| 2020-07-21 10:09:23 | GAS 1ST REVIEW COMMENTS:20011223 | | | 1) SUBMIT WHICH OF THE APPLICABLE SIZING TABLES USED TO | | | SIZE THE GAS SYSTEM AFTER THE PRESSURE REGULATORS OR | | | PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH | | | SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD | | | THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER | | | TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND | | | TABLES 402.4 (1) THRU 402.4 (37) | | | 2) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. | | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | | AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS SEC.409.4 | | | 3) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. 2014 FGC SEC.410.1 | | | 4) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE | | | APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1 | | | 5) DISCOVERY ROOM B116 PROVIDE MAKE UP AIR. SUBMIT | | | CALCULATIONS FOR COMBUSTION AIR PER THE 2017 FBC-FUEL | | | GAS CODE SEC.304.1, | | | | | | | | | TIM HUNT | | | CITY OF WEST PALM BEACH ( CAP GOVERNMENT) | | | [email protected] | | | | | | | | | |
|