Plan Review Notes
Plan Review Notes For Permit 20011116
Permit Number 20011116
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-01-30 14:59:40A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
 1. INCLUDE DATA MATERIAL SHEETS FOR MATERIALS TO BE
 UTILIZED.
 2. WHAT IS THE SCOPE OF THE ADDITIONAL FIRE LINE TO BE
 ADDED TO AN EXISTING SYSTEM?
 3. IF APPLICABLE, DEMOLITION PLANS TO BE SBMITTED FOR
 MATERIALS TO BE REPLACED.
 4. PER NFPA 13 & 24, SECTION 10.8.1.1, ALL TEES, PLUGS,
 CAPS, BENDS, REDUCERS, VALVES, AND HYDRANT BRANCHES
 SHALL BE RESTRAINED AGAINST MOVEMENT BY USING THRUST
 BLOCKS OR RESTRAINED JOINT SYSTEMS.
 5. PER NFPA 13 & 24, SECTION 10.8.3.5, AFTER
 INSTALLATION, RODS, NUTS, BOLTS, WASHERS, CLAMPS, AND
 OTHER RESTRAINING DEVICES SHALL BE CLEANED AND
 THOROUGHLY COATED WITH A BITUMINOUS OR OTHER ACCEPTABLE
 CORROSION-RETARDING MATERIAL.
 6. PER NFPA 13 & 24, SECTION 10.10.2.1.3, UNDERGROUND
 PIPING, FROM THE WATER SUPPLY TO THE SYSTEM RISER, AND
 LEAD-IN CONNECTIONS TO THE SYSTEM RISER SHALL BE
 COMPLETELY FLUSHED BEFORE CONNECTION IS MADE TO
 DOWNSTREAM FIRE PROTECTION SYSTEM PIPING. THE MINIMUM
 RATE OF FLOW SHALL BE NOT LESS THAN THE FLOW NECESSARY
 TO PROVIDE A VELOCITY OF 10 FEET PER SECOND.
 7. PER NFPA 13 & 24, SECTION 10.10.1, THE INSTALLING
 CONTRACTOR SHALL BE RESPONSIBLE FOR THE COMPLETING AND
 SIGNING THE CONTRACTOR?S MATERIAL AND TEST
 CERTIFICATE(S) SHOWN IN FIGURE 10.10.1.
 8. PER NFPA 13 & 24, SECTION 10.10.2.2.1 ALL PIPING AND
 ATTACHED APPURTENANCES SUBJECTED TO SYSTEM WORKING
 PRESSURE SHALL BE HYDROSTATICALLY TESTED AT
 200 PSI OR 50 PSI IN EXCESS OF THE SYSTEM WORKING
 PRESSURE, WHICHEVER IS GREATER, AND SHALL MAINTAIN THAT
 PRESSURE +/-5 PSI FOR 2 HOURS
  
 S. THOMAS
 561-804-4728


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved