| 2020-08-17 16:04:56 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20011223 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) PLEASE SHOW RATED WALLS ON ALL OF THE MECHANICAL |
| | SHEETS. FBC FS 107.2.1 |
| | |
| | 2) SHEET LS-0.0 THE ENERGY CALCULATIONS PRESENTED IN |
| | THIS PACKAGE IS FOR MULTI-FAMILY. PLEASE SPECIFY EACH |
| | OCCUPANCY BASED ON THE FBC CHAPTER 3. |
| | |
| | 3) PLEASE PROVIDE ENERGY CALCULATIONS FOR EACH OF THE |
| | OCCUPANCY CLASSIFICATIONS. FBC EC 403 |
| | |
| | 4) IN THE R-2 OCCUPANCIES PLEASE SHOW WHICH METHOD IS |
| | USED FOR VENTILATION; NATURAL OR MECHANICAL. PROVIDE |
| | CALCULATIONS FOR THE ONE THAT IS USED. FBC M CHAPTER 4 |
| | |
| | 5) PLEASE REMOVE THE NOTE AT THE BOTTOM LEFT OF THE |
| | MECHANICAL SHEETS AS THESE SHOULD BE CONSTRUCTION |
| | DOCUMENTS NOT FOR INITIAL PERMIT REVIEW. FBC FS 107.2.1 |
| | |
| | 6) PLEASE PROVIDE DUCT GRILL SIZES FOR ALL SHEETS. FBC |
| | FS 107.2.1 |
| | |
| | 7) PLEASE PROVIDE RETURN AIR TRANSFER SIZES IN ALL |
| | LIVING QUARTERS. FBC FS 107.2.1 |
| | |
| | 8) SHEET M-6.4: VENTILATION EQUIPMENT SCHEDULE (TOP |
| | CHART) SHOWS 6 NOTES. NOTE 6 HAS BEEN LEFT BLANK. |
| | PLEASE SHOW THE NOTE OR IF THERE IS NO NOTE REMOVE THE |
| | NUMBER 6. FBC FS 107.2.1 |
| | |
| | |
| | 9) SHEET M-6.5 SHOWS OUTSIDE AIR CALCULATIONS FOR |
| | (RESIDENTIAL) ENERGY CALCULATIONS INDICATES 0 CFM |
| | OUTSIDE AIR FOR (SENIOR UNITS) PLEASE BE CONSISTENT ON |
| | BOTH. FBC FS 107.2.1 |
| | |
| | 10) SHEET M-6.4 DESIGNATES OUTSIDE AIR CALCULATIONS FOR |
| | THIS BUILDING. PLEASE REFLECT THESE CALCULATIONS ON THE |
| | ENERGY CALCULATIONS SUBMITTED, SEVERAL AREAS INDICATE 0 |
| | CFM OUTSIDE AIR. FBC M 401. |
| | |
| | 11) PLEASE SHOW HOW YOU ARE PROVIDING OUTDOOR AIR FOR |
| | ALL LOUNGES. FBC M 401 |
| | |
| | |
| | 12) PLEASE PROVIDE CALCULATIONS AND WAY NATURAL |
| | VENTILATION IS PROVIDED ON ALL AREAS THAT ARE USING |
| | NATURAL VENTILATION. FBC M 402 |
| | |
| | |
| | 13) SHEET M-5.1 DRAWING 1- PLEASE PROVIDE THE TYPE OF |
| | MATERIAL USED FOR THE A/C CONDENSATE DRAIN PIPE IN THIS |
| | PLENUM AREA. FBC M 602.2.1 |
| | |
| | |
| | 14) SHEET M-5.1 DRAWING 8- PLEASE PROVE THE SIGNED AND |
| | SEALED DRAWINGS FOR THE ELEVATOR SHAFT RELIEF LOUVER. |
| | FBC FS 107.2.1 |
| | |
| | 15) SHEET M-5.1 DRAWING 3- PLEASE SHOW HOW THIS X-VENT |
| | FOR A DRYER DUCT MEETS- FBC M 504.4 FOR NO SCREENS AT |
| | DUCT TERMINATION AND THE WAY THIS APPEARS TO OPEN FROM |
| | THE MIDDLE, HOW THE BACKDRAFT DAMPER WILL NOT GATHER |
| | LINT. |
| | |
| | |
| | 16) SHEET M-5.1: DRAWING (2) INDICATES A FRESH AIR DUCT |
| | RAN INTO THE MECHANICAL CLOSETS OF THE APARTMENTS. |
| | PLEASE SHOW THESE, THE CEILING ACCESS PANEL AND THE |
| | OUTDOOR AIR TERMINATION ON THE EXTERIOR OF THE |
| | BUILDING, ON ALL THE UNIT DRAWINGS THAT ARE GOING TO |
| | HAVE THESE INSTALLED. FBC FS 107.2.1 |
| | |
| | 17) PROVIDE A COPY OF THE INSTALLATION INSTRUCTIONS FOR |
| | THE MAKE AND MODEL OF THE DRYER FOR EVERY RESIDENTIAL |
| | DRYER WITH AN EXHAUST DUCT LENGTH OVER 35?. FBC M |
| | 504.8.4.2 |
| | |
| | |
| | 18) WHERE THE DRYER EXHAUST DUCT EQUIVALENT LENGTH |
| | EXCEEDS 35? THE EQUIVALENT LENGTH OF THE DUCT SHALL BE |
| | IDENTIFIED ON A PERMANENT LABEL OR TAG. THE LABEL OR |
| | TAG SHALL BE LOCATED WITHIN 6? OF THE EXHAUST DUCT |
| | CONNECTION. FBC M 504.8.5 |
| | |
| | 19) PLEASE SHOW KITCHEN VENTILATION FOR ALL DWELLING |
| | UNITS THAT ARE PROVIDED WITH A KITCHEN. FBC M TABLE |
| | 403.3.1.1 |
| | |
| | |
| | 20) SHEET M-4.3 PLEASE SHOW THE RETURN PATH TO THE |
| | AHU?S THROUGH THE DOOR OF THE MECHANICAL CLOSETS. FBC M |
| | 601.6 |
| | |
| | 21) SHEET M-4.3 UNIT IL-A4- PLEASE SHOW THE RETURN AIR |
| | PATH FROM MASTER BEDROOM. FBC M 601.6 |
| | |
| | 22) SHEET M-4.3 PLEASE PROVIDE THE DISTANCE FROM THE |
| | COOKING APPLIANCE AND THE RETURN AIR OPENINGS. FBC M |
| | 601.5 |
| | |
| | |
| | 23) M-4. SHEETS. PLEASE SHOW HOW YOU ARE PROVIDING |
| | MAKE-UP AIR FOR THE DRYER. FBC M 504.6 |
| | |
| | 24) M-4. SHEETS- PLEASE SHOW THE ENTIRE DRYER DUCT IN |
| | THE APARTMENTS GOING FROM DRYER TO TERMINATION, THEY |
| | APPEAR TO STOP AT THE BATH EXHAUST DUCT. FBC FS 107.2.1 |
| | |
| | |
| | 25) ON THE UNIT DRAWINGS THERE ARE UNITS THAT HAVE A |
| | TOILET ROOM ENCLOSED IN THE BATHROOM, PLEASE PROVIDE |
| | BATHROOM EXHAUST IN THE BATHROOM ALSO. FBC M BATHROOM |
| | DEFINITION; FBC M TABLE 4.3.3.1.1 |
| | |
| | 26) SHEET M-4.SHEETS- PLEASE SHOW THAT THE EXHAUST |
| | TERMINATIONS ARE A MINIMUM OF 3? FROM OPERABLE OPENINGS |
| | INTO THE UNIT. FBC M 501.3.1 (3) |
| | |
| | 27) SHEET M-4.7: UNIT IL-D1- PLEASE SHOW THE RETURN |
| | PATH FOR THE DEN. FBC FS 107.2.1 |
| | |
| | 28) SHEET M-2.5B: PLEASE REMOVE ALL CLOUDS FROM SHEETS |
| | AS THIS IS A 1ST CYCLE REVIEW. FBC FS 107.2.1 |
| | |
| | 29) SHEET M-2.5B: PLEASE SHOW HOW CORRIDOR AT W BATH |
| | B505 AND M BATH B504 IS VENTILATED. FBC M TABLE |
| | 403.3.1.1 |
| | |
| | 30) SHEET M-2.5B : PLEASE SHOW AND IDENTIFY THE EXHAUST |
| | FANS IN THE MENS AND WOMENS BATHROOMS. FBC FS 107.2.1 |
| | |
| | |
| | 31) SHEET M-7.1 VENTILATION RISER DIAGRAM CFM?S DO NOT |
| | MATCH BLDG. PLAN LEVEL SHEETS. EXAMPLES ARE- PLEASE |
| | CHECK THE CFM?S OF THE ACS AT EACH FLOOR. ACS-2 SHOWS |
| | 650 CFM PER FLOOR. SHEETS M-2.6A AND M-2.6B SHOWS ONLY |
| | 400 CFM PER FLOOR. ACS-3 SHOWS 550 FOR EACH FLOOR, |
| | BLDG.. PLAN LEVEL SHEETS SHOW 370 CFM. FBC FS 1.7.2.1 |
| | |
| | 32) IDENTIFY EACH MAU RISER ON EACH FLOOR AT THE SHAFT |
| | WHERE IT ENTERS THE FLOOR. FBC FS 107.2.1 |
| | |
| | 33) SHEET M-2.3.1: THE STORAGE ROOM IS ACCESSED THROUGH |
| | THE PARKING GARAGE. PLEASE PROVIDE A FD FOR THE DUCT |
| | WORK PENETRATING THE RATED WALL AT CORRIDOR AND STORAGE |
| | ROOM. FBC FS 107.2.1 |
| | |
| | 34) PLEASE LABEL WASHERS AND DRYERS IN EACH LAUNDRY |
| | AREA TO PROVIDE A COUNT OF EACH. FBC FS 107.2.1 |
| | |
| | 35) PROVIDE CLOTHES DRYER SPECS AND DUCT SIZES FOR |
| | EACH, ALONG WITH DEVELOPED LENGTH AND TERMINATION |
| | LOCATION FOR ALL LAUNDRY ROOMS. FBC FS 107.2.1 |
| | |
| | 36) PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL |
| | DRYERS IN THE LAUNDRY ROOMS. FBC FS 107.2.1 |
| | |
| | 37) IN ALL ROOMS WITH FCU?S PLEASE PROVIDE OUTDOOR AIR |
| | CFM?S BEING SUPPLIED TO EACH UNIT ON THE DRAWINGS. FBC |
| | FS 107.2.1 |
| | |
| | 38) PLEASE PROVIDE A DETAIL DRAWING SHOWING THE KEF |
| | TERMINATIONS ON THE EXTERIOR OF THE BUILDING. FBC M |
| | 506.3.13 |
| | |
| | 39) PLEASE SHOW DISTANCE FROM PROPERTY LINES FOR ALL |
| | HOOD TERMINATIONS. FBC M 506.3.13.3 |
| | |
| | 40) KITCHEN HOODS WILL REQUIRE A SEPARATE PERMIT AND |
| | REVIEW. FBC FS 107.2.1 |
| | |
| | 41) SHEET M-2.2A: HOW ARE YOU PROVIDING MAKE-UP AIR FOR |
| | THE HOODS? FBC FS M 508.1 |
| | |
| | 42) PLEASE PROVIDE AN AIR BALANCE REPORT FOR THIS |
| | STRUCTURE. FBC M 508.1.2 |
| | |
| | 43) PLEASE PROVIDE KITCHEN EQUIPMENT INFORMATION AND |
| | LOCATIONS. FBC FS 107.2.1 |
| | |
| | 44) SHEET M-2.1A: PLEASE SHOW BATH EXHAUST FAN AND DUCT |
| | WORK TO TERMINATION FOR BATHROOM BEHIND PREPARATION |
| | KITCHEN. FBC FS 107.2.1 |
| | |
| | 45) PLEASE EXPLAIN WHAT TEF-A IS EXHAUSTING AND |
| | IDENTIFY THE ROOM IT IS LOCATED IN. FBC FS 107.2.1 |
| | |
| | 46) PLEASE SHOW THE RATED DAMPER AT THE RATED WALL |
| | DIVIDING THE SMOKE COMPARTMENTS. FBC FS 107.2.1 |
| | |
| | 47) SHEET M-2.1A PROVIDE SPECS FOR THE HORIZONTAL MAU. |
| | NOTE 11 STATES TO LOOK AT THE ROOF PLANS FOR LOCATION |
| | OF THE REMOTE AIR COOLED CONDENSING UNITS. PLEASE |
| | IDENTIFY EACH FOR THE MAU IT IS IDENTIFIED WITH. FBC FS |
| | 107.2.1 |
| | |
| | 48) IT APPEARS THAT YOU HAVE FD?S IN GREASE DUCT AT |
| | RATED WALL PENETRATIONS, PLEASE REMOVE ALL FD?S IN THE |
| | GREASE DUCT AND SHOW HOW YOU WILL PROTECT THE |
| | PENETRATIONS AS FD?S ARE NOT ALLOWED IN GREASE DUCTS. |
| | FBC M 506.3.11 |
| | |
| | 49) THERE WILL BE A SEPARATE PERMIT AND REVIEW FOR ALL |
| | OF THE REFRIGERATION SYSTEMS. FBC FS 107.2.1 |
| | |
| | 50) PLEASE SHOW HOW KEF-1 AND KEF-3 COMPLY WITH FBC M |
| | 506.5.1.2 IN-LINE FAN LOCATION. |
| | |
| | 51) PLEASE SHOW THE CLEANOUTS FOR THE INLINE FANS FOR |
| | KEF-1 AND KEF-3. FBC M 506.3.8.2 |
| | |
| | 52) PLEASE SHOW GREASE DUCT CLEANOUT LOCATIONS. FBC M |
| | 506.3.8 |
| | |
| | 53) PLEASE PROVIDE SPECS FOR COMMERCIAL LAUNDRY |
| | EQUIPMENT. FBC FS 107.2.1 |
| | |
| | 54) PLEASE IDENTIFY LAUNDRY EQUIPMENT ON PLANS. FBC FS |
| | 107.2.1 |
| | |
| | 55) PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR |
| | COMMERCIAL DRYERS AND O.A. LOUVER. FBC FG CHAPTER 4. |
| | |
| | 56) SHEET M-2.A THE WALLS OF THE LAUNDRY ROOM ARE |
| | RATED, PLEASE SHOW HOW ALL THE DUCT PENETRATIONS MEET |
| | FBC M 607.5.3 |
| | |
| | 57) IN THE GRAND FOYER THERE IS A LABEL BAR/GRILL, IS |
| | THERE ANY COOKING BEING DONE IN THIS AREA? FBC FS |
| | 107.2.1 |
| | |
| | 58) PLEASE PROVIDE SPEC SHEETS FOR GENERATOR. FBC FS |
| | 107.2.1 |
| | |
| | 59) THE GENERATOR MUST BE UNDER A SEPARATE PERMIT AND |
| | REVIEW. FBC FS 107.2.1 |
| | |
| | 60) PLEASE PROVIDE A DETAIL DRAWING OF THE GENERATOR |
| | ROOM ALONG WITH VENTILATION CALCULATIONS TO VERIFY |
| | LOUVER SIZES. FBC FS 107.2.1 |
| | |
| | 61) PLEASE SHOW THE GENERATOR EXHAUST PIPING AND |
| | TERMINATION. FBC FS 107.2.1 |
| | |
| | 62) PLEASE EXPLAIN THE INTENT OF EF-4 AND THE 14?X14? |
| | DUCT WORK IN THE GENERATOR ROOM. FBC FS 107.2.1 |
| | |
| | 63) PLEASE PROVIDE SPECS FOR ALL EQUIPMENT IN THE |
| | BOILER ROOM. FBC FS 107.2.1 |
| | |
| | 64) SHEET M-2.1B: NOTE (5) STATES THIS LOUVER IS AN OUT |
| | DOOR AIR TO AHU/ FCU RETURN. THIS LOUVER IS LOCATED |
| | INSIDE THE ENTRANCE OF THE PARKING GARAGE. PLEASE SHOW |
| | THIS LOUVER AT THE EXTERIOR OF THE BUILDING. FBC FS |
| | 107.2.1 |
| | |
| | 65) SHEET M-2.1B: O/A LOUVER FOR AHU-OFF IS LOCATED IN |
| | THE PARKING GARAGE, THIS CANNOT BE LOCATED IN THIS |
| | AREA. PLEASE MOVE THE O/A LOUVER TO THE EXTERIOR OF THE |
| | BUILDING. FBC FS 107.2.1 |
| | |
| | 66) PLEASE PROVIDE DETAILS FOR THE BEAUTY SALON, PLEASE |
| | SHOW IT MEETS FBC M TABLE 403.3.1.1 FOR VENTILATION AND |
| | FOOTNOTES (B & H). |
| | |
| | 67) SHEETS M2.1A AND M2.1B: ACCORDING TO SHEET LS-0.1 |
| | THERE ARE SEVERAL RATED WALLS ON THIS FLOOR. PLEASE |
| | SHOW THE REQUIRED FD FOR EACH DUCT PENETRATION. FBC M |
| | 607.5.3 |
| | |
| | 68) THERE ARE SEVERAL (MEP CLOSETS) ON THIS 1ST FLOOR. |
| | ACCORDING TO SHEET LS-0.1 THESE CLOSETS ARE 1 HR. RATED |
| | FIRE PARTITIONS, PLEASE SHOW FD IN EACH PENETRATION OF |
| | THESE RATED WALLS. FBC M 607.5.3 |
| | |
| | 69) PLEASE PROVIDE DETAIL DRAWINGS AND CALCULATIONS |
| | THAT SHOW THE PARKING GARAGE IS AN OPEN GARAGE. FBC FS |
| | 107.3.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |