| Plan Review Notes For Permit 20011223 |
| Permit Number |
20011223 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-10-20 07:58:29 | NEW 8 STORY BUILDING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) THE WIND DESIGN DATA HAS BEEN REVISED ON THE | | | STRUCTURAL DRAWINGS BUT NOT ON THE PROVIDED STRUCTURAL | | | CALCULATIONS - PLEASE REVISE THE STRUCTURAL | | | CALCULATIONS TO MATCH THE WIND DESIGN DATA SHOWN ON THE | | | STRUCTURAL DRAWINGS. | | | | | | DEFERRED ITEMS ? TO BE REVIEWED AND MARKED APPROVED BY | | | THE BUILDING DESIGNER OF RECORD AND REVIEWED BY THE | | | BUILDING DIVISION PLAN REVIEW BEFORE INSTALLATION - | | | 1) EXTERIOR WINDOW, DOOR AND LOUVER PRODUCT APPROVALS. | | | FBC 1609 | | | 2) SHORING AND RESHORING PLANS. FBC 110.8.4.3 | | | 3) GUARD RAILING. FBC 1607.8 | | | 4) ROOFING SYSTEM PRODUCT APPROVALS. FBC 1609.5.2 | | | 5) ROOF TOP EQUIPMENT SCREENING. FBC 1510.6 | | | 6) POOL. FBC 454 | | | 7) ACOUSTICAL TEST REPORTS FOR THE FLOOR/CEILING | | | ASSEMBLIES IIC AND STC PER FBC 1207 AND FLAME SPREAD | | | INDEX PER FBC 603.1 | | | 8) TRELLIS DETAILS. | | | 9) METAL CANOPIES. | | | | | | |
|