Plan Review Notes
Plan Review Notes For Permit 20010941
Permit Number 20010941
Review Stop B
Sequence Number 5
Notes
Date Text
2020-08-10 07:39:412017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20010941
 ADD: 5300 45TH ST.
 CONT: TBD / TO BE DETERMINED
 TEL: 856-6655 / CONTACT: NEYITA LEIVA
 E-MAIL: NEYITA@/PS01.NET
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 5TH REVIEW
 DATE: MON. AUGUST 10TH/ 2020
 ACTION: BUILDING PROVISOS
  
 1) BUILDING PROVISO: ONCE THE PROPOSED SITE IS
 ACQUIRED, THE DEVELOPER WILL CONTACT ADDRESSING TECH.
 CAROLINE PUELL TO NOTIFY ALL INTERESTED PARTIES
 (POLICE, FIRE, UTILITIES, PALM BEACH COUNTY ADDRESSING,
 U. S. MAIL ? OF THE CHANGE OF ADDRESS FOR THIS SITE.
  
 2) BUILDING PROVISO: A SEPARATE PERMIT IS REQUIRED FOR
 THE WALK IN COOLER/ FREEZER. SEPARATE REVIEW AND
 ASSOCIATED FEES.
  
 3) BUILDING PROVISO: REVISION REQUIRED. DRINKING
 FOUNTAINS. THE LAST TELEPHONE CONFERENCE CALL MEETING
 IT WAS DISCUSSED AND THE WRITTEN COMMENT RESPONSE
 INDICATES WING WALLS ARE TO BE ADDED FOR COMPLIANCE
 WITH PROTRUSION LIMITS. NOT FOUND ON THE UPDATED PLAN
 A2.0 AS NOTED. SHEET A2.1 THE ENLARGED RESTROOM DETAIL
 # 1 SHOWS THE HIGH/ LOW DRINKING FOUNTAINS AND REV.# 7
 BUT THERE IS NO ELEVATION VIEW TO INDICATE THE TYPE OF
 DRINKING FOUNTAIN AND COMPLIANCE WITH PROTRUDING
 OBJECTS AS FOUND ON SHEET A1.2. THE ISSUE, MAYBE WITH
 THE HIGH DRINKING FOUNTAIN IS A SKIRT MAYBE NEED TO BE
 ADDED TO THE BOTTOM OF THE ENCLOSURE FOR COMPLIANCE
 WITH PROTRUDING OBJECTS FROM THE WALL AND COMPLIANCE
 WITH THE 2017 FBC-ACCESSIBILITY CODE SECTION 307.2
 PROTRUSION LIMITS. OBJECTS WITH THE LEADING EDGE MORE
 THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE
 FINISH FLOOR OR GROUND SHALL PROTRUDE 4 INCHES MAXIMUM
 HORIZONTALLY INTO THE CIRCULATION PATH.
  
 4) BUILDING PROVISO: SHEET S201 SHOWS WELDED
 CONNECTIONS TO THE BAR JOIST, STIFFENERS, ADDITIONAL
 STEEL FRAMING AROUND NEW ROOF TOP OPENINGS. WELDED OR
 BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION. IN
 ACCORDANCE WITH THE AMERICAN WELDING SOCIETY.
 11A) 2017 FBC-B 2204.1 WELDING
 11B) 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 5A)BUILDING PROVISO/ DEFERRED SUBMITTALS CODE
 COMPLIANCE SHEET & A6.0: 13) COMPONENTS & CLADDING .
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (G) PRE-ENGINEERED A/C STANDS
  
 5B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5C) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT
 APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER'S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 5D) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  