. FBC 1017.3 |
| | |
| | 46) PLEASE PROVIDE A RESPONSE LETTER ADDRESSING HOW |
| | EACH OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |