| Date |
Text |
| 2020-03-11 08:53:54 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20010955 |
| | 3/11/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THIS IS THE SECOND REQUEST FOR THE HOOD EQUIPMENT |
| | SCHEDULE TO BE PLACED ON THE PLAN. PLEASE PROVIDE THE |
| | SCHEDULE. |
| | |
| | 2) THE HEAT GAIN MAKEUP AIR CALCULATION IS ACCEPTED |
| | HOWEVER THERE IS NO DOCUMENTATION SUBMITTED TO VERIFY |
| | THE ADDITIONAL 17,485 BTU LOAD IN THE KITCHEN SPACE |
| | DOES NOT EXCEED THE CAPACITY OF THE SYSTEM SERVING THE |
| | SPACE- SECTION 508.1.1 FBC M. |
| | |
| | 3) SECOND REQUEST FOR ACCURATE PROJECT VALUE- THE |
| | $10,000 VALUE FOR THE PROJECT APPEARS LOW. PERMIT VALUE |
| | FOR THE PROJECT SHALL INCLUDE LABOR, MATERIALS, |
| | EQUIPMENT, APPLIANCES, AND DESIGN FEES. PLEASE PROVIDE |
| | COPIES OF SIGNED CONTRACTS AND/OR INVOICES, ESTIMATES |
| | ETC. TO VERIFY TOTAL COSTS- SECTION 109.3 WPB. |
| | |
| | 4) NEW DOCUMENTS HAVE BEEN SUBMITTED WITH COPIED |
| | SIGNATURES AND SEALS BY THE ENGINEER OF RECORD. |
| | ORIGINAL SIGNATURES AND SEALS ARE REQUIRED- FL. STATUTE |
| | 471.025 AND SECTION 61G15-23.002 FLORIDA ADMINISTRATIVE |
| | CODE. ALL OCUMENTS AND SPECIFICATIONS SHALL BE |
| | SUBMITTED IN DUPLICATE- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE |
| | RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. |
| | THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |