| 2020-03-06 14:10:11 | PLAN REVIEW COMMENTS |
| | THRESHOLD BUILDING |
| | 8 STORY APARTMENT BUILDING (MIXED USE M, S-2, R-2, A-3 |
| | AND B) |
| | CONST. TYPE 1-A, SPRINKLERED |
| | 170 MPH, EXPOSURE "D" |
| | FLOOD ZONE "X" |
| | 625 S. OLIVE AVE. |
| | PERMIT #20011267 |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) ART IN PUBLIC PLACES |
| | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL |
| | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. PER |
| | CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND CITY |
| | OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, ART |
| | IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. PER CITY OF WEST PALM BEACH |
| | CODE OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, |
| | SECTION 78-122, RENOVATION AND NEW CONSTRUCTION |
| | PROJECTS ARE ASSESSED CUMULATIVELY, SO THE ART |
| | ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE PROJECTS. |
| | FOR INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR AT |
| | 822-1515 OR E-MAIL: [email protected] |
| | |
| | 2) THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION |
| | PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) |
| | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED |
| | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED |
| | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. |
| | C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT |
| | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. |
| | F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE. |
| | G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR |
| | THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS |
| | REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, |
| | APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND |
| | CEILINGS. |
| | J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL |
| | BE HAPPY TO SEND YOU A COPY OF THE CURRENT ( OCTOBER |
| | 2018 ) CITY GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING THRESHOLD/SPECIAL INSPECTORS AND RESIDENT |
| | INSPECTORS. |
| | |
| | 3) THE GEOTECHNICAL REPORT THAT WAS SUBMITTED INDICATES |
| | THAT THE RECOMMENDED VIBRO COMPACTION SOIL PREPARATION |
| | WILL PRODUCE A SOIL BEARING VALUE OF UP TO 6,000 PSF. |
| | NOTE 3A ON SHEET S200 OF THE PLANS STATES THAT THE |
| | BUILDING DESIGN REQUIRES A SOIL BEARING CAPACITY OF |
| | 8,000 PSF. PLEASE INDICATE HOW THIS WILL BE ADDRESSED. |
| | FBC 1801.2 |
| | |
| | 4) SPECIFY HOW COMPLIANCE WITH FBC CHAPTER 33 |
| | SAFEGUARDS DURING CONSTRUCTION FOR THE FOUNDATION |
| | PERMIT WILL BE MET. |
| | |
| | 5) FBC 3002.4 REQUIRES ANY BUILDING THAT IS MORE THAN |
| | THREE STORIES HIGH OR IN WHICH THE VERTICAL DISTANCE |
| | BETWEEN THE BOTTOM TERMINAL LANDING AND THE TOP |
| | TERMINAL LANDING EXCEEDS 25 FEET TO BE CONSTRUCTED TO |
| | CONTAIN AT LEAST ONE PASSENGER ELEVATOR THAT IS |
| | OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE DEPARTMENT |
| | ACCESS TO ALL FLOORS. THE ELEVATOR CAR SHALL BE OF A |
| | SIZE AND ARRANGEMENT TO ACCOMMODATE AN AMBULANCE |
| | STRETCHER 24 INCHES BY 76 INCHES WITH NOT LESS THAN |
| | 5-INCH RADIUS CORNERS, IN THE HORIZONTAL, OPEN POSITION |
| | AND SHALL BE IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR |
| | EMERGENCY MEDICAL SERVICES (STAR OF LIFE). |
| | |
| | 6) THE TRASH CHUTE DISCHARGE ROOM IS REQUIRED TO BE |
| | SEPARATED BY FIRE BARRIERS WITH A FIRE-RESISTANCE |
| | RATING NOT LESS THAN THE REQUIRED FIRE RATING OF THE |
| | SHAFT ENCLOSURE. FBC 713.13.4 |
| | |
| | 7) THE EXIT PASSAGEWAY AT STAIR 01 IS INCORRECTLY |
| | LABELED AS AN EXIT ACCESS CORRIDOR. AN EXIT PASSAGEWAY |
| | IS AN EXTENSION OF THE ENCLOSED INTERIOR EXIT STAIRWAY |
| | AND HAS REQUIREMENTS SIMILAR TO THE STAIRWAY. PLEASE |
| | CORRECT. SEE FBC 1023.1 AND 1024. |
| | |
| | 8) PROVIDE A SITE PLAN WITH ELEVATIONS SHOWN IN NAVD |
| | 88. THERE WAS ONE WITH THE FOUNDATION PLAN, BUT IT |
| | APPEARS TO BE MISSING FROM THESE DOCUMENTS. FBC |
| | 107.2.1.2 |
| | PLEASE REVIEW THE ELEVATIONS OF THE GRADE AROUND THE |
| | EXTERIOR OF THE BUILDING AND COMPARE THEM WITH THE |
| | FLOOR ELEVATION (11.97') OF THE BUILDING TO MAKE SURE |
| | THAT THE EXITS DISCHARGE AT GRADE AND THE ELEVATIONS |
| | AND SLOPES OF LANDINGS AND WALK WAYS WILL MEET THE |
| | RUNNING SLOPE AND CROSS SLOPE REQUIREMENTS OF THE |
| | FLORIDA ACCESSIBILITY CODE SECTION 403. |
| | |
| | 9) THE AR-RENDERINGS APPEAR TO BE MISLABELED. PLEASE |
| | CLARIFY. FBC 107.2.1 |
| | |
| | 10) FBC TABLE 602 REQUIRES MERCANTILE OCCUPANCIES TO |
| | HAVE 2 HOUR FIRE RESISTANCE RATED EXTERIOR WALLS FOR |
| | LESS THAN 10 FT OF FIRE SEPARATION DISTANCE. THIS IS |
| | NOT REFLECTED IN THE CODE DATA ON SHEET CD-1. HOWEVER, |
| | THIS DOES NOT APPEAR TO BE AN ISSUE FOR YOUR PROJECT. |
| | |
| | 11) ON SHEET CD-01 AND THE OTHER EXISTING PLANS THE |
| | RISK CATEGORY IN CODE DATA TABLE HAS BROWARD COUNTY AND |
| | THIS PROJECT IS LOCATED IN PALM BEACH COUNTY. PLEASE |
| | CORRECT. FBC 107.2.1 |
| | |
| | 12) PLEASE REMOVE THE RED DASHED CIRCLES FROM THE |
| | EXITING PLANS ON SHEETS CD-01 AND CD-02. THEY MAKE THE |
| | DRAWINGS DIFFICULT TO REVIEW. FBC 107.2.1.3 |
| | |
| | 13) THERE IS A STAIR #04 SHOWN ON THE PLANS BETWEEN THE |
| | 2ND AND 3RD LEVELS OF THE PARKING GARAGE WITH A NOTE |
| | (WHICH IS MISLABELED AS STAIR 03 ON CD-02) THAT IT IS |
| | TO PREVENT A DEAD END CONDITION AT LEVEL 3. PLEASE |
| | CLARIFY. |
| | |
| | 14) THE COMMERCIAL AREAS ON THE GROUND FLOOR EXITING |
| | PLAN ARE LABELED RESTAURANT/RETAIL AND THE OCCUPANT |
| | LOADS PROVIDED ARE FOR MERCANTILE. A RESTAURANT WOULD |
| | BE AN A-2 ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD OF |
| | 15 NET WHICH WOULD BE MORE THAN THE 60 SQFT FOR |
| | MERCANTILE. PLEASE USE THE MOST RESTRICTIVE OCCUPANT |
| | LOAD. FBC 1004.1 |
| | |
| | 15) THE COVERED OUTDOOR RESTAURANT SEATING SHOULD BE |
| | LABELED A-2 RATHER THAN A-3 PER FBC 303.3. PLEASE |
| | CORRECT. |
| | |
| | 16) SHOW COMPLIANCE WITH FBC 3002.4 FOR THE REQUIREMENT |
| | TO PROVIDE AN ELEVATOR CAR THAT WILL ACCOMMODATE AN |
| | AMBULANCE STRETCHER 24" X 76". |
| | |
| | 17) VERIFY THE REQUIRED VERTICAL CLEARANCE OF 98 INCHES |
| | FOR THE VAN PARKING SPACE, ACCESS AISLE AND VEHICULAR |
| | ROUTE SERVING IT AS REQUIRED BY FBC ACCESSIBILITY |
| | SECTION 502.5. |
| | |
| | 18) THE PARKING DATA ON SHEET GN-00 HAS 20 COMMERCIAL |
| | SPACES AND 183 RESIDENTIAL SPACES. TABLE 208.2 IN THE |
| | FBC ACCESSIBILITY REQUIRES A MINIMUM OF 1 ACCESSIBLE |
| | PARKING SPACE WHEN THE TOTAL NUMBER OF SPACES PROVIDED |
| | IS 1 TO 25. THE FAIR HOUSING GUIDELINES REQUIRE AT |
| | LEAST 2 PERCENT OF THE COVERED RESIDENTIAL UNITS TO |
| | HAVE ACCESSIBLE PARKING WHICH IS 4 SPACES. THIS PROJECT |
| | IS REQUIRED TO HAVE A MINIMUM OF 5 ACCESSIBLE PARKING |
| | SPACES. THE PLANS SHOW ONLY 4 ACCESSIBLE SPACES. |
| | SECTION 208.2.4 REQUIRES AT LEAST ONE VAN PARKING SPACE |
| | COMPLYING WITH SECTION 502 FOR EVERY SIX OR FRACTION OF |
| | SIX REQUIRED ACCESSIBLE SPACES. |
| | |
| | 19) PLEASE LABEL THE EXIT PASSAGEWAY THAT CONNECTS |
| | STAIR #01 TO THE EXIT DISCHARGE. SEE FBC SECTION 1024 |
| | FOR THE REQUIREMENTS OF AN EXIT PASSAGEWAY WHICH |
| | EXTENDS THE INTERIOR EXIT STAIRS TO THE EXTERIOR OF THE |
| | BUILDING AND IS TREATED THE SAME AS AN ENCLOSED EXIT |
| | STAIR WAY. |
| | |
| | 20) THE EXIT DOOR SIZE AND CALCULATIONS ARE NOT |
| | PROVIDED FOR THE EXIT DISCHARGE DOOR AT THE EXIT |
| | PASSAGEWAY FOR STAIR #01 ON SHEET CD-01. |
| | |
| | 21) ON SHEET CD-04, DEAD END PATH A IS NOT IDENTIFIED. |
| | FBC 107.2.1 |
| | |
| | 22) A PORTION OF PATH B IS MISSING ON THE DRAWING. FBC |
| | 107.2.1 |
| | |
| | 23) THE EXIT ACCESS TRAVEL DISTANCE IS MEASURED FROM |
| | THE MOST REMOTE POINT WITHIN A STORY ALONG THE NATURAL |
| | AND UNOBSTRUCTED PATH OF EGRESS TRAVEL TO AN EXIT. THE |
| | MOST REMOTE POINT WOULD BE FROM THE CORNER OF THE |
| | BALCONIES IN THE ROOMS. FBC 1017.3 |
| | |
| | 24) SHOW THE TRAVEL PATHS FROM THE POOL DECK/POOL AREA |
| | TO THE EXITS. FBC 1017.3 |
| | |
| | 25) IN ADDITION TO THE EXIT CAPACITY AT EACH EXIT DOOR |
| | ON THE FLOOR, INDICATE THE NUMBER OF OCCUPANTS THAT |
| | WILL BE USING EACH OF EXITS. FBC SECTION 1006 AND FBC |
| | 107.2.1.2 |
| | |
| | 26) THE OCCUPANT LOADS ARE TOTALS AND THE DISPERSION OF |
| | OCCUPANTS TO EACH OF THE EXITS IS NOT SHOWN ON THE |
| | PLANS. SHOW THE NUMBER OF OCCUPANTS FOR EACH ROOM OR |
| | AREA AND WHICH EXIT THEY WILL USE. FBC 107.2.1 |
| | |
| | 27) SHOW THE EGRESS PATHS AND EXIT DOORS FOR THE |
| | OUTDOOR TERRACE, CLUBROOM, FITNESS ROOM AND AMENITY |
| | DECK SHOWN ON SHEET CD-04. FBC 1007 |
| | |
| | 28) THE EXIT DOOR TO STAIR #03 FROM THE POOL DECK ON |
| | LEVEL 4 IS SPECIFIED WITH A WITH A 19 INCH CLEAR WIDTH. |
| | FBC 1010.1.1 REQUIRES A MINIMUM CLEAR OPENING WIDTH OF |
| | 32 INCHES. THE SIZES FOR THE DOORS TO THIS STAIR ARE |
| | NOT PROVIDED ON LEVELS 2 AND 3. FBC 107.2.1 |
| | |
| | 29) THE DOORS TO OTHER STAIRS ARE MISSING EGRESS |
| | INFORMATION ALSO. FBC 107.2.1 |
| | |
| | 30) SHOW THE EXIT PATHS OF TRAVEL AND TRAVEL DISTANCES |
| | FOR EACH LEVEL OF THE GARAGE. FBC 1006 |
| | |
| | 31) THE FIRST LEVEL OF THE PARKING GARAGE IS ENCLOSED |
| | WITH MECHANICAL VENTILATION REQUIRED. THE SECOND AND |
| | THIRD LEVELS ARE AN OPEN GARAGE. FBC TABLE 705.8 |
| | FOOTNOTE "G" ALLOWS UNLIMITED OPENINGS IN OPEN PARKING |
| | STRUCTURES WHICH APPLIES TO LEVEL 2 AND 3 OF THE |
| | GARAGE. THE WEST ELEVATION IS 10'-1" FROM THE PROPERTY |
| | LINE WHICH IS ALSO THE FIRE SEPARATION DISTANCE. TABLE |
| | 705.8 ALLOWS A SPRINKLERED BUILDING THAT HAS 10 FEET TO |
| | 15 FEET OF FIRE SEPARATION DISTANCE TO HAVE 45 PERCENT |
| | OF THE WALL AREA OF EACH STORY TO BE OPEN. PLEASE |
| | PROVIDE THE CALCULATIONS FOR THE ALLOWABLE OPEN AREA OF |
| | EACH OF STORIES OTHER THAN THE OPEN LEVELS OF THE |
| | PARKING GARAGE FOR THE WEST ELEVATION AND THE PORTION |
| | OF THE SOUTH ELEVATION THAT IS 10' 1-7/8" FROM THE |
| | PROPERTY LINE TO SHOW COMPLIANCE WITH FBC 705.8. |
| | |
| | 32) THE HANDRAIL EXTENSION AT THE BOTTOM OF STAIRS ARE |
| | REQUIRED TO EXTEND AT THE SLOPE OF THE STAIR FLIGHT FOR |
| | A HORIZONTAL DISTANCE AT LEAST EQUAL TO ONE TREAD DEPTH |
| | BEYOND THE LAST RISER NOSING. SEE FBC ACCESSIBILITY |
| | SECTION 505.10.3. IT IS SHOWN WITH A HORIZONTAL |
| | EXTENSION ON THE STAIR SECTION ON SHEET A7-01, A7-03 |
| | |
| | 33) FBC 913.2.1 REQUIRES THE FIRE PUMP ROOM TO BE |
| | SEPARATED FROM ALL OTHER AREAS OF THE BUILDING BY |
| | 2-HOUR FIRE BARRIERS. |
| | |
| | 34) THE TRASH (WASTE) CHUTE IS REQUIRED TO DISCHARGE |
| | INTO AN ENCLOSED ROOM SEPARATED BY FIRE BARRIERS WITH A |
| | FIRE-RESISTANCE RATING NOT LESS THAN THE REQUIRED FIRE |
| | RESISTANCE RATING OF THE SHAFT ENCLOSURE PER FBC |
| | 713.13.4. |
| | |
| | 35) STAIR NUMBER FOUR ON SHEET A7-04 DOES NOT HAVE THE |
| | REQUIRED HANDRAIL EXTENSION AT THE BOTTOM OF STAIRS. |
| | HANDRAILS ARE REQUIRED TO EXTEND AT THE SLOPE OF THE |
| | STAIR FLIGHT FOR A HORIZONTAL DISTANCE AT LEAST EQUAL |
| | TO ONE TREAD DEPTH BEYOND THE LAST RISER NOSING. SEE |
| | FBC ACCESSIBILITY SECTION 505.10.3. |
| | |
| | 36) PROVIDE AREA TABULATIONS FOR THE ENTIRE BUILDING. |
| | FBC 107.2.1.2 |
| | |
| | 37) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL |
| | MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE |
| | DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE |
| | SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT |
| | BEFORE THEY CAN BE INSTALLED. |
| | |
| | 38) FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES |
| | OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS |
| | THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT |
| | THE TIME OF THE APPLICATION AND THAT ARE TO BE |
| | SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED |
| | PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE |
| | PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 39) SHOW COMPLIANCE FBC ACCESSIBILITY SECTION 242 FOR |
| | ACCESSIBLE ENTRY INTO THE POOL OR SPECIFY ON THE PLANS |
| | WHY IT IS NOT REQUIRED. COMMUNITY POOLS THAT ARE |
| | ASSOCIATED WITH A PRIVATE RESIDENTIAL COMMUNITY THAT DO |
| | NOT RECEIVE GOVERNMENTAL FINANCIAL ASSISTANCE OR |
| | SPONSORSHIP AND ARE LIMITED TO THE EXCLUSIVE OF |
| | RESIDENTS AND THEIR GUESTS ARE NOT COVERED BY THE ADA |
| | ACCESSIBILITY REQUIREMENTS, INCLUDING PROVISIONS FOR |
| | POOL LIFTS OR SLOPED ENTRIES. IF A SWIMMING POOL |
| | LOCATED IN A RESIDENTIAL COMMUNITY IS MADE AVAILABLE TO |
| | THE PUBLIC FOR RENTAL OR USE IT IS REQUIRED TO COMPLY |
| | WITH TITLE II OF THE ADA. SPECIFY ON THE PLANS THE |
| | FORMER OR SHOW COMPLIANCE WITH THE LATTER STATEMENTS. |
| | SEE DECLARATORY STATEMENT, DS 2013-011. |
| | |
| | 40) SEPARATE PERMITS, REVIEWS AND FEES ARE REQUIRED FOR |
| | SOME ITEMS THAT MAY HAVE BEEN INCLUDED IN THE VALUE FOR |
| | THIS PROJECT. ITEMS SUCH AS FIRE ALARM, FIRE SPRINKLER, |
| | LOW VOLTAGE, LANDSCAPING, IRRIGATION AND ALL ITEMS |
| | OTHER THAN BUILDING, MECHANICAL, ELECTRIC AND PLUMBING. |
| | PLEASE PROVIDE A COST BREAKDOWN SO THAT WE CAN DEDUCT |
| | THESE ITEMS FROM THE PERMIT VALUE SO THAT YOU WILL NOT |
| | BE CHARGED TWICE FOR THE SAME ITEM. |
| | |
| | 41) THE REST./RETAIL AREAS ON THE GROUND FLOOR HAVE |
| | DOORS THAT OPEN INTO THE PARKING GARAGE. IT APPEARS |
| | THAT THESE ARE MEANT TO BE REQUIRED EXITS. TABLE 508.4 |
| | REQUIRES A ONE HOUR FIRE SEPARATION BETWEEN S-2 AND M |
| | OR B OCCUPANCIES IN A SPRINKLERED BUILDING. IF THESE |
| | ARE REQUIRED EXITS THEY WILL BE REQUIRED TO BE |
| | CONNECTED TO A ONE HOUR RATED CORRIDOR SEPARATING THEM |
| | FROM THE PARKING GARAGE AND DISCHARGING TO THE EXTERIOR |
| | OF THE BUILDING. |
| | |
| | 42) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | |
| | |