Plan Review Notes
Plan Review Notes For Permit 20011267
Permit Number 20011267
Review Stop P
Sequence Number 1
Notes
Date Text
2020-03-09 05:56:41PLUMBING 1ST REVIEW**DENIED**20011267
  
 1) SHT. CS-00 UNDER APPLICABLE CODE PLEASE SHOW FAIR
 HOUSING (FHA) AS THIS PROJECT FALLS UNDER THE FAIR
 HOUSING ACT.
 2) PLEASE CALL OUT WHICH FAIR HOUSING (FHA) DESIGN SPEC
 (A OR B) THIS PROJECT WILL HAVE. IF A MIXTURE OF BOTH
 PLEASE PROVIDE A SHEET LABELING EACH UNIT ON EACH FLOOR
 DESIGN SPEC WILL BE. FBC 107.2.1
 3) SHT A1-01 AND A1-01A ONLY SHOWS 1 TOILET ROOM.
 PROVIDE OCCUPANCY AND OCCUPANT LOAD FOR ALL AREAS AND
 ALL FLOORS AND PROVIDE TOILET ROOMS AS REQUIRED AS IT
 DOES NOT APPEAR 1 IS ENOUGH. FBC-PLB 403.1
 4) SHT A1-01 AND SHT A1-01A PLEASE SHOW THE REQUIRED
 30? X 48? CLEAR FLOOR SPACE OUTSIDE THE ACH OF THE DOOR
 WHEN THE DOOR SWING INTO 1 OF THE REQUIRED CLEAR FLOOR
 SPACES. FBC-ACC 603.2.1
 5) PLEASE MIN THE TEXT WRITING IN EACH ROOM AS ITS TOO
 LARGE AND MAKES IT TOO DIFFICULT TO SEE EACH ROOMS
 LAYOUT. FBC 107.2.1
 6) SHT A1-04 THE COMMON AREA TOILET AREA IT APPEARS THE
 MEN?S HAS MORE TOILET FIXTURES THEN THE WOMEN?S AND
 DOES NOT MEET POTTY PARITY. FBC-PLB 403.1.3
 7) IN YOUR BATHROOM ELEVATION OF THE TOILET (SEE SHT
 A3-02, A3-03,A3-16) YOU ARE SHOWING 19? AND MORE FOR
 THE CENTER OF THE TOILET. PER FHA THE ABSOLUTE
 MEASUREMENT MUST BE 18? FROM THE GRAB BAR SIDE OR AT
 LEAST 1 SIDE WERE A DROP DOWN GRAB BAR IS TO BE USED.
 8) SHT. A3-23 DETAIL # 6, A3-29 DETAIL#5 SINK HEIGHT
 SHOWN AS 2? 10 ??. MAX PERMITTED UNDER FHA IS 2?10?.
 9) SHT A6-60 PLEASE ADD NOTE THAT SHUT OFF VALVES FROM
 WASHER/DRYERS SHALL BE ACCESSIBLE. FBC-PLB 605.6, 606.3
 10) SHT I.D-0.01 DETAIL #6 YOU SHOW THE TOILET CLEAR
 FLOOR SPACE AS 60? X 56?. THIS WOULD ONLY BE IF THE
 TOILET WAS A WALL MOUNT. SEE FBC-ACC 604.8.1.1 AND
 CLARIFY THAT THIS PROJECT IS WALL HUNG TOILETS ONLY IN
 THE ADA TOILET ROOM. FBC 107.2.1
 11) SHT. P1.01A TOILET ROOM PLEASE LIST ASSE 1070
 TEMPERING DEVICE WITH INSTANT WATER HEATER. TEMP
 FACTORY PRE-SET @ 105 DOES NOT MEET THE FOLLOWING CODE.
 FBC-PLB 607.1.2
 12) SHT. P1.01A CALLS OUT AAV TO BE INSTALL HIGH IN
 ROOM. AAV ARE NOT PERMITTED BELOW THE TOP 4 BRANCH
 INTERVALS. FBC-PLB 918.3.1 AND AAV INSTALLATION MANUAL
 13) ON SHT P4-01 YOU SHOW A TEMPERING VALVE ON ALL
 SINK. IS IT YOUR INTENT ON THESE BEING INSTALLED ON ALL
 UNIT BATHROOM AND KITCHEN SINKS? PLEASE CLARIFY. FBC
 107.2.1
 14) SHT P4-01 ISLAND SINK DETAIL FOR THE AAV PLEASE ADD
 NOTE THIS IS NOT PERMITTED BELOW THE TOP 4 BRANCH
 INTERVALS. FBC-PLB 918.3.1
 15) SHT P-02 PLEASE LIST BACKFLOW SHALL BE LEAD FREE.
 2017 WPB CROSS CONNECTION MANUAL
 16) ON SHT. P5-01 THE INSULATION SCHEDULE LIST
 INSULATION AS 1?. FBC-ENERGY C404.4 CALLS FOR
 INSULATION THICKNESS BASED ON TABLE FBC-ENERGY
 C403.2.10 AND BASED ON PIPE SIZE. PLEASE CORRECT.
 17) PROVIDE A COMPLETE SANITARY, WATER, AND STORM
 ISOMETRIC DRAWING. FBC 107.3.5
 18) PROVIDE INFORMATION ON THE GREASE INTERCEPTORS.
 MANUFACTURE, SIZE, HOW YOU SIZED ETC. FBC 107.2.1.
 UNABLE TO LOCATE ANY CIVIL PLANS.
  
  
  
 TIM HUNT
 PLUMBING PLAN REVIEW
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 561-248-2703
 [email protected]
  
  