| 2020-02-10 14:10:38 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20010955 |
| | 2/10/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE PLANS HAVE COPIED ENGINEER'S SEALS AND |
| | SIGNATURES. SUBMIT COMPLETE SETS OF SIGNED AND SEALED |
| | PLANS IN ACCORDANCE WITH FL. STATUTE 471.025 AND |
| | SECTION 61G15-23.002 FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 2) PLEASE PROVIDE EQUIPMENT SCHEDULES ON THE PLAN FOR |
| | THETYPE I AND TYPE II HOODS- SECTION 107.2.1 WPB. |
| | PLEASE REFER TO NOTE #1 ON SHEET M1.1 SPECIFYING A TYPE |
| | I AND TYPE II HOOD. THE ORIGNAL M1.1 APPROVED UNDER THE |
| | MASTER PERMIT #19061420 SHOWS A TYPE II HOOD OVER THE |
| | OVEN AND MAKEUP AIR DROPS TO BOTH THE TYPE I AND II |
| | HOODS |
| | |
| | 3) THE MAKEUP AIR TEMPERATURE FOR THE TYPE I HOOD SHALL |
| | BE IN COMPLIANCE WITH SECTION 508.1.1 FBC M. THE |
| | TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE AIR |
| | IN THE CONDITIONED SPACE SHALL NOT EXCEED 10 DEGREES F |
| | EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS OF THE |
| | MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE HVAC |
| | SYSTEM. |
| | |
| | 4) THE $10,000 VALUE FOR THE PROJECT APPEARS LOW. |
| | PERMIT VALUE FOR THE PROJECT SHALL INCLUDE LABOR, |
| | MATERIALS, EQUIPMENT, APPLIANCES, AND DESIGN FEES. |
| | PLEASE PROVIDE COPIES OF SIGNED CONTRACTS AND/OR |
| | INVOICES, ESTIMATES ETC. TO VERIFY TOTAL COSTS- SECTION |
| | 109.3 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE |
| | RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. |
| | THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |