Plan Review Notes
Plan Review Notes For Permit 20010941
Permit Number 20010941
Review Stop B
Sequence Number 3
Notes
Date Text
2020-05-28 10:38:512017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20010941
 ADD: 5300 45TH ST.
 CONT: TBD / TO BE DETERMINED
 TEL: 856-6655 / CONTACT: NEYITA LEIVA
 E-MAIL: NEYITA@/PS01.NET
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. MAY 28TH/ 2020
 ACTION: DENIED
  
 1) 3RD ROUND OF COMMENTS. THE PERMIT APPLICATION
 INDICATES THE ADDRESS AS 5300 45TH ST. AND WITHIN THE
 TITLEBLOCK (61G1-16.004 TITLE BLOCK. ARCHITECT). WHEN
 VIEWING THIS ADDRESS ON GOOGLE MAPS THERE APPEARS TO BE
 4 TENANTS A-D. THE DEMOLITION PLAN IT WOULD APPEAR THE
 EXISTING TIRE SHOP IS GOING TO REMAIN. HOW WILL THE
 TENANT ADDRESSES BE IDENTIFIED?
 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
 E-MAILED CAROLINE PUELL WEST PALM BEACH CITY ADDRESSING
 FOR TENANT ADDRESS FOR THIS PROJECT.
  
 2) COMPLIED.
  
 3A) 3RD ROUND OF COMMENTS. SHEET A0.1 CODE COMPLIANCE
 INFORMATION SHEET AND SHEET A1.5 THE EGRESS PLAN BOTH
 SHOW MERCANTILE AND THE SALES AREAS WITHIN THE TENANT
 SPACE TAKING THE OCCUPANT LOAD FACTOR @ 30 SQ. FEET PER
 OCCUPANT.
 PLEASE REVIEW THE 2017 FBC-B TABLE 1004.1.2. THE
 MERCANTILE OCCUPANT LOAD FACTOR IS TAKEN AT 60 SQ. FT.
 / OCCUPANT THIS WAS CHANGED IN THE 2017 FBC-B CODE.
  
 3B COMPLIED.
  
 4A) COMPLIED.
  
 4B) 3RD2ND ROUND OF COMMENTS. SHEET A1.3 THE
 ARCHITECTURAL SITE PLAN SHOWS THE ACCESS AISLE BETWEEN
 THE ACCESSIBLE PARKING SPACES BUT THE PLANS DO NOT
 INDICATE HOW THE TRANSITION (DROPPED CURB/ CURB CUT) IS
 MADE BETWEEN THE SIDEWALK AND ACCESS AISLE. 2017
 FBC-ACCESSIBILITY CODE SECTION 406 CURB RAMPS. THE
 ACCESSIBILITY DETAIL SHEET DOES NOT PROVIDE CODE
 COMPLIANCE IN ANY OF THE DETAILS, NEITHER.NOTE 45
 INDICATES EXISTING RAMP TO REMAIN. I SPOKE WITH THE
 DESIGNER OF RECORD THIS MORNING ABOUT THIS ISSUE AND
 COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY AND
 DISPROPORTIONATE COST.
 DISPROPORTIONATE COST. PLEASE REVIEW HOW YOU ARE TO
 MEET DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR
 THE DESIGNER OF RECORD ON THEIR LETTERHEAD ARE TO
 PROVIDE ON THEIR LETTERHEAD HOW THEY ARE GOING TO SPEND
 THE 20% DISPROPORTIONATE FUNDS IN THE ORDER LISTED IN
 SECTION 202.4.1 2017 FBC-ACCESSIBILITY CODE.
  
 4C-D) COMPLIED.
  
 5) 3RD ROUND OF COMMENTS. THE EGRESS SHEET A1.5 SHOWS A
 NEW (1) # 108 BACK STOCK ROOM COOLER, (2) 109 BEER CAVE
 & (3) COOLER VAUL. THEIR COMBINED / AGGREGATE FLOOR
 AREA IS GREATER THAN 400 SQUARE FEET. PLEASE BE AWARE
 OF SECTION 2603.4.1.3. THAT LIMITS THE AGGREGATE AREA
 OF WALK IN COOLERS TO 400 SQ. FT. IN NON-SPRINKLERED
 BUILDINGS. PLEASE BE AWARE THERE ARE OTHER CRITERIA
 THAT HAS TO BE PROVIDED AS WELL. A SEPARATE PERMIT
 REVIEW AND ASSOCIATED FEES WILL BE REQUIRED.
  
 6) COMPLIED.
  
 7) 3RD ROUND OF COMMENTS. SHEET A2.4, M1.1 & S102 ROOF
 PLANS ALL SHOW NEW ROOF TOP EQUIPMENT IN DIFFERENT
 AREAS OF THE ROOF. SHEET A2.4 SHOWS THE CONDENSER # 221
 WITHIN 10 FEET OF THE ROOF EDGE WITH NOTE 14 INDICATES
 PROVIDE A NON-PENETRATING FOLDABLE ROOF GUARD AS SHOWN
 INSTALL PER MANUFACTURERS RECOMENDATIONS.
 PROVIDE THE MANUFACTURERS TESTING FOR COMPLIANCE WITH
 THE 2017 FBC-B SECTIONS:
 1607.8.1
 1607.8.1.1
 1607.8.2
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B: 2017 FBC-B
 1013.6 MECHANICAL EQUIPMENT. GUARDS SHALL BE PROVIDED
 WHERE APPLIANCES, EQUIPMENT, FANS, ROOF HATCH OPENINGS
 OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE LOCATED
 WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF
 A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED
 MORE THAN 30 INCHES ABOVE THE FLOOR, ROOF OR GRADE
 BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT
 THE PASSAGE OF A SPHERE 21 INCHES IN DIAMETER. THE
 GUARD SHALL EXTEND NOT LESS THAN 30 INCHES BEYOND EACH
 END OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT.
  
 8-10) COMPLIED.
  
 11)BUILDING PROVISO: SHEET S201 SHOWS WELDED
 CONNECTIONS TO THE BAR JOIST, STIFFENERS, ADDITIONAL
 STEEL FRAMING AROUND NEW ROOF TOP OPENINGS. WELDED OR
 BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION. IN
 ACCORDANCE WITH THE AMERICAN WELDING SOCIETY.
 11A) 2017 FBC-B 2204.1 WELDING
 11B) 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 12) COMPLIED. NO ACTION REQUIRED. SHEET S001 PROVIDES
 THE WIND DESIGN CRITERIA AND ASSOCIATED PRESSURES,
 WHICH ARE CORRECT.
  
 13) BUILDING PROVISO/ DEFERRED SUBMITTALS. COMPONENTS &
 CLADDING . 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (G) PRE-ENGINEERED A/C STANDS
  
 14) BUILDING PROVISO/ W. P. B. 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 15) BUILDING PROVISO/ 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 16) BUILDING PROVISO/ IDENTIFY GLAZING/ MULLIONS. THE
 SUBMITTED PRODUCT APPROVALS THE ELEMENTS LISTED BELOW
 ARE NOT IDENTIFIED. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER'S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 17) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  