| Date |
Text |
| 2020-02-03 09:36:48 | RESIDENTIAL (R2) ROOF TILE SUBMITTAL BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- CLEARLY SPECIFY THE SPECIFIC ROOF TILE FASTENING AS |
| | REQUIRED BY SEC. 107.2.1.1 CITY AMENDMENTS. |
| | ROOF TILE NOA 19-0814.01 SUBMITTED INDICATE ON PAGE 5 |
| | OF 9 THAT "YOU CAN USE ANY OF THE FASTENER TYPE WITH |
| | EXCEPTION OF 1-10D OR SCREW SHANK NAIL". THIS GENERAL |
| | SPECIFICATION IS NOT ACCEPTABLE BECAUSE MOST OF THE |
| | FASTENER SPECIFICATIONS SHOWN ON THIS PAGE DON'T |
| | MEET THE ATTACHMENT RESISTANCE BASED ON THE HEIGHT AND |
| | BUILDING EXPOSURE OF THIS BUILDING. DESIGNER OF RECORD |
| | TO SPECIFY FASTENER TYPE THAT WILL MEET THE REQUIRED |
| | ATTACHMENT RESISTANCE. |
| | |
| | 2- A) IF USING ROOF TILE ADHESIVE, THEN PROVIDE PRODUCT |
| | APPROVAL FOR ROOF TILE ADHESIVE LISTED ON THE ROOF TILE |
| | NOA. FAC 61G20.3001. |
| | |
| | B) CLEARLY MARK ADHESIVE PADDY SIZE ON THE ROOF TILE |
| | NOA AND ROOF TILE ADHESIVE NOA AS REQUIRED BY CITY |
| | POLICY FOR ALL ROOFING PERMITS TO VERIFY COMPLIANCE |
| | WITH THE DESIGN PRESSURES OF SEC R301.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |