| 2020-11-17 15:49:47 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20011223 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE A LETTER FROM THE DRYER MANUFACTURER |
| | STATING THAT THE X VENT DRYER EXHAUST TERMINATION IS |
| | ALLOWED WITH THEIR DRYER. THE X VENT IS UNIQUE IN THE |
| | FACT THAT IT USES BOTH THE BACK-DRAFT DAMPER AND THE |
| | LOUVER. THE INSTALLATION MANUAL DOES NOT ADDRESS THIS |
| | KIND OF INSTALLATION. WITH THE X VENT SYSTEM THE BOX OF |
| | THE X VENT IS MOUNTED INTO THE EXTERIOR OF THE WALL AND |
| | THE LOUVER IS FLUSH TO THE EXTERIOR WALL. THE EXHAUST |
| | OF THE DRYER MUST TRAVEL THROUGH THE EXHAUST DUCT, OPEN |
| | THE BACK-DRAFT DAMPER AND TRAVEL THROUGH THE X VENT |
| | COVER (LOUVER) BEFORE IT IS EXHAUSTED TO THE OUTDOORS. |
| | BECAUSE THIS PRODUCT USES BOTH THE BACK-DRAFT DAMPER |
| | AND THE OUTER COVER OF THE BOX (LOUVER) INSTEAD OF |
| | EITHER THE BACK-DRAFT DAMPER OR THE LOUVER THE DRYER |
| | MANUFACTURER MUST ADDRESS THE ASSEMBLY. WE MUST HAVE AN |
| | APPROVAL LETTER FROM THE SPECIFIC DRYER MANUFACTURER |
| | FOR THE SPECIFIC DRYER USED IN THIS PROJECT. FBC M |
| | 504.8.4.2 |
| | YOU CAN SUBMIT THE DOCUMENTATION THAT WAS SUBMITTED TO |
| | THE PRIVATE PROVIDER AS PROOF THAT THE XVENT |
| | TERMINATION CAN BE USED WITH THE SPECIFIED DRYERS OR |
| | THE ENGINEER OF RECORD CAN SUBMIT CALCULATIONS |
| | ADDRESSING THE RESTRICTION OF BOTH THE BACKDRAFT DAMPER |
| | AND THE LOUVER AND HOW THIS WILL EFFECT THE DRYER DUCT |
| | LENGTHS. |
| | |
| | |
| | 2) PREVIOUS CYCLE RESPONSE FROM DESIGNER STATED ? FBC |
| | M REQUIRED AMCA 550 RATINGS ONLY FOR LOUVERS. |
| | RESIDENTIAL BATHROOM AND DRYER EXHAUST VENTS DO NOT |
| | CLASSIFY AS LOUVERS THEREFORE THE REQUIREMENT SHOULD |
| | NOT APPLY.? AS THIS IS A COMMERCIAL BUILDING AND NOT |
| | EITHER A ONE OR TWO FAMILY DWELLING AND THE FACT THAT |
| | THE X VENT DOCUMENTATION SUBMITTED DOES CALL THE OUTER |
| | SECTION A LOUVER THE REVIEWERS COMMENT DOES APPLY AND |
| | MUST BE ADDRESSED. PLEASE PROVIDE SPECIFICATIONS THAT |
| | SHOW THE LOUVER SIZE MEETS FBC M 501.3.2. ?OPENINGS IN |
| | LOUVERS SHALL BE SIZED NOT LESS THAN ?? AND NOT LARGER |
| | THAN ??. PLEASE PROVIDE DOCUMENTATION IF THERE IS AN |
| | EXCEPTION FOR THE SIZES OF THE X VENT LOUVERS |
| | |
| | 3) WE ARE ENFORCING THE 2017 FBC MECHANICAL, THE CODE |
| | SECTION MENTIONED IN THE RESPONSE LETTER (2018 IMC |
| | 504.4.1) DOES NOT EXIST IN OUR CURRENT CODE BOOK. |
| | ACCORDING TO THE 2018 IMC COMMENTARY, 504.4.1 EXHAUST |
| | TERMINATION OUTLET AND PASSAGEWAY SIZE SHALL NOT BE |
| | DIMINISHED IN SIZE. PLEASE SHOW THAT THE LOUVERS MEET - |
| | FBC M 501.3.2 |
| | |
| | 4) SHEET M-2.1A; ALL TYPE I HOODS THAT PENETRATE A FIRE |
| | RATED ASSEMBLY MUST BE WRAPPED FROM THE HOOD TO THE |
| | POINT OF PENETRATION TO THE OUTLET TERMINAL. IN-LINE |
| | EXHAUST FANS NOT LOCATED OUTDOORS SHALL BE ENCLOSED AS |
| | REQUIRED FOR GREASE DUCTS. FBC M 506.3.11 |
| | |
| | 5) SHEET M-2.1A; AIR BALANCE REPORT: DESIGN PLANS FOR A |
| | FACILITY WITH A COMMERCIAL KITCHEN VENTILATION SYSTEM |
| | SHALL INCLUDE A SCHEDULE OR DIAGRAM INDICATING THE |
| | DESIGN OUTDOOR AIR BALANCE. THE DESIGN OUTDOOR AIR |
| | BALANCE SHALL INDICATE ALL EXHAUST AND REPLACEMENT AIR |
| | FOR THE FACILITY, PLUS THE NET EXFILTRATION IF |
| | APPLICABLE. THE TOTAL REPLACEMENT AIR AIRFLOW RATE |
| | SHALL EQUAL THE TOTAL EXHAUST AIRFLOW RATE PLUS THE NET |
| | EXFILTRATION. FBC M 508.1.2 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |