| 2020-07-20 14:01:02 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 20011223 |
| | REVIEWED: AUGUST 17, 2020 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | FAIRHOUSING: |
| | |
| | 1) REQUIREMENT 1 - SHOW AT LEAST ONE ACCESSIBLE ROUTE |
| | TO BUILDING ENTRANCE. WALKS THAT ARE PART OF ACCESSIBLE |
| | ROUTES BECOME RAMPS WHEN THEIR SLOPE EXCEEDS 5% (1 IN |
| | 20). HANDRAILS ARE NOT REQUIRED ON WALKS WITH SLOPES |
| | BETWEEN 0% AND 5%, BUT THEY ARE REQUIRED ON THOSE |
| | STEEPER THAN 5% AND UP TO 8.33% (1 IN 12) |
| | - PROVIDE CIVIL PLANS TO VERIFY SLOPES THAT WILL OCCUR |
| | ON THE ACCESSIBLE PATH. PROVIDE SITE PLAN TO SHOW THE |
| | ACCESSIBLE PATH FROM PARKING OR OTHER PUBLIC ACCESS |
| | POINTS SUCH AS BUS STOP OR DROP OFF ZONE. |
| | |
| | 2) REQUIREMENT 3 - USABLE DOORS. THE DOORS IN COMMON |
| | SPACES AND THE SIDE ENTERING INTO DWELLING UNITS NEED |
| | TO HAVE USABLE HARDWARE THAT CAN BE USED WITHOUT TIGHT |
| | GRASPING OR TWISTING. |
| | - TYPICALLY THE HARDWARE WOULD BE A LEVER TYPE. THIS |
| | TYPE OF HARDWARE WOULD NOT BE REQUIRED ONCE INSIDE THE |
| | UNIT. YOU MAY WANT TO CLARIFY HARDWARE ON THE DOOR |
| | SCHEDULE. |
| | |
| | 3) REQUIREMENT 6 - REINFORCED WALLS FOR GRAB BARS |
| | - BARS ONLY NEED TO BE INSTALLED IN THE PUBLIC OR |
| | COMMON USE AREAS. ALL OF THE DWELLING UNITS ONLY NEED |
| | BLOCKING INSTALLED. SHEET A2.3 SHOWS THE BLOCKING AT |
| | TOILET AND WILL WORK. PLEASE ADD BLOCKING AT SHOWER |
| | BECAUSE I ONLY SEE CONTROL ZONE AND THAT WILL BE |
| | COVERED IN REQUIREMENT 7. |
| | |
| | 4) REQUIREMENT 7 - USABLE KITCHENS. |
| | - I ONLY SEE ONE KITCHEN IN UNIT S101. PLEASE SHOW |
| | CLEAR FLOOR SPACE AT COOKTOP,REFRIDGERATOR AND SINK. |
| | THE CLEAR SPACE SHOULD BE CENTERED ON THE APPLIANCE.THE |
| | SINK DOESN'T APPEAR THAT IT WOULD WORK, SO THIS MAY |
| | NEED TO BE RE-WORKED. ALSO, CHECK |
| | |
| | 5) REQUIREMENT 7 - COMMON LAUNDRY ROOMS. |
| | - SHOW CLEAR FLOOR SPACE AT WASHER AND DRYER IN LAUNDRY |
| | ROOM 118 AND LAUNDRY ROOMS ON FLOORS 2-4. THE CLEAR |
| | SPACE SHOULD BE CENTERED ON THE APPLIANCES. |
| | |
| | |
| | ACCESSIBILITY FBC 2017: |
| | |
| | 6) 216.6 ENTRANCES. WHERE NOT ALL ENTRANCES COMPLY WITH |
| | 404, ENTRANCES COMPLYING WITH 404 SHALL BE IDENTIFIED |
| | BY THE INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING |
| | WITH 703.7.2.1. DIRECTIONAL SIGNS COMPLYING WITH 703.5 |
| | THAT INDICATE THE LOCATION OF THE NEAREST ENTRANCE |
| | COMPLYING WITH 404 SHALL BE PROVIDED AT ENTRANCES THAT |
| | DO NOT COMPLY WITH 404. |
| | ADVISORY 216.6 ENTRANCES.WHERE A DIRECTIONAL SIGN IS |
| | REQUIRED, IT SHOULD BE LOCATED TO MINIMIZE |
| | BACKTRACKING. IN SOME CASES, THIS COULDMEAN LOCATING A |
| | SIGN AT THE BEGINNING OF A ROUTE, NOT JUST AT THE |
| | INACCESSIBLE ENTRANCES TO A BUILDING. |
| | - ADD NOTE FOR SIGNAGE TO DIRECT TO LOCATION OF NEAREST |
| | ACCESSIBLE ENTRANCE. SIGNAGE TO MEET REQUIREMENMTS OF |
| | 703.5 |
| | |
| | 7) 503 FBC(A)PASSENGER LOADING ZONES. |
| | - PLEASE SHOW MARKED AREA 5' X 20' AND SLOPES TO COMPLY |
| | WITH 503.4 FLOOR AND GROUND SURFACES. (A CIVIL DRAWING |
| | COULD BE PROVIDED TO SHOW SLOPES AND CURB CUT) |
| | |
| | 8) 502.5 FBC[A] VERTICAL CLEARANCE. PARKING SPACES FOR |
| | VANS AND ACCESS AISLES AND VEHICULAR ROUTES SERVING |
| | THEM SHALL PROVIDE A VERTICAL CLEARANCE OF 98 INCHES |
| | MINIMUM. |
| | - VERIFY THAT GARAGE PROVIDES VAN CLEARANCE OF 98 |
| | INCHES MINIMUM. |
| | |
| | 9) 803.4 FBC[A] BENCHES. A BENCH COMPLYING WITH 903 |
| | SHALL BE PROVIDED WITHIN THE ROOM. |
| | |
| | 903.4 FBC[A] BACK SUPPORT. THE BENCH SHALL PROVIDE FOR |
| | BACK SUPPORT OR SHALL BE AFFIXED TO A WALL. BACK |
| | SUPPORT SHALL BE 42 INCHES LONG MINIMUM AND SHALL |
| | EXTEND FROM A POINT 2 INCHES MAXIMUM ABOVE THE SEAT |
| | SURFACE TO A POINT 18 INCHES MINIMUM ABOVE THE SEAT |
| | SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES MAXIMUM FROM |
| | THE REAR EDGE OF THE SEAT MEASURED HORIZONTALLY. |
| | |
| | OCCUPANCY: |
| | |
| | 10) 107.5.3 FBC[AMENDED] GENERAL. SHEET LS-0.1 |
| | - THE A-2 TAG AND FINE DINING TAGS ARE SHOWING POUND |
| | SIGNS INSTEAD OF THE SQ. FOOTAGE. PLEASE UPDATE SO THE |
| | SQ. FOOTAGE OF A-2 OCCUPANCY IS KNOWN. |
| | |
| | 11) 303.3 FBC[B] GENERAL. SHEET LS-0.1 |
| | - REVIEW GROUP A-2 THAT STATES DINING FACILITIES |
| | INCLUDING COMMERCIAL KITCHENS. SHOULD THE KITCHEN NOT |
| | BE CONSIDERED A-2 INSTEAD OF BUSINESS SINCE THE AREA |
| | SERVICED IS GREATER THAN 2500 SQ. FT.(SEE SECTION 304). |
| | HOWEVER, FOR EGRESS THEY YOU CAN USE OCCUPANT LOAD FOR |
| | COMMERCIAL KITCHEN THAT IS 200 GROSS PER TABLE 1004.1.2 |
| | |
| | 12) 107.5.3 FBC[AMENDED] GENERAL. SHEET LS-0. |
| | - OCCUPANY CLASSIFICATIONS ARE LISTED AS I-1, A-3, B, |
| | S-2 AND R-2, BUT WHEN I LOOK BELOW AT EXITING DATA I DO |
| | NOT SEE ALL THOSE OCCUPACIES LISTED. PLEASE UPDATE |
| | EXITING DATA TO MATCH ALL OCCUPANCY CLASSIFICATIONS. |
| | |
| | SITEWORK: |
| | |
| | 13) 107.3.5.3 FBC[AMENDED] PROVIDE SEDIMENT CONTROL TO |
| | KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT |
| | PROPERTIES AND STORM DRAINS DURING CONSTRUCTION. YOU |
| | CAN JUST ADD SILT FENCE DETAIL AND HOW DRAINS ARE |
| | PROTECTED TO THE DRAINAGE PLAN. SOME ENGINEERING |
| | STANDARD DETAILS CAN BE USED FROM WPB WEBSITE-POLLUTION |
| | CONTROL. HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUB |
| | LIC-WORKS/FORMS,-PERMITS-APPLICATIONS |
| | |
| | 14) 107.3.5.3 FBC[AMENDED] PAVING AND DRAINAGE PLANS |
| | - PROVIDE CIVIL PLANS TO SHOW SLOPES, ELEVATIONS AND |
| | DRAINAGE AS IT RELATES TO PEDESTRIAN PATHWAYS AND |
| | ACCESS(FULL SET NOT REQUIRED) |
| | |
| | 15) 107.5.3 FBC[AMENDED] SEPARATE PERMIT REQUIRED FOR |
| | VIBRO COMPACTION. |
| | - GEOTECHNICAL REPORT (RECEIVED, VIBRO-COMPACTION PROBE |
| | LAYOUT, FOUNDATION PLAN, AND STORM WATER POLLUTION |
| | PREVENTION PLAN (REQUESTED) |
| | |
| | 16) 406.5.2 FBC(B)OPENINGS IN INTERIOR WALLS FOR OPEN |
| | PARKING. |
| | - PLEASE ADD OPENING PERCENTAGES FOR INTERIOR.WALLS OF |
| | OPEN GARAGE. SHEET LS-0.2 DOESN'T APPEAR TO HAVE |
| | OPENINGS ON INTERIOR WALL. |
| | |
| | 17) 1609.4.3 FBC[B] EXPOSURE CATEGORIES. AN EXPOSURE |
| | CATEGORY SHALL BE DETERMINED IN ACCORDANCE WITH THE |
| | FOLLOWING: EXPOSURE B. FOR BUILDINGS WITH A MEAN ROOF |
| | HEIGHT OF LESS THAN OR EQUAL TO 30 FEET, EXPOSURE B |
| | SHALL APPLY WHERE THE GROUND SURFACE ROUGHNESS, AS |
| | DEFINED BY SURFACE ROUGHNESS B, PREVAILS IN THE UPWIND |
| | DIRECTION FOR A DISTANCE OF AT LEAST 1,500 FEET. FOR |
| | BUILDINGS WITH A MEAN ROOF HEIGHT GREATER THAN 30 FEET, |
| | EXPOSURE B SHALL APPLY WHERE SURFACE ROUGHNESS B |
| | PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT |
| | LEAST 2,600 FEET OR 20 TIMES THE HEIGHT OF THE |
| | BUILDING, WHICHEVER IS GREATER. |
| | EXPOSURE C. EXPOSURE C SHALL APPLY FOR ALL CASES WHERE |
| | EXPOSURE B OR D DOES NOT APPLY. |
| | EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE GROUND |
| | SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D, |
| | PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT |
| | LEAST 5,000 FEET OR 20 TIMES THE HEIGHT OF THE |
| | BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL ALSO |
| | APPLY WHERE THE GROUND SURFACE ROUGHNESS IMMEDIATELY |
| | UPWIND OF THE SITE IS B OR C, AND THE SITE IS WITHIN A |
| | DISTANCE OF 600 FEET OR 20 TIMES THE BUILDING HEIGHT, |
| | WHICHEVER IS GREATER, FROM AN EXPOSURE D CONDITION AS |
| | DEFINED IN THE PREVIOUS SENTENCE. |
| | - IN REVIEWING LOCATION I WOULD PUT THIS LOCATION AT A |
| | CATEGORY C INSTEAD OF D. PLEASE REVIEW THIS WITH NEXT |
| | COMMENT ABOUT CATEGORY SELECTION AND PLEASE ADJUST IF |
| | APPLICABLE. PLEASE CONSIDER EXPOSURE C WITH CATEGORY |
| | III DESIGNATION OR PROVIDE JUSTIFICATION FOR THE |
| | CURRENT CATEGORY II SELCTION WITH D EXPOSURE. |
| | |
| | 18) 1604.5 FBC[B] RISK CATEGORY. EACH BUILDING AND |
| | STRUCTURE SHALL BE ASSIGNED A RISK CATEGORY IN |
| | ACCORDANCE WITH TABLE 1604.5. WHERE A REFERENCED |
| | STANDARD SPECIFIES AN OCCUPANCY CATEGORY, THE RISK |
| | CATEGORY SHALL NOT BE TAKEN AS LOWER THAN THE OCCUPANCY |
| | CATEGORY SPECIFIED THEREIN. WHERE A REFERENCED STANDARD |
| | SPECIFIES THAT THE ASSIGNMENT OF A RISK CATEGORY BE IN |
| | ACCORDANCE WITH ASCE 7, TABLE 1.5-1, TABLE 1604.5 SHALL |
| | BE USED IN LIEU OF ASCE 7, TABLE 1.5-1. 1604.5.1 |
| | MULTIPLE OCCUPANCIES. |
| | - TABLE 1604.5 FBC[B]. PLEASE REVIEW CRITERIA FOR |
| | CATEGORY II BEING SELECTED. CATEGORY III IS USED FOR |
| | BUILDINGS THAT REPRESENT A SUBSTAINTIAL HAZARD TO HUMAN |
| | LIFE. THIS BUILDING HAS HIGH OCCUPANT LOAD, OCCUPANTS |
| | UNDER CUSTODIAL CARE AND OCCUPANTS UNDER MEMORY CARE. |
| | |
| | 19)3202.2 FBC[B]ENCROACHMENTS ABOVE GRADE AND BELOW 8 |
| | FEET IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC |
| | RIGHT-OF-WAY ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN |
| | HEIGHT SHALL BE PROHIBITED EXCEPT AS PROVIDED FOR IN |
| | SECTIONS 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS |
| | SHALL NOT OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| | - CHECK DOOR FROM STAIR 3 APPEARS TO CROSS PROPERTY |
| | LINES. |
| | |
| | 20) 3002.4 FBC[B] ELEVATOR CAR TO ACCOMMODATE AMBULANCE |
| | STRETCHER. ANY BUILDING THAT IS MORE THAN THREE STORIES |
| | HIGH OR IN WHICH THE VERTICAL DISTANCE BETWEEN THE |
| | BOTTOM TERMINAL LANDING AND THE TOP TERMINAL LANDING |
| | EXCEEDS 25 FEET (7620 MM), MUST BE CONSTRUCTED TO |
| | CONTAIN AT LEAST ONE PASSENGER ELEVATOR THAT IS |
| | OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE DEPARTMENT |
| | EMERGENCY ACCESS TO ALL FLOORS. THE ELEVATOR CAR SHALL |
| | BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE AN |
| | AMBULANCE STRETCHER 24 INCHES BY 76 INCHES (610 MM BY |
| | 1950 MM) WITH NOT LESS THAN 5-INCH (127 MM) RADIUS |
| | CORNERS, IN THE HORIZONTAL, OPEN POSITION AND SHALL BE |
| | IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY |
| | MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL BE |
| | NOT LESS THAN 3 INCHES (76 MM) IN HEIGHT AND SHALL BE |
| | PLACED INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME. |
| | - INDICATE WHICH PASSENGER ELEVATOR WILL BE IDENTIFIED |
| | TO ACCOMMODATE STRETCHER. |
| | |
| | ASSEMBLIES: |
| | |
| | 21) PLEASE PROVIDE OR STATE WHERE TO FIND TESTED |
| | ASSEMBLIES FOR FIRE RATED SPECIFIED IN TABLE 601 FOR |
| | FLOORS AND OTHER RATED ASSEMBLIES AS REQUIRED FROM |
| | TABLE 601. |
| | |
| | SUBMITTALS: |
| | |
| | 22) 1014 FBC [B] GUARDS AND HANDRAILS. 1607.8 FBC [B] |
| | LOADS ON HANDRAILS AND GUARDRAILS. PROVIDE HANDRAIL AND |
| | GUARDRAIL ENGINEERING, OR INDICATE THAT YOU WOULD LIKE |
| | IT DEFERRED. |
| | |
| | 107.3.4.1 FBC[AMENDED] DEFERRAL OF ANY SUBMITTAL ITEMS |
| | SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL FOR |
| | REVIEW, AND THEN FORWARED TO THE BUILDING OFFICIAL |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE |
| | INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 107.3.4.1 FBC[AMENDED] IF ANY SPEC SHEETS OR PRODUCT |
| | APPROVALS ARE ADDED, PLEASE UPLOAD THEM AS MULTIPAGE |
| | FORMAT PDF IN SUPPORTING DOCUMENTS. |
| | |
