| 2020-05-20 14:32:46 | |
| | |
| | |
| | |
| | 1) 1ST FLOOR MECHANICAL SHEETS - THERE DOES NOT APPEAR |
| | TO BE ANY FIRE DAMPERS INDICATED WHERE DUCT PENETRATES |
| | THROUGH A FIRE RATED WALL; LAUNDRY ROOM; VOID SPACE |
| | WALL. |
| | |
| | NFPA 101 , CH 32, NEW RESIDENTIAL BOARD AND CARE |
| | OCCUPPANCIES |
| | |
| | 32.3.6.2 HEATING, VENTILATING, AND AIR-CONDITIONING. |
| | 32.3.6.2.1 HEATING, VENTILATING, AND AIR-CONDITIONING |
| | EQUIPMENT |
| | SHALL COMPLY WITH SECTION 9.2. |
| | |
| | NFPA 101, CH 9 |
| | |
| | 9.2 HEATING, VENTILATING, AND AIR-CONDITIONING. |
| | 9.2.1 AIR-CONDITIONING, HEATING, VENTILATING DUCTWORK, |
| | AND |
| | RELATED EQUIPMENT. AIR-CONDITIONING, HEATING, |
| | VENTILATING DUCTWORK, |
| | AND RELATED EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA |
| | 90A, |
| | STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND |
| | VENTILATING |
| | SYSTEMS, OR NFPA 90B, STANDARD FOR THE INSTALLATION OF |
| | WARM AIR |
| | HEATING AND AIR-CONDITIONING SYSTEMS, AS APPLICABLE, |
| | UNLESS SUCH |
| | INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, |
| | WHICH SHALL BE |
| | PERMITTED TO BE CONTINUED IN SERVICE. |
| | |
| | NFPA 90A |
| | |
| | 4.3.9 FIRE DAMPERS. |
| | 4.3.9.1 APPROVED FIRE DAMPERS SHALL BE PROVIDED AS |
| | REQUIRED |
| | IN CHAPTER 5. |
| | 4.3.9.2 APPROVED FIRE DAMPERS SHALL BE INSTALLED IN |
| | CONFORMANCE |
| | WITH THE CONDITIONS OF THEIR LISTINGS. |
| | |
| | 5.3* PENETRATIONS ? PROTECTION OF OPENINGS. |
| | 5.3.1 FIRE-RATED WALLS AND PARTITIONS. |
| | 5.3.1.1* APPROVED FIRE DAMPERS SHALL BE PROVIDED WHERE |
| | AIR |
| | DUCTS PENETRATE OR TERMINATE AT OPENINGS IN WALLS OR |
| | PARTITIONS |
| | REQUIRED TO HAVE A FIRE RESISTANCE RATING OF 2 HOURS OR |
| | MORE. |
| | 5.3.1.1.1* FIRE DAMPERS SHALL NOT BE REQUIRED WHERE |
| | OTHER |
| | OPENINGS THROUGH THE WALL ARE NOT REQUIRED TO BE |
| | PROTECTED. |
| | 5.3.1.2 APPROVED FIRE DAMPERS SHALL BE PROVIDED IN ALL |
| | AIR |
| | TRANSFER OPENINGS IN PARTITIONS THAT ARE REQUIRED TO |
| | HAVE A FIRE |
| | RESISTANCE RATING AND IN WHICH OTHER OPENINGS ARE |
| | REQUIRED TO |
| | BE PROTECTED. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERNCES. |
| | |
| | |
| | 1A) THROUGHOUT THE UPPER FLOORS THERE ARE INDICATIONS |
| | OF FIRE AND SMOKE DAMPER WITHIN 1 HOUR RATED WALLS; |
| | HOWEVER, ON THE 1ST FLOOR THERE ARE NO INDICATIONS OF |
| | FIRE AND SMOKE DAMPERS WHERE A/C DUCT APPEAR TO |
| | PENETRATE THESE RATED WALLS. |
| | |
| | PLEASE REVIEW AND JUSTIFY OR CORRECT. |
| | |
| | |
| | |
| | 1B) A CLEAR SEQUENCE OF OPERATION OF THE FIRE/SMOKE |
| | DAMPERS COULD NOT BE LOCATED. |
| | |
| | PLEASE PROVIDE A SOO FOR EACH |
| | DAMPER/FLOOR/FLOORS/ENTIRE BUILDING INCLUING ACTIVATION |
| | OF THE FIRE ALARM. |
| | |
| | |
| | |
| | |
| | 2) FLOOR PLAN SHEETS - THERE ARE NO INDICATIONS OF THE |
| | WIDTH OF THE CORRIDORS ON ANY FLOOR. |
| | |
| | 32.3.2.3.3 THE WIDTH OF CORRIDORS SHALL BE SUFFICIENT |
| | FOR THE |
| | OCCUPANT LOAD SERVED BUT SHALL BE NOT LESS THAN 60 IN. |
| | |
| | PLEASE PROVIDE WIDTH DIMENSIONS IN COMPLIANCE. |
| | |
| | |
| | |
| | 3) SHEET LS 05 & 06 THRU 8 - THE VEST. DOOR FOR |
| | ELEVATOR # 3 IS INDICATED AS OUTSWING INTO THE EGRESS |
| | CORRIDOR. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR |
| | LEAF IS FULLY OPEN. |
| | |
| | PLEASE CORRECT OR JUSTIFY WITH SPECIFIC CODE REFERNCES. |
| | |
| | |
| | 4) SHEET LS 05 - THE EXIT DOOR FROM THE POOL DECK ON |
| | THE WEST SIDE IS INDICATED AS OUTSWING INTO THE EGRESS |
| | CORRIDOR. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR |
| | LEAF IS FULLY OPEN. |
| | |
| | PLEASE CORRECT OR JUSTIFY WITH SPECIFIC CODE REFERNCES. |
| | |
| | |
| | |
| | 5) ALL ELECTRICAL SHEETS - WHERE EXIT SIGNS ARE LOCATED |
| | ON BOTH SIDES OF A OPPISITE SWINGING DOUBLE DOORS, THE |
| | EXIT SIGNS SHALL BE PLAC OVER THE CENTER OF THE DOOR IN |
| | THE PATH OF TRAVEL. |
| | |
| | PLEAS CORRECT ALL LOCATIONS. |
| | |
| | |
| | |
| | 6) SHEET E 2.5A - IN THE CORNER OF THE RIDER AT THE |
| | DOUBLE DOORS INTO THE SKY LOUNGE THERE IS AN EXIT SIGN |
| | DIRECTLY OVER THE OUTSWING DOUBLE DOOR WITH A CHEVRON |
| | INDICATED AWAY/TO THE RIGHT FROM THAT DOOR TOWARDS THE |
| | STAIR. THIS CONFIGURATION MAY LEAD TO PEOPLE THINKING |
| | THEY COULD EXIT THROUGH THOSE DOUBLE DOORS. |
| | |
| | THE EXIT SIGN SHOULD BE MOVED OUT AWAY FROM DIRECTLY |
| | OVER THOSE DOORS TO THE CENTER/RIGHT (OFF-CENTER) OF |
| | THE CORRIDOR CLOSE TO THE EDGE LINE OF THE VEST. |
| | CORRIDOR WALL. |
| | |
| | |
| | 6A) SHEET E 2.5A - WITHIN THE SKY LOUNGE THERE IS AN |
| | EXIT SIGN DIRECTLY OUTSIDE THE DOUBLE DOORS COMING FROM |
| | THE POOL. THIS SIGN APPEARS TO BE UNNECESSARY AND CAN |
| | BE REMOVED. |
| | |
| | PLEASE REVIEW AND CONSIDER REMOVING UNLESS YOU CAN |
| | JUSTIFY IT. |
| | |
| | |
| | |
| | 7) SHEET E 2.5B - WITHIN THE CORRIDOR THERE IS AN EXIT |
| | SIGN DIRECTLY OUTSIDE THE DOUBLE DOORS COMING FROM THE |
| | POOL. THIS SIGN APPEARS TO BE UNNECESSARY AND CAN BE |
| | REMOVED. |
| | |
| | PLEASE REVIEW AND CONSIDER REMOVING UNLESS YOU CAN |
| | JUSTIFY IT. |
| | |
| | |
| | |
| | 8) SHEET E 2.5B - AT THE WEST END OF THE POOL THERE IS |
| | A CORRIDOR LEADING TO THE INTERIOR; THERE IS AN EXIT |
| | SIGNIN THE MIDDLE OF THAT CORRIDOR THAT ASPPEARS TO BE |
| | MISLOCATED AND NOT VISIBLE TO POOL ATTENDEES. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 8A) SHEET E 2.5B - IF THEWEST EXTERIOR CORRIDOR FROM |
| | THE POOL AREA IS INTENDED TO BE AN EXIT AN EXIT SIGN |
| | SHALL BE PLACED AT THE ENTRANCE TO THAT CORRIDOR. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 8B) SHEET E 2.5B - THE NORTH DOUBLE DOOR EXIT FROM THE |
| | POOL AREA HAS AN EXIT SIGN DIRECTLY OVER IT THAT IS NOT |
| | VISIABLE FROM THE GENERAL OPEN POOL AREA. THIS EXIT |
| | SING NEEDS TO BE VISABLE FROM THE GENRAL POOL AREA. |
| | |
| | THIS EXIT SIGN CAN BE MOVED OUT FROM DIRECTLY OVER THE |
| | EXIT DOORS AND PLACED AT THE ENTRANCE TO THE SHORT |
| | CORRIDOR. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 9) SHEET E 2.6A - THERE IS NO EXIT SIGN LOCATED WITHIN |
| | THE VEST OF ELEVATOR # 3. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 10) SHEET E2. 2A, 3A & 4A - THERE IS AND EXIT SIGN |
| | WITHIN THE STAIRWELL THAT LEADS TO THE PARKING GARAGE. |
| | IT SHOULD NOT BE INTENT TO LEAVE A PROTECTED STAIRWELL |
| | TO ENTER INTO A HIGHER HAZARD UNPROTECTED AREA. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | 7.2.3.5 DISCHARGE. |
| | 7.2.3.5.1 EVERY SMOKEPROOF ENCLOSURE SHALL DISCHARGE |
| | INTO A PUBLIC |
| | WAY, INTO A YARD OR COURT HAVING DIRECT ACCESS TO A |
| | PUBLIC WAY, OR |
| | INTO AN EXIT PASSAGEWAY. SUCH EXIT PASSAGEWAYS SHALL BE |
| | WITHOUT |
| | OPENINGS, OTHER THAN THE ENTRANCE TO THE SMOKEPROOF |
| | ENCLOSURE AND |
| | THE DOOR OPENING TO THE OUTSIDE YARD, COURT, OR PUBLIC |
| | WAY. THE EXIT |
| | PASSAGEWAY SHALL BE SEPARATED FROM THE REMAINDER OF THE |
| | BUILDING |
| | BY A 2-HOUR FIRE RESISTANCE RATING. |
| | |
| | THIS DOOR CAN FUNCTION AS AN EXIT FROM THE GARAGE BY |
| | NOT BE OPERABLE FROM THE INSIDE OF THE STAIR NOT MARKED |
| | AS AN EXIT FROM THE WITHIN THE STAIR. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 10A) SHEET E2 2B & LS 0.2 - THERE IS NO INDICATION ON |
| | E2 2B OF AN EXIT SIGN AT THE EAST GARAGE EXIT DOOR TO |
| | STAIR # 2 AS IS INDICATED ON LS 0.2. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 11) SHEET E2 2.1A , A 2.1 & LS 0.1 - THERE IS A |
| | CONFLICT OF THE DISCHARG DESIGN OF STAIR # 2 AND THUS |
| | THE EXIT SIGNAGE. SHOULD A 2.1 & LS 0.1 BE CORRECT |
| | PLEASE MOVE THE EXIT SIGN FROM OVER THE DOOR TO THE |
| | AREA VISABLE THROUGH THE OPENING WITH A CHEVRON LEADING |
| | TO THE DOOR. |
| | |
| | PLEASE REVIEW AND CORRECT THE EXIT SIGN AND THE CORRECT |
| | FLOOR PLAN ACCORDINGLY. |
| | |
| | |
| | |
| | 12) SHEET E2 2.1A - THERE IS AN INDICATION OF AN EXIT |
| | SIGN FROM THE WEST SIDE OF THE MAIN KITCHEN THAT IS NOT |
| | VISABLE FROM THE GENRAL KITCHEN ARE. AN ADDITIONAL EXIT |
| | SIGN NEEDS TO BE LOCATED OUT INTO THE MAIN KITCHEN AREA |
| | THAT LEADS TO THIS EXIT. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 13) SHEET E2 2.1B - THERE IS NO INDICATION OF AN EXIT |
| | SIGNS FROM THE PUMP ROOM, MDF/BDA ROOM, BOILER ROOM, |
| | MAIN ELECT ROOM, FPL VAULT, & GERNATOR ROOM. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 14) SHEET E2 2.1B - THERE IS NO INDICATION OF AN EXIT |
| | SIGNS FROM THE LARGE WOMEN AND MENS RESTOOMS NEAR THE |
| | EXERCISE ROOM. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 15) SHEET E2 2.1B - THERE IS NO INDICATION OF AN EXIT |
| | SIGN FROM THE BEAUTY SALON FOR THOSE WITH DISABILTY. |
| | THERE IS AN EXIT SIGN INDICATED WITHIN THE TREATMENT |
| | THAT CAN BE REMOVED AND RELOCATED AT THAT SMALL |
| | CORRIDOR EDGE SO THAT IT IS VISABLE FROM THE SALON. |
| | THERE IS ALSO AN EXIT SIGN DIRECTLY OUTSIDE THE SALON |
| | THAT CAN BE REMOVED. |
| | |
| | ADDITIONALLY, THERE IS CONFLICT OF THE LAYOUT OF RECEPT |
| | AREA COMPARED TO THE LS 0.1. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 16) SHEET E2 7A & 7B - THERE ARE NO INDICATIONS OF EXIT |
| | SIGNS AT EACH STAIRWELL NOR ALONG ANY DEFINED EXIT |
| | PATH. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 17) SHEET LS 0.0 - UNDER DEFERRED SUBMITTALS # 5 THERE |
| | IS AN INDICATION OF PREFABRICATED WOOD ROOF TRUSSES; |
| | HOWEVER, THERE ARE NO INDICATION OF FIRE SPRINKLER |
| | PROTECTION ON THE ROOF, SHEET FS 2.7A & B. |
| | |
| | PER NFPA 13 |
| | |
| | 8.3.2.5* THE FOLLOWING PRACTICES SHALL BE OBSERVED TO |
| | PROVIDE |
| | SPRINKLERS OF OTHER THAN ORDINARY-TEMPERATURE |
| | CLASSIFICATION |
| | UNLESS OTHER TEMPERATURES ARE DETERMINED OR UNLESS |
| | HIGHTEMPERATURE |
| | SPRINKLERS ARE USED THROUGHOUT, AND TEMPERATURE |
| | SELECTION SHALL BE IN ACCORDANCE WITH TABLE 8.3.2.5(A), |
| | TABLE 8.3.2.5(B), AND FIGURE 8.3.2.5: |
| | |
| | (5) SPRINKLERS IN AN UNVENTILATED, CONCEALED SPACE, |
| | UNDER |
| | AN UNINSULATED ROOF, OR IN AN UNVENTILATED ATTIC SHALL |
| | BE |
| | OF THE INTERMEDIATE-TEMPERATURE CLASSIFICATION. |
| | |
| | 8.6.4.1.4 SPRINKLERS UNDER ROOF OR CEILING IN |
| | COMBUSTIBLE |
| | CONCEALED SPACES OF WOOD JOIST OR WOOD TRUSS |
| | CONSTRUCTION |
| | WITH MEMBERS LESS THAN 3 FT (0.91 M) ON CENTER AND |
| | SLOPE |
| | HAVING PITCH OF 4 IN 12 OR GREATER. SPRINKLERS SHALL BE |
| | POSITIONED |
| | IN ACCORDANCE WITH FIGURE 8.6.4.1.4 AND THE |
| | REQUIREMENTS |
| | OF 8.6.4.1.4.1 THROUGH 8.6.4.1.4.5. |
| | 8.6.4.1.4.1 SPRINKLERS UNDER A ROOF OR CEILING IN |
| | COMBUSTIBLE |
| | CONCEALED SPACES OF WOOD JOIST OR WOOD TRUSS |
| | CONSTRUCTION WITH |
| | MEMBERS LESS THAN 3 FT (0.91 M) ON CENTER AND A SLOPE |
| | HAVING A |
| | PITCH OF 4 IN 12 OR GREATER SHALL BE QUICK-RESPONSE. |
| | 8.6.4.1.4.2 SPRINKLERS UNDER A ROOF OR CEILING IN |
| | COMBUSTIBLE |
| | CONCEALED SPACES OF WOOD JOIST OR WOOD TRUSS |
| | CONSTRUCTION WITH |
| | MEMBERS LESS THAN 3 FT (0.91 M) ON CENTER AND A SLOPE |
| | HAVING A |
| | PITCH OF 4 IN 12 OR GREATER SHALL BE INSTALLED SO THAT |
| | A ROW OF |
| | SPRINKLERS IS INSTALLED WITHIN 12 IN. (305 MM) |
| | HORIZONTALLY OF |
| | THE PEAK AND BETWEEN 1 IN. AND 12 IN. (25.4 MM AND 305 |
| | MM) |
| | DOWN FROM THE BOTTOM OF THE TOP CHORD MEMBER. |
| | 8.6.4.1.4.3 SPRINKLERS UNDER A ROOF OR CEILING IN |
| | COMBUSTIBLE |
| | CONCEALED SPACES OF WOOD JOIST OR WOOD TRUSS |
| | CONSTRUCTION WITH |
| | MEMBERS LESS THAN 3 FT (0.91 M) ON CENTER AND A SLOPE |
| | HAVING A |
| | PITCH OF 4 IN 12 OR GREATER SHALL BE INSTALLED SO THAT |
| | THE SPRINKLERS |
| | INSTALLED ALONG THE EAVE ARE LOCATED NOT LESS THAN 5 FT |
| | (1.52 M) FROM THE INTERSECTION OF THE UPPER AND LOWER |
| | TRUSS |
| | CHORDS OR THE WOOD RAFTERS AND CEILING JOISTS. |
| | 8.6.4.1.4.4 SPRINKLERS UNDER A ROOF OR CEILING IN |
| | COMBUSTIBLE |
| | CONCEALED SPACES OF COMBUSTIBLE WOOD JOIST OR WOOD |
| | TRUSS CONSTRUCTION |
| | WITH MEMBERS LESS THAN 3 FT (0.91 M) ON CENTER AND A |
