| Notes |
| Date |
Text |
| 2020-02-20 13:11:29 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 20010994 | | | REVIEWED: DECEMBER 10, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC[B] = FBC BUILDING | | | | | | 107.5.3 FBC[AMNENDED] | | | PLEASE PROVIDE DOCUMENTATION FOR TWO ASSEMBLIES. | | | 30 MINUTES FOR FLOORING BETWEEN LEVELS AND 2 HOUR AT | | | SHAFT. | | | | | | IT ISN'T CLEAR WHAT THE FIRE SPRAY IS BEING USED FOR | | | AND IN THE ASSEMLY PROVIDED WHAT RATING IS BEING USED | | | AND FOR WHAT AREA. | | | | | | PLEASE PROVIDE TESTED ASSEMBLIES WITH SELECTIONS MADE | | | AND WHERE THE ASSEMBLY IS BEING UTILIZED. | | | IF TESTED ASSEMBLIES DON'T FIT THE CONDITIONS OF | | | CONSTRUCTION YOU CAN PROVIDE SIGNED/SEALED PRESCRIPTIVE | | | DESIGNS. | | | | | | |
|