| | 23) 806.3 FBC[B] COMBUSTIBLE DECORATIVE MATERIALS. IN |
| | OTHER THAN GROUP I-3, CURTAINS, DRAPERIES, FABRIC |
| | HANGINGS AND SIMILAR COMBUSTIBLE DECORATIVE MATERIALS |
| | SUSPENDED FROM WALLS OR CEILINGS SHALL COMPLY WITH |
| | SECTION 806.4 AND SHALL NOT EXCEED 10 PERCENT OF THE |
| | SPECIFIC WALL OR CEILING AREA TO WHICH SUCH MATERIALS |
| | ARE ATTACHED. FIXED OR MOVABLE WALLS AND PARTITIONS, |
| | PANELING, WALL PADS AND CRASH PADS APPLIED STRUCTURALLY |
| | OR FOR DECORATION, ACOUSTICAL CORRECTION, SURFACE |
| | INSULATION OR OTHER PURPOSES SHALL BE CONSIDERED |
| | INTERIOR FINISH SHALL COMPLY WITH SECTION 803 AND SHALL |
| | NOT BE CONSIDERED DECORATIVE MATERIALS OR FURNISHINGS. |
| | - (SEE 806.3 FOR EXCEPTIONS) |
| | |
| | 806.4 FBC[B] ACCEPTANCE CRITERIA AND REPORTS. WHERE |
| | REQUIRED TO EXHIBIT IMPROVED FIRE PERFORMANCE, |
| | CURTAINS, DRAPERIES, FABRIC HANGINGS AND SIMILAR |
| | COMBUSTIBLE DECORATIVE MATERIALS SUSPENDED FROM WALLS |
| | OR CEILINGS SHALL BE TESTED BY AN APPROVED AGENCY AND |
| | MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA OF TEST |
| | 1 OR 2, AS APPROPRIATE, OF NFPA 701, OR EXHIBIT A |
| | MAXIMUM HEAT RELEASE RATE OF 100 KW WHEN TESTED IN |
| | ACCORDANCE WITH NFPA 289, USING THE 20 KW IGNITION |
| | SOURCE. REPORTS OF TEST RESULTS SHALL BE PREPARED IN |
| | ACCORDANCE WITH THE TEST METHOD USED AND FURNISHED TO |
| | THE BUILDING OFFICIAL UPON REQUEST. |
| | -PROVIDE AS SUBMITTAL TO DEVELOPMENT SERVICES OFFICE |
| | |
| | 24) 1207.2 FBC[B] FLOORING SUBMITTAL. |
| | - TYPE OF CEILING ASSEMBLY INCLUDING THICKNESS OF |
| | CONCRETE AND IF THERE IS A SOUND RATED ASSEMBLY IN UNIT |
| | BELOW. |
| | |
| | 1207.2 FBC[B] PLEASE ADVISE ,VIA EMAIL, WHAT FLOORING |
| | AND UNDERLAYMENT ARE PROPOSED? IF THE UNDERLAYMENT |
| | PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST |
| | REPORTS ON FILE, THE FOLLOWING REPORTS WILL BE |
| | REQUIRED: |
| | 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND |
| | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND |
| | SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF |
| | NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E90. |
| | 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR |
| | BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR |
| | NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E492. |
| | 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND FLOOR |
| | COVERING MATERIALS SHALL COMPLY WITH SECTIONS 804.2 |
| | THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND |
| | COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL, |
| | LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING |
| | MATERIALS THAT ARE NOT COMPRISED OF FIBERS. |
| | |
| | TEMPORARY CONSTRUCTION: |
| | |
| | 25) 3104.1.1 FBC[B] APPLICATION. PEDESTRIAN WALKWAYS |
| | SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH |
| | SECTIONS 3104.2 THROUGH 3104.9. TUNNELS SHALL BE |
| | DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH SECTIONS |
| | 3104.2 AND 3104.10. |
| | - SEPARATE PERMIT NEEDED TEMP FENCING AND RIGHT OF WAY |
| | PERMIT FOR SIDEWALK CLOSURES. |
| | |
| | 26) 3306.1 FBC[B] PROTECTION REQUIRED. PEDESTRIANS |
| | SHALL BE PROTECTED DURING CONSTRUCTION, REMODELING AND |
| | DEMOLITION ACTIVITIES AS REQUIRED BY THIS CHAPTER AND |
| | TABLE 3306.1. SIGNS SHALL BE PROVIDED TO DIRECT |
| | PEDESTRIAN TRAFFIC. 3306.2 FBC[B] WALKWAYS. A WALKWAY |
| | SHALL BE PROVIDED FOR PEDESTRIAN TRAVEL IN FRONT OF |
| | EVERY CONSTRUCTION AND DEMOLITION SITE UNLESS THE |
| | APPLICABLE GOVERNING AUTHORITY AUTHORIZES THE SIDEWALK |
| | TO BE FENCED OR CLOSED. WALKWAYS SHALL BE OF SUFFICIENT |
| | WIDTH TO ACCOMMODATE THE PEDESTRIAN TRAFFIC, BUT IN NO |
| | CASE SHALL THEY BE LESS THAN 4 FEET (1219 MM) IN WIDTH. |
| | WALKWAYS SHALL BE PROVIDED WITH A DURABLE WALKING |
| | SURFACE. WALKWAYS SHALL BE ACCESSIBLE IN ACCORDANCE |
| | WITH CHAPTER 11 AND SHALL BE DESIGNED TO SUPPORT ALL |
| | IMPOSED LOADS AND IN NO CASE SHALL THE DESIGN LIVE LOAD |
| | BE LESS THAN 150 POUNDS PER SQUARE FOOT (PSF) |
| | |
| | 27) 3306.7 FBC[B] COVERED WALKWAYS. COVERED WALKWAYS |
| | SHALL HAVE A CLEAR HEIGHT OF NOT LESS THAN 8 FEET (2438 |
| | MM) AS MEASURED FROM THE FLOOR SURFACE TO THE CANOPY |
| | OVERHEAD. ADEQUATE LIGHTING SHALL BE PROVIDED AT ALL |
| | TIMES. COVERED WALKWAYS SHALL BE DESIGNED TO SUPPORT |
| | ALL IMPOSED LOADS. IN NO CASE SHALL THE DESIGN LIVE |
| | LOAD BE LESS THAN 150 PSF (7.2 KN/M2) FOR THE ENTIRE |
| | STRUCTURE. |
| | |
| | PROVISOS: |
| | |
| | A) AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED |
| | PRIOR TO C.O. |
| | B) DEFERRED SUBMITTALS - COMPONENT & CLADDING PRODUCT |
| | APPROVALS SUBMITTED TO PLAN REVIEW OFFICE. PRODUCT |
| | APPROVALS FOR LOUVERS AND EQUIPMENT STANDS. |
| | C) VEHICLE BARRIER SUBMITTAL TO PLAN REVIEW OFFICE |
| | D) ROOF ENGINEERING AND PRODUCT APPOVAL TO BE SUBMITTED |
| | WITH ROOF SUB-PERMIT APPLICATION. SEE ENERGY |
| | CALCULATIONS THAT CALL FOR HIGH ALBEDO ROOF. |
| | E) SEPARATE PERMITS REQUIRED FOR - GENERATOR, LIGHT |
| | POLES/SITE LIGHTING, FIRE ALARM, FIRE SPRINKLER, LOW |
| | VOLTAGE, ACCESS, LANDSCAPING, IRRIGATION, POOL, |
| | TEMPORARY FENCE AND RIGHT OF WAY PERMITS(ENGINEERING) |
| | F) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| | SAT-SUN |
| | - NO RESPONSE REQUIRED. THESE WILL BE ADDED TO THE |
| | PLANS AT FINAL STAMPING. |
| | |
| | NOTES: |
| | |
| | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F 8-5) TO |
| | DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected] |
| | |
| | |
| | |