| 2020-03-11 09:03:47 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING |
| | PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK |
| | IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY |
| | OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1 |
| | 2. PROVIDE ACKNOWLEDGEMENT THAT EMERGENCY RESPONDER |
| | RADIO COVERAGE WILL BE SUPPLIED UNDER SEPARATE PERMIT. |
| | FBC 403.4.5; WPB FBC 107.2.1 |
| | 3. RISER DIAGRAM DOES NOT CONTAIN INFORMATION FOR THE |
| | SERVICE TO THE FIRE PUMP. PROVIDE CORRECTION. NEC |
| | 215.5; WPB FBC 107.2.1 |
| | 4. PROVIDE MULTIPLE SOURCES FOR RELIABLE POWER TO THE |
| | FIRE PUMP. NEC 695.3(B) |
| | 5. PROVIDE STANDBY AND EMERGENCY POWER FOR STANDBY |
| | POWER LOADS SPECIFIED IN FBC 403.4.8.3 AND EMERGENCY |
| | POWER LOADS SPECIFIED IN FBC 403.4.8.4. FBC 403.4.8 |
| | 6. RISER DIAGRAM INDICATES THAT EXCEPTION 3 TO NEC |
| | 230.90(A) WILL BE USED FOR THE 6000 AMP DISTRIBUTION |
| | CENTER, BUT NO DETAILS ARE PROVIDED ABOUT THE |
| | OVERCURRENT PROTECTION IN THIS EQUIPMENT. THE 6 MAINS |
| | PERMITTED ARE REQUIRED TO BE GROUPED IN THE SAME |
| | LOCATION. PROVIDE CLARIFICATION AND/OR CORRECTIONS AS |
| | NEEDED. PROVIDE PANEL SCHEDULE FOR THIS DISTRIBUTION |
| | EQUIPMENT TO CONFIRM CODE COMPLIANCE. WPB FBC 107.2.1; |
| | NEC 230.90, 230.72 |
| | 7. PROVIDE NAME OF METER CENTERS ON THE METER CENTER. |
| | THE LOAD CALCULATION FOR EACH METER CENTER ARE SHOWN |
| | TOGETHER, SO IT IS UNCLEAR WHICH CALCULATION IS FOR |
| | WHICH METER CENTER. WPB FBC 107.2.1 |
| | 8. PROVIDE LOAD CALCULATION FOR EACH BUSWAY FEEDING THE |
| | METER CENTERS. WPB FBC 107.2.1; NEC 215.2, 220 |
| | 9. PROVIDE CONDUCTOR SIZE FEEDING EACH BUSWAY. WPB FBC |
| | 107.2.1; NEC 215.2, 220 |
| | 10. PROVIDE VOLTAGE DROP CALCULATIONS FOR EACH BUSWAY. |
| | FBC EC C405.6.3 |
| | 11. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT |
| | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2, |
| | C405.2.1 |
| | 12. SHEET E2-04 SHOWS LIGHTING BEING INSTALLED WITHIN 5 |
| | FEET OF THE POOL. WHAT IS THE HEIGHT OF THESE FIXTURES? |
| | LIGHTING SHALL NOT BE INSTALLED AT A HEIGHT LESS THAN |
| | 12 FEET WHEN WITHIN 5 FEET OF THE INSIDE WALL OF THE |
| | POOL. PROVIDE CLARIFICATION AND/OR CORRECTION. NEC |
| | 680.22(B)(1) |
| | 13. RISER DIAGRAM INDICATES AIC FAULT CURRENT IS |
| | ASSUMED. PROVIDE ACTUAL AVAILABLE SHORT CIRCUIT |
| | CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE |
| | POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT |
| | CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC |
| | RATING OF THE SERVICE EQUIPMENT IS ADEQUATE. AS AN |
| | ALTERNATIVE, A BLOCK NOTE WILL BE ACCEPTED INDICATING |
| | THIS WILL BE A DEFERRED SUBMITTAL PROVIDED PRIOR TO |
| | RELEASE OF POWER. NEC 110.9, 110.10 |
| | 14. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 15. PROVIDE BLOCK NOTE INDICATING COMPLIANCE: WITHIN 30 |
| | DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD |
| | DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDE TO |
| | THE BUILDING OWNER, INCLUDING: 1. A SINGLE LINE DIAGRAM |
| | OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND 2. |
| | FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL |
| | DISTRIBUTION. FBC EC C405.6.4.1 |
| | 16. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FOR RESIDENTIAL |
| | AREAS, A MINIMUM OF 75 PERCENT OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN |
| | ONLY HIGH EFFICACY LAMPS. FBC EC C405.1, C405.4.2 |
| | 17. FOR POOL ROOM EQUIPMENT, PROVIDE ENCLOSURE TYPES |
| | DESIGNED TO PROTECT AGAINST CORROSIVE ENVIRONMENTS. NEC |
| | TABLE 110.28 |
| | 18. PROVIDE DETAILS OF SELECTIVE COORDINATION PER NEC |
| | 700.28 AND 701.27. |
| | 19. PROVIDE DETAILS OF ARC ENERGY REDUCTION PER NEC |
| | 240.87. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |