| 2020-05-28 10:38:51 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20010941 |
| | ADD: 5300 45TH ST. |
| | CONT: TBD / TO BE DETERMINED |
| | TEL: 856-6655 / CONTACT: NEYITA LEIVA |
| | E-MAIL: NEYITA@/PS01.NET |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: THURS. MAY 28TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) 3RD ROUND OF COMMENTS. THE PERMIT APPLICATION |
| | INDICATES THE ADDRESS AS 5300 45TH ST. AND WITHIN THE |
| | TITLEBLOCK (61G1-16.004 TITLE BLOCK. ARCHITECT). WHEN |
| | VIEWING THIS ADDRESS ON GOOGLE MAPS THERE APPEARS TO BE |
| | 4 TENANTS A-D. THE DEMOLITION PLAN IT WOULD APPEAR THE |
| | EXISTING TIRE SHOP IS GOING TO REMAIN. HOW WILL THE |
| | TENANT ADDRESSES BE IDENTIFIED? |
| | 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND |
| | EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED |
| | ADDRESS IDENTIFICATION. |
| | E-MAILED CAROLINE PUELL WEST PALM BEACH CITY ADDRESSING |
| | FOR TENANT ADDRESS FOR THIS PROJECT. |
| | |
| | 2) COMPLIED. |
| | |
| | 3A) 3RD ROUND OF COMMENTS. SHEET A0.1 CODE COMPLIANCE |
| | INFORMATION SHEET AND SHEET A1.5 THE EGRESS PLAN BOTH |
| | SHOW MERCANTILE AND THE SALES AREAS WITHIN THE TENANT |
| | SPACE TAKING THE OCCUPANT LOAD FACTOR @ 30 SQ. FEET PER |
| | OCCUPANT. |
| | PLEASE REVIEW THE 2017 FBC-B TABLE 1004.1.2. THE |
| | MERCANTILE OCCUPANT LOAD FACTOR IS TAKEN AT 60 SQ. FT. |
| | / OCCUPANT THIS WAS CHANGED IN THE 2017 FBC-B CODE. |
| | |
| | 3B COMPLIED. |
| | |
| | 4A) COMPLIED. |
| | |
| | 4B) 3RD2ND ROUND OF COMMENTS. SHEET A1.3 THE |
| | ARCHITECTURAL SITE PLAN SHOWS THE ACCESS AISLE BETWEEN |
| | THE ACCESSIBLE PARKING SPACES BUT THE PLANS DO NOT |
| | INDICATE HOW THE TRANSITION (DROPPED CURB/ CURB CUT) IS |
| | MADE BETWEEN THE SIDEWALK AND ACCESS AISLE. 2017 |
| | FBC-ACCESSIBILITY CODE SECTION 406 CURB RAMPS. THE |
| | ACCESSIBILITY DETAIL SHEET DOES NOT PROVIDE CODE |
| | COMPLIANCE IN ANY OF THE DETAILS, NEITHER.NOTE 45 |
| | INDICATES EXISTING RAMP TO REMAIN. I SPOKE WITH THE |
| | DESIGNER OF RECORD THIS MORNING ABOUT THIS ISSUE AND |
| | COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY AND |
| | DISPROPORTIONATE COST. |
| | DISPROPORTIONATE COST. PLEASE REVIEW HOW YOU ARE TO |
| | MEET DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR |
| | THE DESIGNER OF RECORD ON THEIR LETTERHEAD ARE TO |
| | PROVIDE ON THEIR LETTERHEAD HOW THEY ARE GOING TO SPEND |
| | THE 20% DISPROPORTIONATE FUNDS IN THE ORDER LISTED IN |
| | SECTION 202.4.1 2017 FBC-ACCESSIBILITY CODE. |
| | |
| | 4C-D) COMPLIED. |
| | |
| | 5) 3RD ROUND OF COMMENTS. THE EGRESS SHEET A1.5 SHOWS A |
| | NEW (1) # 108 BACK STOCK ROOM COOLER, (2) 109 BEER CAVE |
| | & (3) COOLER VAUL. THEIR COMBINED / AGGREGATE FLOOR |
| | AREA IS GREATER THAN 400 SQUARE FEET. PLEASE BE AWARE |
| | OF SECTION 2603.4.1.3. THAT LIMITS THE AGGREGATE AREA |
| | OF WALK IN COOLERS TO 400 SQ. FT. IN NON-SPRINKLERED |
| | BUILDINGS. PLEASE BE AWARE THERE ARE OTHER CRITERIA |
| | THAT HAS TO BE PROVIDED AS WELL. A SEPARATE PERMIT |
| | REVIEW AND ASSOCIATED FEES WILL BE REQUIRED. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) 3RD ROUND OF COMMENTS. SHEET A2.4, M1.1 & S102 ROOF |
| | PLANS ALL SHOW NEW ROOF TOP EQUIPMENT IN DIFFERENT |
| | AREAS OF THE ROOF. SHEET A2.4 SHOWS THE CONDENSER # 221 |
| | WITHIN 10 FEET OF THE ROOF EDGE WITH NOTE 14 INDICATES |
| | PROVIDE A NON-PENETRATING FOLDABLE ROOF GUARD AS SHOWN |
| | INSTALL PER MANUFACTURERS RECOMENDATIONS. |
| | PROVIDE THE MANUFACTURERS TESTING FOR COMPLIANCE WITH |
| | THE 2017 FBC-B SECTIONS: |
| | 1607.8.1 |
| | 1607.8.1.1 |
| | 1607.8.2 |
| | PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B: 2017 FBC-B |
| | 1013.6 MECHANICAL EQUIPMENT. GUARDS SHALL BE PROVIDED |
| | WHERE APPLIANCES, EQUIPMENT, FANS, ROOF HATCH OPENINGS |
| | OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE LOCATED |
| | WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF |
| | A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED |
| | MORE THAN 30 INCHES ABOVE THE FLOOR, ROOF OR GRADE |
| | BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT |
| | THE PASSAGE OF A SPHERE 21 INCHES IN DIAMETER. THE |
| | GUARD SHALL EXTEND NOT LESS THAN 30 INCHES BEYOND EACH |
| | END OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT. |
| | |
| | 8-10) COMPLIED. |
| | |
| | 11)BUILDING PROVISO: SHEET S201 SHOWS WELDED |
| | CONNECTIONS TO THE BAR JOIST, STIFFENERS, ADDITIONAL |
| | STEEL FRAMING AROUND NEW ROOF TOP OPENINGS. WELDED OR |
| | BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO |
| | PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR |
| | PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH |
| | THE REFERENCED STANDARDS AT TIME OF INSPECTION. IN |
| | ACCORDANCE WITH THE AMERICAN WELDING SOCIETY. |
| | 11A) 2017 FBC-B 2204.1 WELDING |
| | 11B) 2017 FBC-B 2204.2 BOLTING. |
| | IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS |
| | FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING |
| | INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU. |
| | |
| | 12) COMPLIED. NO ACTION REQUIRED. SHEET S001 PROVIDES |
| | THE WIND DESIGN CRITERIA AND ASSOCIATED PRESSURES, |
| | WHICH ARE CORRECT. |
| | |
| | 13) BUILDING PROVISO/ DEFERRED SUBMITTALS. COMPONENTS & |
| | CLADDING . 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 14) BUILDING PROVISO/ W. P. B. 107.3.4.1 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 15) BUILDING PROVISO/ 107.3.4.2 DEFERRED SUBMITTALS. |
| | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| | NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT |
| | ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 16) BUILDING PROVISO/ IDENTIFY GLAZING/ MULLIONS. THE |
| | SUBMITTED PRODUCT APPROVALS THE ELEMENTS LISTED BELOW |
| | ARE NOT IDENTIFIED. PLEASE IDENTIFY ON THE PRODUCT |
| | APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND |
| | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL |
| | PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING |
| | WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH |
| | IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURER'S INSTRUCTIONS. FASTENER SIZE AND SPACING |
| | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| | THE TESTS. |
| | |
| | 17) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |