| 2020-05-03 15:55:32 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20010941 |
| | ADD: 5300 45TH ST. |
| | CONT: TBD / TO BE DETERMINED |
| | TEL: 856-6655 / CONTACT: NEYITA LEIVA |
| | E-MAIL: NEYITA@/PS01.NET |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON.4/27---SUN. MAY 03RD 2020 |
| | ACTION: DENIED |
| | |
| | NOTICE : 4X FEE / NOTICE!!!!! FLORIDA STATUTE |
| | 553.80(2)(B) |
| | |
| | |
| | |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | THRE |
| | |
| | IN THE 2ND SUBMISSION THERE WAS NO BUILDING RESONSE |
| | COMMENTS WITHIN THE FOLDER. ON 4/27 I E-MAILED THE |
| | CONTACT PERSON AT [email protected] THERE WERE NO |
| | BUILDING RESPONSE COMMENTS. TODAY 5/03 I FINISHED THE |
| | REVIEW WITH NO COMMENT RESPONSE SHEET WHERE THE COMMENT |
| | RESPONSES COULD BE FOUND. |
| | |
| | 1) 2ND ROUND OF COMMENTS. THE PERMIT APPLICATION |
| | INDICATES THE ADDRESS AS 5300 45TH ST. AND WITHIN THE |
| | TITLEBLOCK. WHEN VIEWING THIS ADDRESS ON GOOGLE MAPS |
| | THERE APPEARS TO BE 4 TENANTS A-D. THE DEMOLITION PLAN |
| | IT WOULD APPEAR THE EXISTING TIRE SHOP IS GOING TO |
| | REMAIN. HOW WILL THE TENANT ADDRESSES BE IDENTIFIED? |
| | 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND |
| | EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED |
| | ADDRESS IDENTIFICATION. |
| | |
| | 2) 2ND ROUND OF COMMENTS. THE DEMOLITION SHEET A1.7 |
| | SHOWS INTERIOR TENANT SEPARATION WALLS BEING REMOVED |
| | BUT THE NOTE TAG # 22 INDICATES THIS IS AN EXISTING |
| | GREASE TRAP TO REMAIN. 107.2.1.2 ADDITIONAL INFORMATION |
| | IS REQUIRED, IT APPEARS THERE IS A TYPO. AN EXISTING |
| | GREASE TRAP IS NOTED ON THE PLANS BUT NOT SHOWN. |
| | |
| | 3A) 2ND ROUND OF COMMENTS. SHEET A0.1 CODE COMPLIANCE |
| | INFORMATION SHEET AND SHEET A1.5 THE EGRESS PLAN BOTH |
| | SHOW MERCANTILE AND THE SALES AREAS WITHIN THE TENANT |
| | SPACE TAKING THE OCCUPANT LOAD FACTOR @ 30 SQ. FEET PER |
| | OCCUPANT. |
| | PLEASE REVIEW THE 2017 FBC-B TABLE 1004.1.2. THE |
| | MERCANTILE OCCUPANT LOAD FACTOR IS TAKEN AT 60 SQ. FT. |
| | / OCCUPANT THIS WAS CHANGED IN THE 2017 FBC-B CODE. |
| | |
| | 3B)2ND ROUND OF COMMENTS. WITH THE REVISED OCCUPANT |
| | LOAD OF 50 THE TENANT SPACE WOULD STILL REQUIRE 2 EXITS |
| | FOR THE PUBLIC, NOT THROUGH THE STOREROOM. |
| | |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| | EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | IS THE BACK EGRESS DOOR HAVE A LANDING THAT IS AT GRADE |
| | AND LEAD TO THE PUBLIC WAY? SEE THE 2017 FBC-B 1028.5 |
| | ACCESS TO THE PUBLIC WAY. |
| | |
| | 4A) 2ND ROUND OF COMMENTS. SHEET A1.3 THE ARCHITECTURAL |
| | SITE PLAN SHOWS 2 ACCESSIBLE PARKING SPACES 18 & 19 BUT |
| | THE PLANS DO NOT SHOW COMPLIANCE WITH THE CITY STANDARD |
| | OF DOUBLE LINED STRIPES AND COMPLIANCE WITH THE CITY OF |
| | WEST PALM BEACH ACCESSIBLE PARKING STANDARD. AN |
| | ACCESSIBLE PARKING SPACE AND ACCESS AISLE, PLEASE SEE |
| | THE 2017 FBC-ACCESSIBILITY CODE 502.3.3 MARKING. ACCESS |
| | AISLES SHALL BE MARKED SO AS TO DISCOURAGE PARKING IN |
| | THEM. THE ACCESS AISLE MUST BE STRIPED DIAGONALLY TO |
| | DESIGNATE IT AS A NO-PARKING ZONE. |
| | |
| | ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF |
| | MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY |
| | BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. |
| | BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE |
| | TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT |
| | THE AISLE BE CLEARLY MARKED. FLORIDA |
| | LAW, S.553.5041(5)(C)1., REQUIRES DIAGONAL STRIPING OF |
| | ACCESS AISLES. |
| | THE CITY OF W. P. B. MUNI CODE ARTICLE XV 94-485 |
| | PARKING PROVIDES A DOUBLE LINED DIMENSIONED PARKING |
| | STALL DETAIL. |
| | |
| | 4B) 2ND ROUND OF COMMENTS. SHEET A1.3 THE ARCHITECTURAL |
| | SITE PLAN SHOWS THE ACCESS AISLE BETWEEN THE ACCESSIBLE |
| | PARKING SPACES BUT THE PLANS DO NOT INDICATE HOW THE |
| | TRANSITION (DROPPED CURB/ CURB CUT) IS MADE BETWEEN THE |
| | SIDEWALK AND ACCESS AISLE. 2017 FBC-ACCESSIBILITY CODE |
| | SECTION 406 CURB RAMPS. THE ACCESSIBILITY DETAIL SHEET |
| | DOES NOT PROVIDE CODE COMPLIANCE IN ANY OF THE DETAILS, |
| | NEITHER. |
| | |
| | 4C) 2ND ROUND OF COMMENTS. SHEET A1.3 THE ARCHITECTURAL |
| | SITE PLAN SHOWS 2 PARKING SPACES IN THE FRONT OF THE |
| | BUILDING WITH AN ASTERISK SIGN AND 6 BEHIND THE |
| | BUILDING IN BOTH CASES KEYNOTE # 4 IS SHOWN AND THE |
| | COMMENT PARKING REFER TO THE CIVIL SHEETS. THEY ARE NOT |
| | PART OF THIS SET OF PLANS. ADDITIONAL INFORMATION IS |
| | REQUIRED. 107.2.1.2. |
| | |
| | 4D) 2ND ROUND OF COMMENTS. IN THE SITE PLAN THE CANOPY |
| | AND GAS PUMPS ARE SHOWN, ARE THE EXISTING PUMPS AND |
| | CANOPY GOING TO BE REUSED, OR ARE THEY BEING DEMOLISHED |
| | AND NEW PUMPS AND CANOPY GOING TO BE SUBMITTED UNDER |
| | SEPARATE PERMITS WITH ASSOCIATED REVIEW AND FEES. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 5) 2ND ROUND OF COMMENTS. THE EGRESS SHEET A1.5 SHOWS A |
| | NEW COOLER VAULT AND BEER CAVE. THEIR COMBINED / |
| | AGGREGATE FLOOR AREA IS 458 SQ. FT. EXTERIOR OF COOLER |
| | AND 423 SQ. FT. ON THE INTERIOR SIDE OF THE NEW COOLER |
| | AND BEER CAVE. PLEASE BE AWARE OF SECTION 2603.4.1.3. |
| | THAT LIMITS THE AGGREGATE AREA OF WALK IN COOLERS TO |
| | 400 SQ. FT. IN NON-SPRINKLERED BUILDINGS. PLEASE BE |
| | AWARE THERE ARE OTHER CRITERIA THAT HAS TO BE PROVIDED |
| | AS WELL. A SEPARATE PERMIT REVIEW AND ASSOCIATED FEES |
| | WILL BE REQUIRED. |
| | |
| | 6) 2ND ROUND OF COMMENTS. SHEET A2.1 THE ENLARGED |
| | RESTROOM DETAIL # 1 SHOWS THE HIGH/ LOW DRINKING |
| | FOUNTAINS BUT THERE IS NO ELEVATION VIEW TO INDICATE |
| | THE TYPE OF DRINKING FOUNTAIN AND COMPLIANCE WITH |
| | PROTRUDING OBJECTS AS FOUND ON SHEET A1.2. THE ISSUE, |
| | MAYBE WITH THE HIGH DRINKING FOUNTAIN IS A SKIRT MAYBE |
| | NEED TO BE ADDED TO THE BOTTOM OF THE ENCLOSURE FOR |
| | COMPLIANCE WITH PROTRUDING OBJECTS FROM THE WALL AND |
| | COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE SECTION |
| | 307.2 PROTRUSION LIMITS. OBJECTS WITH THE LEADING EDGE |
| | MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE |
| | THE FINISH FLOOR OR GROUND SHALL PROTRUDE 4 INCHES |
| | MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH. |
| | |
| | 7)2ND ROUND OF COMMENTS. SHEET A2.4, M1.1 & S102 ROOF |
| | PLANS ALL SHOW NEW ROOF TOP EQUIPMENT. SHEET M1.1 SHOWS |
| | THE BEER CAVE BACKSTOCK CONDENSER WITHIN 10 FEET OF THE |
| | ROOF EDGE. |
| | PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B: |
| | 2017 FBC-B 1013.6 MECHANICAL EQUIPMENT. GUARDS SHALL BE |
| | PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS, ROOF HATCH |
| | OPENINGS OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE |
| | LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN |
| | SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS |
| | LOCATED MORE THAN 30 INCHES ABOVE THE FLOOR, ROOF OR |
| | GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO |
| | PREVENT THE PASSAGE OF A SPHERE 21 INCHES IN DIAMETER. |
| | THE GUARD SHALL EXTEND NOT LESS THAN 30 INCHES BEYOND |
| | EACH END OF SUCH APPLIANCE, EQUIPMENT, FAN OR |
| | COMPONENT. |
| | |
| | 8) 2ND ROUND OF COMMENTS. THE PLANS ELEVATIONS WILL |
| | NEED TO SHOW HOW COMPLIANCE WITH SECTION 2017 FBC-M |
| | 306.5. EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED |
| | STRUCTURES. WHERE EQUIPMENT REQUIRING ACCESS OR |
| | APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR ROOF |
| | OF A BUILDING SUCH AS PERSONNEL WILL HAVE TO CLIMB |
| | HIGHER THAN 16 FEET ABOVE GRADE TO ACCESS SUCH |
| | EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR MEANS |
| | OF EGRESS SHALL BE PROVIDED. |
| | |
| | 9) 2ND ROUND OF COMMENTS. SHEETS A2.4 & M1.1 WILL NEED |
| | TO SHOW COMPLIANCE FOR ROOF TOP A/C CONDENSER STANDS |
| | WITH COMPLIANCE WHERE ROOFING MATERIALS EXTEND BENEATH |
| | THE UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A |
| | MINIMUM CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE |
| | 1510.10 OF THE 2017 FBC-B. |
| | |
| | 10) 2ND ROUND OF COMMENTS. ROOF TOP CONDENSING STANDS |
| | WILL NEED TO BE REVIEWED BY THE DESIGNER OF RECORD. |
| | PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS CALCULATING |
| | THE AREA (SIDE VIEW) OF THE ROOF TOP COMPRESSORS, |
| | CONFIGURATION ON STAND, THE MEAN ROOF HEIGHT OF THE |
| | STAND AND COMPRESSORS, WEIGHT, CIRCLED THE DESIGN |
| | PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT VERSES |
| | MOMENT FOR THE UNIT TO THE STAND AND THE STAND TO THE |
| | ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY THE |
| | DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. |
| | LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP |
| | EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, |
| | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| | 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | 11) 2ND REQUEST. THE STRUCTURAL ENGINEER HAS A THROUGH |
| | THE ROOF HVAC DETAIL FOR THE RE-ENFORCING OF THE CUT |
| | HOLE THROUGH THE ROOF. THE ARCHITECT NOW HAS A DETAIL |
| | ON SHEET A2.4 SHOWING A SIMILAR DETAIL BUT ANCHORING |
| | THE NEW ROOF TOP CURB ONLY THROUGH THE B METAL DECK AND |
| | NOT TRANSFERRING THE LOADS TO BE RESISTED TO THE BAR |
| | JOIST PART OF THE MWFRS (PART OF THE MAIN WIND FORCE |
| | RESISTING SYSTEM). WHO IS GOING TO WITHDRAW THEIR |
| | DETAIL? THE ONLY ISSUE I HAD IS THE BELOW IS A NOTICE |
| | FOR THE CONTRACTOR TO HAVE FIELD WELDED STEEL |
| | CONNECTIONS, TO HAVE A COPY OF THE WIELDERS |
| | CERTIFICATIONS ON HAND AT TIME OF INSPECTION. |
| | |
| | NOTICE ONLY.SHEET S201 SHOWS WELDED CONNECTIONS TO THE |
| | BAR JOIST, STIFFENERS, ADDITIONAL STEEL FRAMING AROUND |
| | NEW ROOF TOP OPENINGS. WELDED OR BOLTED CONNECTIONS. |
| | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE |
| | AMERICAN WELDING SOCIETY. |
| | 11A) 2017 FBC-B 2204.1 WELDING |
| | 11B) 2017 FBC-B 2204.2 BOLTING. |
| | IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS |
| | FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING |
| | INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU. |
| | |
| | 12) NO ACTION REQUIRED. SHEET S001 PROVIDES THE WIND |
| | DESIGN CRITERIA AND ASSOCIATED PRESSURES, WHICH ARE |
| | CORRECT. |
| | |
| | 13) COMPONENTS & CLADDING . 2017 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 14) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 15) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 16) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT |
| | APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED. |
| | PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| | SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| | TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| | OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER'S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 17) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, SFP & CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |