| 2020-02-18 10:13:47 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SEPARATE PERMIT IS REQUIRED FOR BACKFLOW ASSEMBLIES |
| | PER WPB UTILITIES. PLACE NOTE ON PLAN |
| | |
| | 2. ALL PLUMBING WORK SHALL COMPLY WITH FBC PLUMBING 6TH |
| | EDITION 2017 PLEASE CORRECT NOTE #7 ON SHEET P101 UNDER |
| | GENERAL NOTES. |
| | |
| | 3. PROVIDE PIPING DETAIL WATER AND SANITARY FOR THE |
| | WATER FOUNTAIN SHOWING ALL SHUT VALVE P-TRAP AND VENT. |
| | PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 4. PROVIDE DETAIL FOR ELECTRICAL OUTLET PEDESTAL WITH |
| | HOSE BIB NOTE ON PLAN REFERENCE ELECTRICAL DRAWING I |
| | COULD NOT LOCATE ANY DETAILS. PER WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | |
| | 5. EACH HOSE BIB IS REQUIRED TO HAVE A VACUUM BREAKER |
| | AND SHUT OFF VALVE. PER FBC PL 608.15.4.2, 606.2(2) |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |