2020-02-20 13:11:29BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 20010994
 REVIEWED: DECEMBER 10, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
  
 107.5.3 FBC[AMNENDED]
 PLEASE PROVIDE DOCUMENTATION FOR TWO ASSEMBLIES.
 30 MINUTES FOR FLOORING BETWEEN LEVELS AND 2 HOUR AT
 SHAFT.
  
 IT ISN'T CLEAR WHAT THE FIRE SPRAY IS BEING USED FOR
 AND IN THE ASSEMLY PROVIDED WHAT RATING IS BEING USED
 AND FOR WHAT AREA.
  
 PLEASE PROVIDE TESTED ASSEMBLIES WITH SELECTIONS MADE
 AND WHERE THE ASSEMBLY IS BEING UTILIZED.
 IF TESTED ASSEMBLIES DON'T FIT THE CONDITIONS OF
 CONSTRUCTION YOU CAN PROVIDE SIGNED/SEALED PRESCRIPTIVE
 DESIGNS.
  
  