| Plan Review Notes For Permit 20010971 |
| Permit Number |
20010971 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-04-28 12:12:13 | REVIEWED BY JERRY SMITH: | | | | | | PLUMBING COMMENTS: APPROVED W/PROVISO | | | PLUMBING PROVISO: PROVIDE DEFERRED SUBMITTAL; SEE BELOW | | | 1. THE INSINKERATOR HOT WATER DISPENSER AS SHOWN ON | | | SUPPLIED SPECIFICATION SHEET IS A TANK TYPE WATER | | | HEATER AND IF USED SHALL COMPLY WITH THE REQUIREMENTS | | | OF FBC PL SECTION 504 AND 607.3 INCLUDING BUT NOT | | | LIMITED TO A SAFETY RELIEF VALVE WITH DISCHARGE PIPING, | | | ANTI-SIPHON DEVICE, THERMAL EXPANSION CONTROL AND A PAN | | | WITH DRAIN. ADDITIONALLY, IT IS NOT REPRESENTATIVE OF | | | THE TANKLESS WATER HEATER SPECIFIED ON PLAN SHEET P0.1 | | | FIXTURE SCHEDULE. THEREFORE PER WPB FBC 107.2.1 AND WPB | | | FBC 107.3.4.1, PROVIDE AS A DEFERRED SUBMITTAL | | | MANUFACTURER?S SPECIFICATION AND INSTALLATION GUIDE FOR | | | THE SPECIFIED TANKLESS WATER HEATER OR REVISE PLUMBING | | | FIXTURE SCHEDULES TO REFLECT THE SUBMITTED INSINKERATOR | | | WITH A DETAIL SHOWING COMPLIANCE WITH FBC PL SECTION | | | 504 AND 607.3. DOCUMENT SHALL BE SUBMITTED, APPROVED | | | AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR | | | OWN RISK. | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-246-0882 MOBILE | | | | | | 20010978 505 S FLAGLER DR # 200 | | | SEE ALSO 20010989 AND 20010971 | | | |
|