2020-02-10 14:10:381ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010955
 2/10/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLANS HAVE COPIED ENGINEER'S SEALS AND
 SIGNATURES. SUBMIT COMPLETE SETS OF SIGNED AND SEALED
 PLANS IN ACCORDANCE WITH FL. STATUTE 471.025 AND
 SECTION 61G15-23.002 FLORIDA ADMINISTRATIVE CODE.
  
 2) PLEASE PROVIDE EQUIPMENT SCHEDULES ON THE PLAN FOR
 THETYPE I AND TYPE II HOODS- SECTION 107.2.1 WPB.
 PLEASE REFER TO NOTE #1 ON SHEET M1.1 SPECIFYING A TYPE
 I AND TYPE II HOOD. THE ORIGNAL M1.1 APPROVED UNDER THE
 MASTER PERMIT #19061420 SHOWS A TYPE II HOOD OVER THE
 OVEN AND MAKEUP AIR DROPS TO BOTH THE TYPE I AND II
 HOODS
  
 3) THE MAKEUP AIR TEMPERATURE FOR THE TYPE I HOOD SHALL
 BE IN COMPLIANCE WITH SECTION 508.1.1 FBC M. THE
 TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE AIR
 IN THE CONDITIONED SPACE SHALL NOT EXCEED 10 DEGREES F
 EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS OF THE
 MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE HVAC
 SYSTEM.
  
 4) THE $10,000 VALUE FOR THE PROJECT APPEARS LOW.
 PERMIT VALUE FOR THE PROJECT SHALL INCLUDE LABOR,
 MATERIALS, EQUIPMENT, APPLIANCES, AND DESIGN FEES.
 PLEASE PROVIDE COPIES OF SIGNED CONTRACTS AND/OR
 INVOICES, ESTIMATES ETC. TO VERIFY TOTAL COSTS- SECTION
 109.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE
 RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS.
 THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  