| | SLOPE HAVING A PITCH OF 4 IN 12 OR GREATER, AND USING |
| | STANDARD |
| | SPRAY SPRINKLERS, WHERE THE DIMENSION PERPENDICULAR TO |
| | THE |
| | SLOPE EXCEEDS 8 FT (2.4 M), SHALL HAVE A MINIMUM |
| | PRESSURE OF |
| | 20 PSI (1.4 BAR). |
| | 8.6.4.1.4.5 THE SPECIAL REQUIREMENTS OF 8.6.2.2.1 AND |
| | 8.6.4.1.4 |
| | FOR SPRINKLERS UNDER A ROOF OR CEILING IN COMBUSTIBLE |
| | CONCEALED |
| | SPACES OF WOOD JOIST OR WOOD TRUSS CONSTRUCTION WITH |
| | MEMBERS |
| | LESS THAN 3 FT (0.91 M) ON CENTER AND A SLOPE HAVING A |
| | PITCH OF 4 IN |
| | 12 OR GREATER SHALL NOT APPLY WHEN THE EXPOSED |
| | COMBUSTIBLE |
| | SHEATHING IN THE ROOF OR CEILING SPACE ARE CONSTRUCTED |
| | OF PRESSURE |
| | IMPREGNATED FIRE-RETARDANT TREATED WOOD AS DEFINED BY |
| | NFPA703. |
| | |
| | 8.15 SPECIAL SITUATIONS. |
| | 8.15.1 CONCEALED SPACES. |
| | 8.15.1.1 CONCEALED SPACES REQUIRING SPRINKLER |
| | PROTECTION. |
| | CONCEALED SPACES OF EXPOSED COMBUSTIBLE CONSTRUCTION |
| | SHALL |
| | BE PROTECTED BY SPRINKLERS EXCEPT IN CONCEALED SPACES |
| | WHERE |
| | SPRINKLERS ARE NOT REQUIRED TO BE INSTALLED BY |
| | 8.15.1.2.1 |
| | THROUGH 8.15.1.2.18 AND 8.15.6. |
| | 8.15.1.2* CONCEALED SPACES NOT REQUIRING SPRINKLER |
| | PROTECTION. |
| | 8.15.1.2.1* CONCEALED SPACES OF NONCOMBUSTIBLE AND |
| | LIMITEDCOMBUSTIBLE |
| | CONSTRUCTION WITH MINIMAL COMBUSTIBLE LOADING |
| | HAVING NO ACCESS SHALL NOT REQUIRE SPRINKLER |
| | PROTECTION. |
| | 8.15.1.2.1.1 THE SPACE SHALL BE CONSIDERED A CONCEALED |
| | SPACE |
| | EVEN WITH SMALL OPENINGS SUCH AS THOSE USED AS RETURN |
| | AIR FOR A |
| | PLENUM. |
| | 8.15.1.2.2 CONCEALED SPACES OF NONCOMBUSTIBLE AND |
| | LIMITEDCOMBUSTIBLE |
| | CONSTRUCTION WITH LIMITED ACCESS AND NOT PERMITTING |
| | OCCUPANCY OR STORAGE OF COMBUSTIBLES SHALL NOT REQUIRE |
| | SPRINKLER PROTECTION. |
| | |
| | 8.15.1.2.9 CONCEALED SPACES OVER ISOLATED SMALL ROOMS |
| | NOT |
| | EXCEEDING 55 FT2 (5.1 M2) IN AREA SHALL NOT REQUIRE |
| | SPRINKLER |
| | PROTECTION. |
| | |
| | 8.15.1.2.11* CONCEALED SPACES IN WHICH THE EXPOSED |
| | MATERIALS |
| | ARE CONSTRUCTED ENTIRELY OF FIRE RETARDANT?TREATED WOOD |
| | AS DEFINED |
| | BY NFPA 703 SHALL NOT REQUIRE SPRINKLER PROTECTION. |
| | |
| | PLEASE REVIEW AND PROVIDE SPRINKLER PROTECTION OR |
| | JUSTIFY WITH SPECIFIC CODE REFERNCES AND SPECIFIC |
| | DETALS THAT MEET OMMISSION REQUIREMENTS. |
| | |
| | |
| | |
| | 18) FIRE ALARM SHEETS - THERE APPEARS TO BE AN OVER |
