| 2020-03-09 05:56:41 | PLUMBING 1ST REVIEW**DENIED**20011267 |
| | |
| | 1) SHT. CS-00 UNDER APPLICABLE CODE PLEASE SHOW FAIR |
| | HOUSING (FHA) AS THIS PROJECT FALLS UNDER THE FAIR |
| | HOUSING ACT. |
| | 2) PLEASE CALL OUT WHICH FAIR HOUSING (FHA) DESIGN SPEC |
| | (A OR B) THIS PROJECT WILL HAVE. IF A MIXTURE OF BOTH |
| | PLEASE PROVIDE A SHEET LABELING EACH UNIT ON EACH FLOOR |
| | DESIGN SPEC WILL BE. FBC 107.2.1 |
| | 3) SHT A1-01 AND A1-01A ONLY SHOWS 1 TOILET ROOM. |
| | PROVIDE OCCUPANCY AND OCCUPANT LOAD FOR ALL AREAS AND |
| | ALL FLOORS AND PROVIDE TOILET ROOMS AS REQUIRED AS IT |
| | DOES NOT APPEAR 1 IS ENOUGH. FBC-PLB 403.1 |
| | 4) SHT A1-01 AND SHT A1-01A PLEASE SHOW THE REQUIRED |
| | 30? X 48? CLEAR FLOOR SPACE OUTSIDE THE ACH OF THE DOOR |
| | WHEN THE DOOR SWING INTO 1 OF THE REQUIRED CLEAR FLOOR |
| | SPACES. FBC-ACC 603.2.1 |
| | 5) PLEASE MIN THE TEXT WRITING IN EACH ROOM AS ITS TOO |
| | LARGE AND MAKES IT TOO DIFFICULT TO SEE EACH ROOMS |
| | LAYOUT. FBC 107.2.1 |
| | 6) SHT A1-04 THE COMMON AREA TOILET AREA IT APPEARS THE |
| | MEN?S HAS MORE TOILET FIXTURES THEN THE WOMEN?S AND |
| | DOES NOT MEET POTTY PARITY. FBC-PLB 403.1.3 |
| | 7) IN YOUR BATHROOM ELEVATION OF THE TOILET (SEE SHT |
| | A3-02, A3-03,A3-16) YOU ARE SHOWING 19? AND MORE FOR |
| | THE CENTER OF THE TOILET. PER FHA THE ABSOLUTE |
| | MEASUREMENT MUST BE 18? FROM THE GRAB BAR SIDE OR AT |
| | LEAST 1 SIDE WERE A DROP DOWN GRAB BAR IS TO BE USED. |
| | 8) SHT. A3-23 DETAIL # 6, A3-29 DETAIL#5 SINK HEIGHT |
| | SHOWN AS 2? 10 ??. MAX PERMITTED UNDER FHA IS 2?10?. |
| | 9) SHT A6-60 PLEASE ADD NOTE THAT SHUT OFF VALVES FROM |
| | WASHER/DRYERS SHALL BE ACCESSIBLE. FBC-PLB 605.6, 606.3 |
| | 10) SHT I.D-0.01 DETAIL #6 YOU SHOW THE TOILET CLEAR |
| | FLOOR SPACE AS 60? X 56?. THIS WOULD ONLY BE IF THE |
| | TOILET WAS A WALL MOUNT. SEE FBC-ACC 604.8.1.1 AND |
| | CLARIFY THAT THIS PROJECT IS WALL HUNG TOILETS ONLY IN |
| | THE ADA TOILET ROOM. FBC 107.2.1 |
| | 11) SHT. P1.01A TOILET ROOM PLEASE LIST ASSE 1070 |
| | TEMPERING DEVICE WITH INSTANT WATER HEATER. TEMP |
| | FACTORY PRE-SET @ 105 DOES NOT MEET THE FOLLOWING CODE. |
| | FBC-PLB 607.1.2 |
| | 12) SHT. P1.01A CALLS OUT AAV TO BE INSTALL HIGH IN |
| | ROOM. AAV ARE NOT PERMITTED BELOW THE TOP 4 BRANCH |
| | INTERVALS. FBC-PLB 918.3.1 AND AAV INSTALLATION MANUAL |
| | 13) ON SHT P4-01 YOU SHOW A TEMPERING VALVE ON ALL |
| | SINK. IS IT YOUR INTENT ON THESE BEING INSTALLED ON ALL |
| | UNIT BATHROOM AND KITCHEN SINKS? PLEASE CLARIFY. FBC |
| | 107.2.1 |
| | 14) SHT P4-01 ISLAND SINK DETAIL FOR THE AAV PLEASE ADD |
| | NOTE THIS IS NOT PERMITTED BELOW THE TOP 4 BRANCH |
| | INTERVALS. FBC-PLB 918.3.1 |
| | 15) SHT P-02 PLEASE LIST BACKFLOW SHALL BE LEAD FREE. |
| | 2017 WPB CROSS CONNECTION MANUAL |
| | 16) ON SHT. P5-01 THE INSULATION SCHEDULE LIST |
| | INSULATION AS 1?. FBC-ENERGY C404.4 CALLS FOR |
| | INSULATION THICKNESS BASED ON TABLE FBC-ENERGY |
| | C403.2.10 AND BASED ON PIPE SIZE. PLEASE CORRECT. |
| | 17) PROVIDE A COMPLETE SANITARY, WATER, AND STORM |
| | ISOMETRIC DRAWING. FBC 107.3.5 |
| | 18) PROVIDE INFORMATION ON THE GREASE INTERCEPTORS. |
| | MANUFACTURE, SIZE, HOW YOU SIZED ETC. FBC 107.2.1. |
| | UNABLE TO LOCATE ANY CIVIL PLANS. |
| | |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLAN REVIEW |
| | CITY OF WEST PALM BEACH (CGA SOLUTIONS) |
| | 561-248-2703 |
| | [email protected] |
| | |
| | |