| Date |
Text |
| 2020-02-22 12:03:40 | PLAN REVIEW - ELECTRIC |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE A NEW PANEL SCHEDULE. INCLUDE ALL EXISTING |
| | AND NEW CIRCUTS. |
| | PROVIDE PANEL SCHEDULE INDLUDING ALL EXISTING AND ANY |
| | NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR |
| | THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE |
| | APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, |
| | 210.19, 210.20, 215.5, 408.4; WPB FBC 107.3.5; FBC RE |
| | E3706.2, E3902 |
| | |
| | 2. PROVIDE NEW LOAD CALC'S. |
| | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. |
| | NEC 220; FBC RE E3602.2 |
| | |
| | 3. IDENTIFY LOCATION OF SERVICE DISCONNECT AND PANEL |
| | BOARD ON PLAN. |
| | FBC R 3601.6.2 |
| | |
| | 4. PLAN SHALL BE SIGNED AND SEALED BY THE DESIGN |
| | PROFESSIONAL. |
| | 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH |
| | FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE |
| | NEXT REVIEW CYCLE REQUIRE REVIEW. |
| | 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. |
| | |
| | |
| | |
| | |