| 2020-07-20 12:09:29 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PLANS ARE LABELED AS NOT FOR CONSTRUCTION. TO BE |
| | USED FOR PERMIT THE PLANS MUST BE 100% COMPLETE AND |
| | THIS STATEMENT MUST NOT BE PRESENT. PROVIDE CORRECTION. |
| | WPB FBC 105.1, 107.2.1 |
| | 2. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING |
| | PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK |
| | IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY |
| | OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1 |
| | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | SERVICE AND DOWNSTREAM PANELS, INCLUDING INFORMATION |
| | FROM THE POWER COMPANY, STATING WHAT THE AVAILABLE |
| | SHORT CIRCUIT CURRENT IS FOR THE SERVICE AND DOWNSTREAM |
| | PANELS TO CONFIRM THE STATED AIC RATING OF THE |
| | ELECTRICAL EQUIPMENT IS ADEQUATE. CALCULATIONS SHOULD |
| | BE PERFORMED UNTIL THEY REACH BELOW 10,000 AIC. NEC |
| | 110.9, 110.10 |
| | 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| | 5. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| | FBC EC C405.1, R404.1 |
| | 6. PROVIDE VOLTAGE DROP CALCULATIONS TO COMPLY WITH |
| | CODE. FBC EC C405.6.3 |
| | 7. PROVIDE ENCLOSURE FOR POOL PANEL ADEQUATE FOR THE |
| | ENVIRONMENT. NEC TABLE 110.28 |
| | 8. IT APPEARS THAT NEC 220.84 WAS USED FOR CALCULATIONS |
| | FOR ALL RESIDENTIAL SERVICES. THIS METHOD IS PERMITTED |
| | ONLY WHERE THE UNITS ARE EQUIPPED WITH ELECTRIC COOKING |
| | EQUIPMENT. THIS IS NOT THE CASE FOR ALL UNITS. PROVIDE |
| | ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. NEC |
| | 220.84 |
| | 9. PROVIDE ACCURATE LOAD CALCULATION AND PANEL SCHEDULE |
| | FOR PANEL GEDP. WHAT WILL THE LOAD ON THE GENERATOR BE? |
| | NEC 220 |
| | 10. PROVIDE DETAILS OF COMPLIANCE WITH THE EMERGENCY |
| | ENVIRONMENTAL CONTROL REQUIRED PER FLORIDA |
| | ADMINISTRATIVE CODE, RULE 58A-5.036 |
| | 11. SHEET E-7.2 STATES THE GENERATOR DESIGN IS BASED ON |
| | NEC 702, WHICH IS FOR OPTIONAL STANDBY SYSTEMS. THIS IS |
| | A LEGALLY REQUIRED SYSTEM. PROVIDE CLARIFICATION AND/OR |
| | CORRECTIONS. NEC 701.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |
| | [email protected] |
| | JAKE LEAHY |
| | 561-805-6713 |
| | |