| | DESIGN OF THE SMOKE DETECTORS LOCATED THROUGHOUT THE |
| | FLOORS PLANS THAT MAY NOT BE REQUIRED. SMOKE DETECTORS |
| | INSTALLED WHERE NOT REQUIRED OR FOR A SPECIFIC PURPOSE |
| | MAY LEAD TO EXCESSIVE FALSE ALARMS AND MAINTENANCE. |
| | |
| | I'M NOT SURE WHAT CODE IS BEING USED FOR THIS |
| | OCCUPANCY; HOWEVER, PER NFPA 101, CH 32, NEW |
| | RESIDENTIAL BOARD OCCUPANCIES. |
| | |
| | 32.3.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 32.3.3.4.1 GENERAL. A FIRE ALARM SYSTEM SHALL BE |
| | PROVIDED IN |
| | ACCORDANCE WITH SECTION 9.6. |
| | 32.3.3.4.2 INITIATION. THE REQUIRED FIRE ALARM SYSTEM |
| | SHALL BE |
| | INITIATED BY EACH OF THE FOLLOWING: |
| | (1) MANUAL MEANS IN ACCORDANCE WITH 9.6.2 |
| | (2) MANUAL FIRE ALARM BOX LOCATED AT A CONVENIENT |
| | CENTRAL CONTROL |
| | POINT UNDER CONTINUOUS SUPERVISION OF RESPONSIBLE |
| | EMPLOYEES |
| | (3) REQUIRED AUTOMATIC SPRINKLER SYSTEM |
| | (4) REQUIRED DETECTION SYSTEM |
| | 32.3.3.4.7 SMOKE ALARMS. APPROVED SMOKE ALARMS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH 9.6.2.10 INSIDE EVERY |
| | SLEEPING ROOM, |
| | OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY |
| | OF THE |
| | BEDROOMS, AND ON ALL LEVELS WITHIN A RESIDENT UNIT. |
| | 32.3.3.4.8 SMOKE DETECTION SYSTEMS. |
| | 32.3.3.4.8.1 CORRIDORS AND SPACES OPEN TO THE |
| | CORRIDORS, OTHER THAN |
| | THOSE MEETING THE REQUIREMENT OF 32.3.3.4.8.3, SHALL BE |
| | PROVIDED |
| | WITH SMOKE DETECTORS THAT COMPLY WITH NFPA 72, NATIONAL |
| | FIRE |
| | ALARM AND SIGNALING CODE, AND ARE ARRANGED TO INITIATE |
| | AN ALARM |
| | THAT IS AUDIBLE IN ALL SLEEPING AREAS. |
| | 32.3.3.4.8.2 RESERVED. |
| | 32.3.3.4.8.3 SMOKE DETECTION SYSTEMS SHALL NOT BE |
| | REQUIRED IN |
| | UNENCLOSED CORRIDORS, PASSAGEWAYS, BALCONIES, |
| | COLONNADES, OR |
| | OTHER ARRANGEMENTS WITH ONE OR MORE SIDES ALONG THE |
| | LONG |
| | DIMENSION FULLY OR EXTENSIVELY OPEN TO THE EXTERIOR AT |
| | ALL TIMES. |
| | |
| | I.E. LOCATIONS - 1ST FLOOR) KITCHEN, ENCLOSED AL |
| | DINING, LAUNDRY,LOCKERS 1ST FL, PACKAGE ROOM, VOID |
| | SPACE, THEATRE, MUTLTI FUNCTION AREA, DISCOVERY ROOM, |
| | LIBRARY, BEAUTY SALON, DIRECTOR OFFICE, EXAM TOILET, |
| | ETC. |
| | 2ND FLOOR - STORAGE, PREPARATION KITCHEN, |
| | 3RD FLOOR - LAUNDRY, GARAGE STORAGE |
| | 4TH FLOOR - LAUNDRY, GARAGE STORAGE, MED DISP |
| | 5TH FLOOR -SKY LOUNGE, |
| | |
