| Plan Review Notes For Permit 20011017 |
| Permit Number |
20011017 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-10 10:17:25 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) NOT SURE OF THE EXTENT OF THE SCOPE OF WORK FOR THIS | | | PERMIT "LOW VOLTAGE" ? LOW VOLTAGE FOR WHAT? DATA? | | | TELEPHONES? TVS? SECURITY? CAMERAS? | | | | | | 2) THIS IS A FULL SET OF PLANS OF YOUR OFFICE. PLEASE | | | SUBMIT A SET OF PLANS THAT SHOW WHAT YOU ARE SUBMITTING | | | FOR A PERMIT. HIGHLIGHTS, CLOUDS, WOULD HELP IN | | | IDENTIFYING YOUR SCOPE OF WORK. | | | | | | 3) YOU SHOW PANELBOARD SCHEDULES LISTING NEW OUTLETS | | | AND LIGHTS I THINK, THIS IS NOT CONSIDERED LOW VOLTAGE | | | WORK. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING | | | EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED | | | SHEETS. | | | | | | SINCERELY, | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | | | | |
|