Plan Review Notes
Plan Review Notes For Permit 20011267
Permit Number 20011267
Review Stop B
Sequence Number 1
Notes
Date Text
2020-03-06 14:10:11PLAN REVIEW COMMENTS
 THRESHOLD BUILDING
 8 STORY APARTMENT BUILDING (MIXED USE M, S-2, R-2, A-3
 AND B)
 CONST. TYPE 1-A, SPRINKLERED
 170 MPH, EXPOSURE "D"
 FLOOD ZONE "X"
 625 S. OLIVE AVE.
 PERMIT #20011267
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. PER
 CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND CITY
 OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, ART
 IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST. PER CITY OF WEST PALM BEACH
 CODE OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES,
 SECTION 78-122, RENOVATION AND NEW CONSTRUCTION
 PROJECTS ARE ASSESSED CUMULATIVELY, SO THE ART
 ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE PROJECTS.
 FOR INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR AT
 822-1515 OR E-MAIL: [email protected]
  
 2) THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE CURRENT ( OCTOBER
 2018 ) CITY GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING THRESHOLD/SPECIAL INSPECTORS AND RESIDENT
 INSPECTORS.
  
 3) THE GEOTECHNICAL REPORT THAT WAS SUBMITTED INDICATES
 THAT THE RECOMMENDED VIBRO COMPACTION SOIL PREPARATION
 WILL PRODUCE A SOIL BEARING VALUE OF UP TO 6,000 PSF.
 NOTE 3A ON SHEET S200 OF THE PLANS STATES THAT THE
 BUILDING DESIGN REQUIRES A SOIL BEARING CAPACITY OF
 8,000 PSF. PLEASE INDICATE HOW THIS WILL BE ADDRESSED.
 FBC 1801.2
  
 4) SPECIFY HOW COMPLIANCE WITH FBC CHAPTER 33
 SAFEGUARDS DURING CONSTRUCTION FOR THE FOUNDATION
 PERMIT WILL BE MET.
  
 5) FBC 3002.4 REQUIRES ANY BUILDING THAT IS MORE THAN
 THREE STORIES HIGH OR IN WHICH THE VERTICAL DISTANCE
 BETWEEN THE BOTTOM TERMINAL LANDING AND THE TOP
 TERMINAL LANDING EXCEEDS 25 FEET TO BE CONSTRUCTED TO
 CONTAIN AT LEAST ONE PASSENGER ELEVATOR THAT IS
 OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE DEPARTMENT
 ACCESS TO ALL FLOORS. THE ELEVATOR CAR SHALL BE OF A
 SIZE AND ARRANGEMENT TO ACCOMMODATE AN AMBULANCE
 STRETCHER 24 INCHES BY 76 INCHES WITH NOT LESS THAN
 5-INCH RADIUS CORNERS, IN THE HORIZONTAL, OPEN POSITION
 AND SHALL BE IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR
 EMERGENCY MEDICAL SERVICES (STAR OF LIFE).
  
 6) THE TRASH CHUTE DISCHARGE ROOM IS REQUIRED TO BE
 SEPARATED BY FIRE BARRIERS WITH A FIRE-RESISTANCE
 RATING NOT LESS THAN THE REQUIRED FIRE RATING OF THE
 SHAFT ENCLOSURE. FBC 713.13.4
  
 7) THE EXIT PASSAGEWAY AT STAIR 01 IS INCORRECTLY
 LABELED AS AN EXIT ACCESS CORRIDOR. AN EXIT PASSAGEWAY
 IS AN EXTENSION OF THE ENCLOSED INTERIOR EXIT STAIRWAY
 AND HAS REQUIREMENTS SIMILAR TO THE STAIRWAY. PLEASE
 CORRECT. SEE FBC 1023.1 AND 1024.
  
 8) PROVIDE A SITE PLAN WITH ELEVATIONS SHOWN IN NAVD
 88. THERE WAS ONE WITH THE FOUNDATION PLAN, BUT IT
 APPEARS TO BE MISSING FROM THESE DOCUMENTS. FBC
 107.2.1.2
 PLEASE REVIEW THE ELEVATIONS OF THE GRADE AROUND THE
 EXTERIOR OF THE BUILDING AND COMPARE THEM WITH THE
 FLOOR ELEVATION (11.97') OF THE BUILDING TO MAKE SURE
 THAT THE EXITS DISCHARGE AT GRADE AND THE ELEVATIONS
 AND SLOPES OF LANDINGS AND WALK WAYS WILL MEET THE
 RUNNING SLOPE AND CROSS SLOPE REQUIREMENTS OF THE
 FLORIDA ACCESSIBILITY CODE SECTION 403.
  
 9) THE AR-RENDERINGS APPEAR TO BE MISLABELED. PLEASE
 CLARIFY. FBC 107.2.1
  
 10) FBC TABLE 602 REQUIRES MERCANTILE OCCUPANCIES TO
 HAVE 2 HOUR FIRE RESISTANCE RATED EXTERIOR WALLS FOR
 LESS THAN 10 FT OF FIRE SEPARATION DISTANCE. THIS IS
 NOT REFLECTED IN THE CODE DATA ON SHEET CD-1. HOWEVER,
 THIS DOES NOT APPEAR TO BE AN ISSUE FOR YOUR PROJECT.
  
 11) ON SHEET CD-01 AND THE OTHER EXISTING PLANS THE
 RISK CATEGORY IN CODE DATA TABLE HAS BROWARD COUNTY AND
 THIS PROJECT IS LOCATED IN PALM BEACH COUNTY. PLEASE
 CORRECT. FBC 107.2.1
  
 12) PLEASE REMOVE THE RED DASHED CIRCLES FROM THE
 EXITING PLANS ON SHEETS CD-01 AND CD-02. THEY MAKE THE
 DRAWINGS DIFFICULT TO REVIEW. FBC 107.2.1.3
  
 13) THERE IS A STAIR #04 SHOWN ON THE PLANS BETWEEN THE
 2ND AND 3RD LEVELS OF THE PARKING GARAGE WITH A NOTE
 (WHICH IS MISLABELED AS STAIR 03 ON CD-02) THAT IT IS
 TO PREVENT A DEAD END CONDITION AT LEVEL 3. PLEASE
 CLARIFY.
  
 14) THE COMMERCIAL AREAS ON THE GROUND FLOOR EXITING
 PLAN ARE LABELED RESTAURANT/RETAIL AND THE OCCUPANT
 LOADS PROVIDED ARE FOR MERCANTILE. A RESTAURANT WOULD
 BE AN A-2 ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD OF
 15 NET WHICH WOULD BE MORE THAN THE 60 SQFT FOR
 MERCANTILE. PLEASE USE THE MOST RESTRICTIVE OCCUPANT
 LOAD. FBC 1004.1
  
 15) THE COVERED OUTDOOR RESTAURANT SEATING SHOULD BE
 LABELED A-2 RATHER THAN A-3 PER FBC 303.3. PLEASE
 CORRECT.
  
 16) SHOW COMPLIANCE WITH FBC 3002.4 FOR THE REQUIREMENT
 TO PROVIDE AN ELEVATOR CAR THAT WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 24" X 76".
  
 17) VERIFY THE REQUIRED VERTICAL CLEARANCE OF 98 INCHES
 FOR THE VAN PARKING SPACE, ACCESS AISLE AND VEHICULAR
 ROUTE SERVING IT AS REQUIRED BY FBC ACCESSIBILITY
 SECTION 502.5.
  
 18) THE PARKING DATA ON SHEET GN-00 HAS 20 COMMERCIAL
 SPACES AND 183 RESIDENTIAL SPACES. TABLE 208.2 IN THE
 FBC ACCESSIBILITY REQUIRES A MINIMUM OF 1 ACCESSIBLE
 PARKING SPACE WHEN THE TOTAL NUMBER OF SPACES PROVIDED
 IS 1 TO 25. THE FAIR HOUSING GUIDELINES REQUIRE AT
 LEAST 2 PERCENT OF THE COVERED RESIDENTIAL UNITS TO
 HAVE ACCESSIBLE PARKING WHICH IS 4 SPACES. THIS PROJECT
 IS REQUIRED TO HAVE A MINIMUM OF 5 ACCESSIBLE PARKING
 SPACES. THE PLANS SHOW ONLY 4 ACCESSIBLE SPACES.
 SECTION 208.2.4 REQUIRES AT LEAST ONE VAN PARKING SPACE
 COMPLYING WITH SECTION 502 FOR EVERY SIX OR FRACTION OF
 SIX REQUIRED ACCESSIBLE SPACES.
  
 19) PLEASE LABEL THE EXIT PASSAGEWAY THAT CONNECTS
 STAIR #01 TO THE EXIT DISCHARGE. SEE FBC SECTION 1024
 FOR THE REQUIREMENTS OF AN EXIT PASSAGEWAY WHICH
 EXTENDS THE INTERIOR EXIT STAIRS TO THE EXTERIOR OF THE
 BUILDING AND IS TREATED THE SAME AS AN ENCLOSED EXIT
 STAIR WAY.
  
 20) THE EXIT DOOR SIZE AND CALCULATIONS ARE NOT
 PROVIDED FOR THE EXIT DISCHARGE DOOR AT THE EXIT
 PASSAGEWAY FOR STAIR #01 ON SHEET CD-01.
  
 21) ON SHEET CD-04, DEAD END PATH A IS NOT IDENTIFIED.
 FBC 107.2.1
  
 22) A PORTION OF PATH B IS MISSING ON THE DRAWING. FBC
 107.2.1
  
 23) THE EXIT ACCESS TRAVEL DISTANCE IS MEASURED FROM
 THE MOST REMOTE POINT WITHIN A STORY ALONG THE NATURAL
 AND UNOBSTRUCTED PATH OF EGRESS TRAVEL TO AN EXIT. THE
 MOST REMOTE POINT WOULD BE FROM THE CORNER OF THE
 BALCONIES IN THE ROOMS. FBC 1017.3
  
 24) SHOW THE TRAVEL PATHS FROM THE POOL DECK/POOL AREA
 TO THE EXITS. FBC 1017.3
  
 25) IN ADDITION TO THE EXIT CAPACITY AT EACH EXIT DOOR
 ON THE FLOOR, INDICATE THE NUMBER OF OCCUPANTS THAT
 WILL BE USING EACH OF EXITS. FBC SECTION 1006 AND FBC
 107.2.1.2
  
 26) THE OCCUPANT LOADS ARE TOTALS AND THE DISPERSION OF
 OCCUPANTS TO EACH OF THE EXITS IS NOT SHOWN ON THE
 PLANS. SHOW THE NUMBER OF OCCUPANTS FOR EACH ROOM OR
 AREA AND WHICH EXIT THEY WILL USE. FBC 107.2.1
  
 27) SHOW THE EGRESS PATHS AND EXIT DOORS FOR THE
 OUTDOOR TERRACE, CLUBROOM, FITNESS ROOM AND AMENITY
 DECK SHOWN ON SHEET CD-04. FBC 1007
  
 28) THE EXIT DOOR TO STAIR #03 FROM THE POOL DECK ON
 LEVEL 4 IS SPECIFIED WITH A WITH A 19 INCH CLEAR WIDTH.
 FBC 1010.1.1 REQUIRES A MINIMUM CLEAR OPENING WIDTH OF
 32 INCHES. THE SIZES FOR THE DOORS TO THIS STAIR ARE
 NOT PROVIDED ON LEVELS 2 AND 3. FBC 107.2.1
  
 29) THE DOORS TO OTHER STAIRS ARE MISSING EGRESS
 INFORMATION ALSO. FBC 107.2.1
  
 30) SHOW THE EXIT PATHS OF TRAVEL AND TRAVEL DISTANCES
 FOR EACH LEVEL OF THE GARAGE. FBC 1006
  
 31) THE FIRST LEVEL OF THE PARKING GARAGE IS ENCLOSED
 WITH MECHANICAL VENTILATION REQUIRED. THE SECOND AND
 THIRD LEVELS ARE AN OPEN GARAGE. FBC TABLE 705.8
 FOOTNOTE "G" ALLOWS UNLIMITED OPENINGS IN OPEN PARKING
 STRUCTURES WHICH APPLIES TO LEVEL 2 AND 3 OF THE
 GARAGE. THE WEST ELEVATION IS 10'-1" FROM THE PROPERTY
 LINE WHICH IS ALSO THE FIRE SEPARATION DISTANCE. TABLE
 705.8 ALLOWS A SPRINKLERED BUILDING THAT HAS 10 FEET TO
 15 FEET OF FIRE SEPARATION DISTANCE TO HAVE 45 PERCENT
 OF THE WALL AREA OF EACH STORY TO BE OPEN. PLEASE
 PROVIDE THE CALCULATIONS FOR THE ALLOWABLE OPEN AREA OF
 EACH OF STORIES OTHER THAN THE OPEN LEVELS OF THE
 PARKING GARAGE FOR THE WEST ELEVATION AND THE PORTION
 OF THE SOUTH ELEVATION THAT IS 10' 1-7/8" FROM THE
 PROPERTY LINE TO SHOW COMPLIANCE WITH FBC 705.8.
  
 32) THE HANDRAIL EXTENSION AT THE BOTTOM OF STAIRS ARE
 REQUIRED TO EXTEND AT THE SLOPE OF THE STAIR FLIGHT FOR
 A HORIZONTAL DISTANCE AT LEAST EQUAL TO ONE TREAD DEPTH
 BEYOND THE LAST RISER NOSING. SEE FBC ACCESSIBILITY
 SECTION 505.10.3. IT IS SHOWN WITH A HORIZONTAL
 EXTENSION ON THE STAIR SECTION ON SHEET A7-01, A7-03
  
 33) FBC 913.2.1 REQUIRES THE FIRE PUMP ROOM TO BE
 SEPARATED FROM ALL OTHER AREAS OF THE BUILDING BY
 2-HOUR FIRE BARRIERS.
  
 34) THE TRASH (WASTE) CHUTE IS REQUIRED TO DISCHARGE
 INTO AN ENCLOSED ROOM SEPARATED BY FIRE BARRIERS WITH A
 FIRE-RESISTANCE RATING NOT LESS THAN THE REQUIRED FIRE
 RESISTANCE RATING OF THE SHAFT ENCLOSURE PER FBC
 713.13.4.
  
 35) STAIR NUMBER FOUR ON SHEET A7-04 DOES NOT HAVE THE
 REQUIRED HANDRAIL EXTENSION AT THE BOTTOM OF STAIRS.
 HANDRAILS ARE REQUIRED TO EXTEND AT THE SLOPE OF THE
 STAIR FLIGHT FOR A HORIZONTAL DISTANCE AT LEAST EQUAL
 TO ONE TREAD DEPTH BEYOND THE LAST RISER NOSING. SEE
 FBC ACCESSIBILITY SECTION 505.10.3.
  
 36) PROVIDE AREA TABULATIONS FOR THE ENTIRE BUILDING.
 FBC 107.2.1.2
  
 37) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE
 DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE
 SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT
 BEFORE THEY CAN BE INSTALLED.
  
 38) FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES
 OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS
 THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT
 THE TIME OF THE APPLICATION AND THAT ARE TO BE
 SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED
 PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE
 PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 39) SHOW COMPLIANCE FBC ACCESSIBILITY SECTION 242 FOR
 ACCESSIBLE ENTRY INTO THE POOL OR SPECIFY ON THE PLANS
 WHY IT IS NOT REQUIRED. COMMUNITY POOLS THAT ARE
 ASSOCIATED WITH A PRIVATE RESIDENTIAL COMMUNITY THAT DO
 NOT RECEIVE GOVERNMENTAL FINANCIAL ASSISTANCE OR
 SPONSORSHIP AND ARE LIMITED TO THE EXCLUSIVE OF
 RESIDENTS AND THEIR GUESTS ARE NOT COVERED BY THE ADA
 ACCESSIBILITY REQUIREMENTS, INCLUDING PROVISIONS FOR
 POOL LIFTS OR SLOPED ENTRIES. IF A SWIMMING POOL
 LOCATED IN A RESIDENTIAL COMMUNITY IS MADE AVAILABLE TO
 THE PUBLIC FOR RENTAL OR USE IT IS REQUIRED TO COMPLY
 WITH TITLE II OF THE ADA. SPECIFY ON THE PLANS THE
 FORMER OR SHOW COMPLIANCE WITH THE LATTER STATEMENTS.
 SEE DECLARATORY STATEMENT, DS 2013-011.
  
 40) SEPARATE PERMITS, REVIEWS AND FEES ARE REQUIRED FOR
 SOME ITEMS THAT MAY HAVE BEEN INCLUDED IN THE VALUE FOR
 THIS PROJECT. ITEMS SUCH AS FIRE ALARM, FIRE SPRINKLER,
 LOW VOLTAGE, LANDSCAPING, IRRIGATION AND ALL ITEMS
 OTHER THAN BUILDING, MECHANICAL, ELECTRIC AND PLUMBING.
 PLEASE PROVIDE A COST BREAKDOWN SO THAT WE CAN DEDUCT
 THESE ITEMS FROM THE PERMIT VALUE SO THAT YOU WILL NOT
 BE CHARGED TWICE FOR THE SAME ITEM.
  
 41) THE REST./RETAIL AREAS ON THE GROUND FLOOR HAVE
 DOORS THAT OPEN INTO THE PARKING GARAGE. IT APPEARS
 THAT THESE ARE MEANT TO BE REQUIRED EXITS. TABLE 508.4
 REQUIRES A ONE HOUR FIRE SEPARATION BETWEEN S-2 AND M
 OR B OCCUPANCIES IN A SPRINKLERED BUILDING. IF THESE
 ARE REQUIRED EXITS THEY WILL BE REQUIRED TO BE
 CONNECTED TO A ONE HOUR RATED CORRIDOR SEPARATING THEM
 FROM THE PARKING GARAGE AND DISCHARGING TO THE EXTERIOR
 OF THE BUILDING.
  
 42) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  