| | PLEASE PROVIDE THE CODE USED THAT REQUIRED SD IN THESE |
| | LOCATIONS. |
| | |
| | PLEASE REVIEW AND REMOVE IN AN ATTEMPT TO REDUCE FALSE |
| | ALARMS AND STILL COMPLY WITH THE CODE. |
| | |
| | |
| | |
| | 19) FIRE ALARM SHEETS - THERE ARE INDICATIONS OF MANUAL |
| | PULL STATIONS LOCATED THROUGHT THE BUILDING AT EXIT |
| | LOCATIONS. |
| | |
| | PER NFPA 101, CH 32 |
| | |
| | 32.3.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 32.3.3.4.1 GENERAL. A FIRE ALARM SYSTEM SHALL BE |
| | PROVIDED IN |
| | ACCORDANCE WITH SECTION 9.6. |
| | |
| | PER NFPA 101, CH 9 |
| | |
| | 9.6.2 SIGNAL INITIATION. |
| | |
| | 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE |
| | DETECTION OR |
| | WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM |
| | SYSTEM IN |
| | ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN |
| | ONE MANUAL |
| | FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY |
| | HAVING |
| | JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE |
| | ALARM SIGNAL. |
| | |
| | THE * APPENDIX NARRATIVE STATES: |
| | |
| | A.9.6.2.6 THE MANUAL FIRE ALARM BOX REQUIRED BY 9.6.2.6 |
| | IS INTENDED |
| | TO PROVIDE A MEANS TO MANUALLY ACTIVATE THE FIRE ALARM |
| | SYSTEM WHEN THE AUTOMATIC FIRE DETECTION SYSTEM OR |
| | WATERFLOW DEVICES |
| | ARE OUT OF SERVICE DUE TO MAINTENANCE OR TESTING, OR |
| | WHERE |
| | HUMAN DISCOVERY OF THE FIRE PRECEDES AUTOMATIC |
| | SPRINKLER SYSTEM |
| | OR AUTOMATIC DETECTION SYSTEM ACTIVATION. WHERE THE |
| | FIRE ALARM |
| | SYSTEM IS CONNECTED TO A MONITORING FACILITY, THE |
| | MANUAL FIRE |
| | ALARM BOX REQUIRED BY 9.6.2.6 SHOULD BE CONNECTED TO A |
| | SEPARATE |
| | CIRCUIT THAT IS NOT PLACED ?ON TEST? WHEN THE DETECTION |
| | OR SPRINKLER |
| | SYSTEM IS PLACED ON TEST. THE MANUAL FIRE ALARM BOX |
| | SHOULD BE |
| | LOCATED IN AN AREA THAT IS ACCESSIBLE TO OCCUPANTS OF |
| | THE BUILDING |
| | AND SHOULD NOT BE LOCKED. |
| | |
| | |
| | IN AN EFFORT TO REDUCE FALL ALARMS WHILE STILL |
| | COMPLYING WITH THE CODE PULL STATIONS CAN BE REMOVED |
| | THROUGHTOUT THE BUILDING AND PLACED IN A LOCATION |
| | ACCEPTABLE TO THE AHJ. |
| | |
| | COSIDER LOCATING ONE AT THE FRONT LOBBY; A 126, ONE AT |
| | THE EXIT DOOR OF ELEV LOBBY A132 AND ONE AT THE BEAUTY |
| | SALON; B124, MAIN EXIT DOOR ONLY. |
| | |
| | |
| | |
| | 20) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 21) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |