| 2020-02-13 08:47:23 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20011032 |
| | 2/13/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE AC PLAN IS INCOMPLETE. |
| | |
| | A) PROVIDE RETURN AIR FROM THE BEDROOMS- SECTION |
| | M1602.3 FBC RES. |
| | |
| | B) SHOW THE SUPPLY CFMS AT EACH DIFFUSER LOCATION- |
| | M1601.1 FBC RES. |
| | |
| | C) VERIFY 10' CLEARANCE FROM THE COOKING APPLIANCES TO |
| | THE MAIN RETURN IN THE KITCHEN- M1602.2 FBC RES |
| | |
| | D) NO ACCESS TO AIR HANDLER IN ATTIC SHOWN- M1305.1.3 |
| | FBC RES |
| | |
| | D) LOCATION OF CONDENSER AND INSTALLATION DETAIL NOT |
| | PROVIDED- M1305.1.4.1 & M1401.4 FBC RES. |
| | |
| | 2) NO ELECTRICAL PLAN SUBMITTED TO INDICATE CIRCUITRY, |
| | WIRE AND BREAKER SIZES- SECTION 107.2.1 WPB. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE |
| | RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. |
| | THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |