Plan Review Notes
Plan Review Notes For Permit 20010941
Permit Number 20010941
Review Stop P
Sequence Number 2
Notes
Date Text
2020-05-13 08:21:46 
 2ND REVIEW FBC-2017 PLUMBING
 PERMIT #20010941
 5/13/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A2.1 & A.2.1.1: PROVIDE THE CLEAR WIDTH
 OPENINGS OF THE ACCESSIBLE TOILET COMPARTMENT ROOM
 DOORS- SECTION 404.2.3 FBC ACC. INDICATE THE DOORS WILL
 BE SELF-CLOSING- SECTION 604.8.1.7, AND SHOW THE
 MANEUVERING CLEARANCE AT THE MEN?S DOOR- SEE TABLE
 404.2.4.1 AND FIGURE C.
  
 2) PROVIDE THE CLEAR FLOOR SPACE APPROACH FOR THE
 ACCESSIBLE DRINKING FOUNTAIN, AND PROVIDE AN ELEVATION
 VIEW SHOWING THE KNEE AND TOE CLEARANCE, SPOUT OUTLET
 HEIGHTS, SPOUT LOCATIONS ETC. ? SECTION 602.1 FBC ACC.
 VERIFY THE FIXTURE WILL BE IN COMPLIANCE WITH SECTION
 307- PROTRUDING OBJECTS.
  
 3) P1.1: SHOW THE LOCATION OF THE MAIN SHUTOFF VALVE
 FOR THE WATER DISTRIBUTION SYSTEM- SECTION 606.1 FBC P.
  
 4) P1.1 & P1.3: WATER HAMMER ARRESTORS ARE REQUIRED FOR
 THE SUPPLY LINES TO THE ICE MAKER AND BEVERAGE
 DISPENSERS- SECTION 604.9 FBC P.
  
 5) THE PREVIOUS REVIEW COMMENT REQUESTING THE SIZE OF
 THE GREASE INTERCEPTOR, AND THE ROUTING OF THE GREASE
 LINE TO OTHER GREASE PRODUCING FIXTURES SUCH AS THE
 FLOOR SINKS AND MOP SINK WAS NOT ADDRESSED ON THE PLAN.
 PLEASE REVIEW SECTION 1003.3.1 FBC P AND SHOW
 COMPLIANCE. ADDITIONAL INFORMATION NEEDS TO BE PROVIDED
 CONCERNING THE TYPE, SIZE, AND LOCATION OF THE EXISTING
 INTERCEPTOR- SECTION 107.2.1 WPB.
 GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES REQUIRED. A GREASE INTERCEPTOR OR AUTOMATIC
 GREASE REMOVAL DEVICE SHALL BE REQUIRED TO RECEIVE THE
 DRAINAGE FROM FIXTURES AND EQUIPMENT WITH GREASE-LADEN
 WASTE LOCATED IN FOOD PREPARATION AREAS, SUCH AS IN
 RESTAURANTS, HOTEL KITCHENS, HOSPITALS, SCHOOL
 KITCHENS, BARS, FACTORY CAFETERIAS AND CLUBS. FIXTURES
 AND EQUIPMENT SHALL INCLUDE POT SINKS, PRERINSE SINKS;
 SOUP KETTLES OR SIMILAR DEVICES; WOK STATIONS; FLOOR
 DRAINS OR SINKS INTO WHICH KETTLES ARE DRAINED;
 AUTOMATIC HOOD WASH UNITS AND DISHWASHERS WITHOUT
 PRERINSE SINKS. GREASE INTERCEPTORS AND AUTOMATIC
 GREASE REMOVAL DEVICES SHALL RECEIVE WASTE ONLY FROM
 FIXTURES AND EQUIPMENT THAT ALLOW FATS, OILS OR GREASE
 TO BE DISCHARGED. WHERE LACK OF SPACE OR OTHER
 CONSTRAINTS PREVENT THE INSTALLATION OR REPLACEMENT OF
 A GREASE INTERCEPTOR, ONE OR MORE GREASE INTERCEPTORS
 SHALL BE PERMITTED TO BE INSTALLED ON OR ABOVE THE
 FLOOR AND UPSTREAM OF AN EXISTING GREASE INTERCEPTOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  