| Plan Review Notes For Permit 20011193 |
| Permit Number |
20011193 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-01-31 14:50:21 | KITCHEN AND BATH REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE PROVIDE FLOORING UNDERLAYMENT ACOUSTICAL TEST | | | REPORT TO SHOW THE REQUIRED "IIC" AND "STC" MINIMUM AT | | | 50 OR HIGHER PER FBC 1207 | | | FBC 1207.2 WALLS, PARTITIONS AND FLOOR/CEILING | | | ASSEMBLIES SEPARATING DWELLING UNITS AND SLEEPING UNITS | | | FROM EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL | | | HAVE A SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR | | | NOT LESS THAN 45 IF FIELD TESTED, FOR AIR-BORNE NOISE | | | WHEN TESTED IN ACCORDANCE WITH ASTM E90. | | | FBC 1207.3 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING | | | UNITS AND SLEEPING UNITS OR BETWEEN A DWELLING UNIT OR | | | SLEEPING UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE | | | STRUCTURE SHALL HAVE AN IMPACT INSULATION CLASS RATING | | | OF NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD | | | TESTED, WHEN TESTED IN ACCORDANCE WITH ASTM E492. | | | |
|