| 2020-03-18 15:41:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) ALL A SHEETS - THERE ARE INDICATIONS OF THE COLOR |
| | RED ON SOME WALLS HOWEVER, THERE ARE NO INDICATION OF |
| | WHAT THOSE ABBREVIATED OR SOLID RED LINES MEANS |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 2) SHEET A1-01 - THERE ARE INDICATIONS OF A TRASH ROOM |
| | HOWEVER, NO INDICATION OF ANY REQUIRED FIRE RATING OF |
| | THE TRASH ROOM WALLS. |
| | |
| | PET NFPA 101, CH 30 |
| | |
| | 30.3.2 PROTECTION FROM HAZARDS. |
| | 30.3.2.1 HAZARDOUS AREAS. ANY HAZARDOUS AREA SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 8.7. |
| | 30.3.2.1.1 THE AREAS DESCRIBED IN TABLE 30.3.2.1.1 |
| | SHALL BE |
| | PROTECTED AS INDICATED. |
| | |
| | TRASH COLLECTION ROOMS 1 HOUR AND SPRINKLERS |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 3) SHEET CD 01 - THERE ARE INDICATIONS OF THE M SPACES |
| | WITH AN OCCUPANT LOAD OF 60SF/OCC. |
| | |
| | PER NFPA 101 CH 7 - 60 IS USED FOR SALES AREAS ON |
| | FLOORS ABOVE STREET FLOOR. 30 SHOULD BE USED FOR STREET |
| | FLOOR SALES |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE A DETAILED |
| | NARRATIVE AND SPECIFIC FIRE CODE. |
| | |
| | |
| | |
| | |
| | 4) SHEET CD 01 - THERE ARE INDICATIONS THAT THE M |
| | OCCUPANCY EXITS AT THE REAR INTO A S OCCUPANCY. |
| | |
| | EXITING INTO A HIGHER HAZARD OCCUPANCY IS NOT ALLOWED |
| | IN THE FIRE CODE. |
| | |
| | |
| | PER NFPA 101 CH 7 |
| | |
| | 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE |
| | PERMITTED TO BE |
| | THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS, |
| | PROVIDED THAT SUCH |
| | ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED. |
| | FOYERS, LOBBIES, AND |
| | RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS |
| | SHALL NOT BE |
| | CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE |
| | ARRANGED SO |
| | THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA |
| | IDENTIFIED UNDER |
| | PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43. |
| | |
| | PLEASE REVIEW AND CORRECT |
| | |
| | |
| | 5) SHEET A1-01 - THERE IS NO INDICATION OF A REQUIRED |
| | FIRE RATING OF THE PET SPA WALLS. |
| | |
| | PER NFPA 101 CH 6 |
| | |
| | 6.1.14.3 MIXED OCCUPANCIES. |
| | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| | CLASSIFIED AS TO ITS USE IN |
| | ACCORDANCE WITH SECTION 6.1. |
| | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| | RESTRICTIVE |
| | REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS |
| | SEPARATE SAFEGUARDS |
| | ARE APPROVED. |
| | 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) |
| | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| | EACH PART OF THE |
| | BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED |
| | IN THIS CHAPTER, |
| | SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| | FIRE-RESISTIVE |
| | ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3, |
| | TABLE 6.1.14.4.1(A), |
| | AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED |
| | BY APPROVED |
| | EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY |
| | 6.1.14.4.6. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 6) SHEET A 1-04 & ALL FLOOR LEVELS ABOVE - PLEASE |
| | PROVIDE THE DIMESION OF THE NORTH AND SOUTH DEAD-END |
| | CORRIDOR SHOWING COMPLIANCE WITH NFPA 101 CH 30 |
| | |
| | 30.2.5.4.2 DEAD-END CORRIDORS SHALL NOT EXCEED 50 FT |
| | (15 M) IN |
| | BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| | SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH 30.3.5. |
| | |
| | PLEASE REVIEW AND PROVIDE |
| | |
| | |
| | |
| | 7) SHEET A 1-04 - PLEASE PROVIDE THE DIMENSION IN |
| | BETWEEN THE STRAIRWELLS SHOWING COMPLIANCE WITH THE |
| | HOSELINE LENGHTS PER NFPA 14 |
| | |
| | 7.3.2.2* WHERE THE MOST REMOTE PORTION OF A |
| | NONSPRINKLERED |
| | FLOOR OR STORY IS LOCATED IN EXCESS OF 150 FT (45.7 M) |
| | OF TRAVEL |
| | DISTANCE FROM A HOSE CONNECTION IN OR ADJACENT TO A |
| | REQUIRED |
| | EXIT OR THE MOST REMOTE PORTION OF A SPRINKLERED FLOOR |
| | OR STORY |
| | IS LOCATED IN EXCESS OF 200 FT (61 M) OF TRAVEL |
| | DISTANCE FROM A |
| | HOSE CONNECTION IN OR ADJACENT TO A REQUIRED EXIT, |
| | ADDITIONAL |
| | HOSE CONNECTIONS SHALL BE PROVIDED, IN APPROVED |
| | LOCATIONS, |
| | WHERE REQUIRED BY THE LOCAL FIRE DEPARTMENT OR THE AHJ. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS OF COMPLIANCE OR |
| | CORRECT |
| | |
| | |
| | |
| | 8) SHEET A 1-04 - THE DOORS TO THE FITNESS ROOM ARE |
| | INDICATED AS IN-SWING. |
| | |
| | PER NFPA 101 CH 7 |
| | |
| | 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES |
| | REQUIRED TO BE |
| | OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING |
| | IN THE |
| | DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING |
| | CONDITIONS: |
| | (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| | OF 50 OR |
| | MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| | REQUIRED TO |
| | SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED |
| | BY 7.2.4.3.8.1 OR 7.2.4.3.8.2. |
| | (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| | TO |
| | SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING |
| | HEALTH |
| | CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19. |
| | (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| | ENCLOSURE, UNLESS |
| | THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT |
| | OPENS |
| | DIRECTLY INTO AN EXIT ENCLOSURE |
| | (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD |
| | CONTENTS AREA |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 9)THIS IS A HIGH RISE BUILDING HOWEVER A FIRE COMMAND |
| | ROOM COULD NOT BE READILY IDENTIFIED OR LOCATED. |
| | |
| | PER NFPA 1 & 101 |
| | |
| | 3.3.36.7* HIGH-RISE BUILDING. A BUILDING WHERE THE |
| | FLOOR OF AN |
| | OCCUPIABLE STORY IS GREATER THAN 75 FT (23 M) ABOVE THE |
| | LOWEST |
| | LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS. |
| | |
| | |
| | THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1, |
| | CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN |
| | THE FOLLOWING FEATURES: |
| | |
| | A. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM |
| | DIMENSION OF 10 FT. |
| | B. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. |
| | C. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE PUBLIC TELEPHONE SYSTEM |
| | D. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| | FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF |
| | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| | EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION |
| | OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE |
| | BARRIERS AND SMOKE PARTITIONS |
| | E. A WORK TABLE. |
| | F. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN |
| | FOR THE BUILDING. |
| | G. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM |
| | CONTROL UNIT. |
| | H. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF |
| | THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL |
| | I. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION |
| | SYSTEMS. |
| | J. CONTROLS FOR UNLOCKING STAIRWAY DOORS SIMULTANEOUSLY |
| | K. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY |
| | PANELS |
| | L. EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| | M. FIRE PUMP STATUS INDICATORS |
| | N. GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| | TRANSFER FEATURES. |
| | O. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| | BY OTHER SECTIONS OF THIS CODE |
| | P. CONTROLS REQUIRED FOR SMOKE CONTROL |
| | Q. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| | A17.1. |
| | R. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR |
| | SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS |
| | PROVIDED |
| | |
| | |
| | PER NFPA 101 |
| | |
| | 11.8.6* EMERGENCY COMMAND CENTER. |
| | 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED |
| | IN A |
| | LOCATION APPROVED BY THE FIRE DEPARTMENT. |
| | 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE |
| | FOLLOWING: |
| | (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS |
| | (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION |
| | SERVICE |
| | PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION |
| | OF THIS |
| | CODE |
| | (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION |
| | PANELS |
| | (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS |
| | (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS |
| | (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE |
| | PROVIDED |
| | IN ACCORDANCE WITH ASME A17.1/CSA B44 |
| | (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS |
| | (8) EMERGENCY GENERATOR STATUS INDICATORS |
| | (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING |
| | SYSTEM |
| | (10) FIRE PUMP STATUS INDICATORS |
| | (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE |
| | PUBLIC TELEPHONE SYSTEM |
| | (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY |
| | 11.8.8 |
| | |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS. |
| | |
| | |
| | |
| | 10) THERE APPEARS TO BE NO CLEAR INDICATION OF ANY |
| | SMOKE CONTROL SYSTEM(S). |
| | |
| | PLEASE PROVIDE DETAILS |
| | |
| | |
| | |
| | 11) SHEETS A7-20 & 21 - THERE ARE NO INDICATIONS OF |
| | ELEVATORS THAT COMPLY WITH THE FIRE CODE |
| | |
| | PER NFPA 101 |
| | |
| | 30.5.3 ELEVATORS, ESCALATORS, AND CONVEYORS. ELEVATORS, |
| | ESCALATORS, AND CONVEYORS SHALL COMPLY WITH THE |
| | PROVISIONS OF |
| | SECTION 9.4. |
| | |
| | 9.4.2 CODE COMPLIANCE. |
| | 9.4.2.1 EXCEPT AS MODIFIED HEREIN, NEW ELEVATORS, |
| | ESCALATORS, |
| | DUMBWAITERS, AND MOVING WALKS SHALL BE IN ACCORDANCE |
| | WITH THE |
| | REQUIREMENTS OF ASME A17.1/CSA B44, SAFETY CODE FOR |
| | ELEVATORS AND ESCALATORS. |
| | |
| | 9.4.3 FIRE FIGHTERS? EMERGENCY OPERATIONS. |
| | 9.4.3.1 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE |
| | FIGHTERS? |
| | EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA |
| | B44, |
| | SAFETY CODE FOR ELEVATORS AND ESCALATORS. |
| | 9.4.3.2 ALL EXISTING ELEVATORS HAVING A TRAVEL DISTANCE |
| | OF 25 FT |
| | (7620 MM) OR MORE ABOVE OR BELOW THE LEVEL THAT BEST |
| | SERVES THE |
| | NEEDS OF EMERGENCY PERSONNEL FOR FIRE-FIGHTING OR |
| | RESCUE PURPOSES |
| | SHALL CONFORM TO THE FIRE FIGHTERS? EMERGENCY |
| | OPERATIONS |
| | REQUIREMENTS OF ASME A17.3, SAFETY CODE FOR EXISTING |
| | ELEVATORS |
| | AND ESCALATORS. |
| | |
| | |
| | 12) SHEETS A7-20 & 21 - PLEASE PROVIDE INDICATIONS FOR |
| | COMPLIANCE OF THE ELEVATOR INTERIOR SIZE FOR EMS |
| | STRETCHER DIMESIONS. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 13) SHEET E0-00 & ELECTRICAL SHEETS - THERE ARE |
| | INDICATIONS OF FIRE ALARM DEVICES; HOWEVER, ALL FIRE |
| | ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP |
| | DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT |
| | |
| | |
| | |
| | 14) ELECTRICAL SHEETS - THERE ARE NO INDICATIONS OF BDA |
| | INSTALLATIONS FOR RADIO TWO-WAY COMMUNICATIONS PER NFPA |
| | 72 |
| | |
| | A BDA PERMIT AND REPORT IS REQUIRED UNDER SPERATE |
| | PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT |
| | |
| | |
| | 15) SHEET FPO - THERE ARE INDICATIONS UNDER GENERAL |
| | NOTE OF A FIRE SPRINKLER PERMIT. |
| | |
| | ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE |
| | PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT |
| | |
| | |
| | |
| | 16) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 17 ) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |