| 2020-10-16 10:40:56 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20011223 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE LOUVER OF THE XVENT WILL RESTRICT THE EXHAUST |
| | FLOW OF THE DRYER. PLEASE PROVIDE A LETTER FROM THE |
| | MANUFACTURE OF THE DRYER STATING THAT THE DRYER WILL IN |
| | FACT WORK WITH THE XVENT. FBC M 504.8.4.2 |
| | |
| | 2) PLEASE PROVIDE SPECIFICATIONS FOR THE XVENT EXHAUST |
| | TERMINATION SHOWING THEY COMPLY WITH AMCA STANDARD 550 |
| | . FBC M 501.3.2 |
| | |
| | 3) PLEASE PROVIDE SPECIFICATIONS FOR THE XVENT EXHAUST |
| | TERMINATION INDICATING THE OPENINGS AT THE TERMINATION |
| | FACE MEETS THE SIZES REQUIRED IN FBC M 501.3.2 (MINIMUM |
| | ?? AND NOT LARGER THAN ??) |
| | |
| | 4) PLEASE SHOW DRYER DUCT WORK AND LOCATION OF |
| | TERMINATION FOR THE LAUNDRY ROOM DRYERS. FBC M 504.9 |
| | |
| | 5) THE AIR BALANCE REPORT ON SHEET M-2.1A MUST MEET FBC |
| | M 508.1.2. |
| | |
| | 6) SHEET M2.1A: THE FD?S ARE STILL BEING SHOWN IN THE |
| | GREASE DUCT FOR KEF-1 AND KEF-3 AND KEF-4. AS THESE ARE |
| | RATED WALLS PER SHEET LS-0.1 ALL GREASE DUCT MUST |
| | COMPLY WITH FBC M 506.3.11 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |