Plan Review Notes
Plan Review Notes For Permit 20010941
Permit Number 20010941
Review Stop B
Sequence Number 2
Notes
Date Text
2020-05-03 15:55:322017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20010941
 ADD: 5300 45TH ST.
 CONT: TBD / TO BE DETERMINED
 TEL: 856-6655 / CONTACT: NEYITA LEIVA
 E-MAIL: NEYITA@/PS01.NET
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON.4/27---SUN. MAY 03RD 2020
 ACTION: DENIED
  
 NOTICE : 4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B)
  
  
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 THRE
  
 IN THE 2ND SUBMISSION THERE WAS NO BUILDING RESONSE
 COMMENTS WITHIN THE FOLDER. ON 4/27 I E-MAILED THE
 CONTACT PERSON AT [email protected] THERE WERE NO
 BUILDING RESPONSE COMMENTS. TODAY 5/03 I FINISHED THE
 REVIEW WITH NO COMMENT RESPONSE SHEET WHERE THE COMMENT
 RESPONSES COULD BE FOUND.
  
 1) 2ND ROUND OF COMMENTS. THE PERMIT APPLICATION
 INDICATES THE ADDRESS AS 5300 45TH ST. AND WITHIN THE
 TITLEBLOCK. WHEN VIEWING THIS ADDRESS ON GOOGLE MAPS
 THERE APPEARS TO BE 4 TENANTS A-D. THE DEMOLITION PLAN
 IT WOULD APPEAR THE EXISTING TIRE SHOP IS GOING TO
 REMAIN. HOW WILL THE TENANT ADDRESSES BE IDENTIFIED?
 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 2) 2ND ROUND OF COMMENTS. THE DEMOLITION SHEET A1.7
 SHOWS INTERIOR TENANT SEPARATION WALLS BEING REMOVED
 BUT THE NOTE TAG # 22 INDICATES THIS IS AN EXISTING
 GREASE TRAP TO REMAIN. 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED, IT APPEARS THERE IS A TYPO. AN EXISTING
 GREASE TRAP IS NOTED ON THE PLANS BUT NOT SHOWN.
  
 3A) 2ND ROUND OF COMMENTS. SHEET A0.1 CODE COMPLIANCE
 INFORMATION SHEET AND SHEET A1.5 THE EGRESS PLAN BOTH
 SHOW MERCANTILE AND THE SALES AREAS WITHIN THE TENANT
 SPACE TAKING THE OCCUPANT LOAD FACTOR @ 30 SQ. FEET PER
 OCCUPANT.
 PLEASE REVIEW THE 2017 FBC-B TABLE 1004.1.2. THE
 MERCANTILE OCCUPANT LOAD FACTOR IS TAKEN AT 60 SQ. FT.
 / OCCUPANT THIS WAS CHANGED IN THE 2017 FBC-B CODE.
  
 3B)2ND ROUND OF COMMENTS. WITH THE REVISED OCCUPANT
 LOAD OF 50 THE TENANT SPACE WOULD STILL REQUIRE 2 EXITS
 FOR THE PUBLIC, NOT THROUGH THE STOREROOM.
  
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
 IS THE BACK EGRESS DOOR HAVE A LANDING THAT IS AT GRADE
 AND LEAD TO THE PUBLIC WAY? SEE THE 2017 FBC-B 1028.5
 ACCESS TO THE PUBLIC WAY.
  
 4A) 2ND ROUND OF COMMENTS. SHEET A1.3 THE ARCHITECTURAL
 SITE PLAN SHOWS 2 ACCESSIBLE PARKING SPACES 18 & 19 BUT
 THE PLANS DO NOT SHOW COMPLIANCE WITH THE CITY STANDARD
 OF DOUBLE LINED STRIPES AND COMPLIANCE WITH THE CITY OF
 WEST PALM BEACH ACCESSIBLE PARKING STANDARD. AN
 ACCESSIBLE PARKING SPACE AND ACCESS AISLE, PLEASE SEE
 THE 2017 FBC-ACCESSIBILITY CODE 502.3.3 MARKING. ACCESS
 AISLES SHALL BE MARKED SO AS TO DISCOURAGE PARKING IN
 THEM. THE ACCESS AISLE MUST BE STRIPED DIAGONALLY TO
 DESIGNATE IT AS A NO-PARKING ZONE.
  
 ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE
 TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT
 THE AISLE BE CLEARLY MARKED. FLORIDA
 LAW, S.553.5041(5)(C)1., REQUIRES DIAGONAL STRIPING OF
 ACCESS AISLES.
 THE CITY OF W. P. B. MUNI CODE ARTICLE XV 94-485
 PARKING PROVIDES A DOUBLE LINED DIMENSIONED PARKING
 STALL DETAIL.
  
 4B) 2ND ROUND OF COMMENTS. SHEET A1.3 THE ARCHITECTURAL
 SITE PLAN SHOWS THE ACCESS AISLE BETWEEN THE ACCESSIBLE
 PARKING SPACES BUT THE PLANS DO NOT INDICATE HOW THE
 TRANSITION (DROPPED CURB/ CURB CUT) IS MADE BETWEEN THE
 SIDEWALK AND ACCESS AISLE. 2017 FBC-ACCESSIBILITY CODE
 SECTION 406 CURB RAMPS. THE ACCESSIBILITY DETAIL SHEET
 DOES NOT PROVIDE CODE COMPLIANCE IN ANY OF THE DETAILS,
 NEITHER.
  
 4C) 2ND ROUND OF COMMENTS. SHEET A1.3 THE ARCHITECTURAL
 SITE PLAN SHOWS 2 PARKING SPACES IN THE FRONT OF THE
 BUILDING WITH AN ASTERISK SIGN AND 6 BEHIND THE
 BUILDING IN BOTH CASES KEYNOTE # 4 IS SHOWN AND THE
 COMMENT PARKING REFER TO THE CIVIL SHEETS. THEY ARE NOT
 PART OF THIS SET OF PLANS. ADDITIONAL INFORMATION IS
 REQUIRED. 107.2.1.2.
  
 4D) 2ND ROUND OF COMMENTS. IN THE SITE PLAN THE CANOPY
 AND GAS PUMPS ARE SHOWN, ARE THE EXISTING PUMPS AND
 CANOPY GOING TO BE REUSED, OR ARE THEY BEING DEMOLISHED
 AND NEW PUMPS AND CANOPY GOING TO BE SUBMITTED UNDER
 SEPARATE PERMITS WITH ASSOCIATED REVIEW AND FEES.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) 2ND ROUND OF COMMENTS. THE EGRESS SHEET A1.5 SHOWS A
 NEW COOLER VAULT AND BEER CAVE. THEIR COMBINED /
 AGGREGATE FLOOR AREA IS 458 SQ. FT. EXTERIOR OF COOLER
 AND 423 SQ. FT. ON THE INTERIOR SIDE OF THE NEW COOLER
 AND BEER CAVE. PLEASE BE AWARE OF SECTION 2603.4.1.3.
 THAT LIMITS THE AGGREGATE AREA OF WALK IN COOLERS TO
 400 SQ. FT. IN NON-SPRINKLERED BUILDINGS. PLEASE BE
 AWARE THERE ARE OTHER CRITERIA THAT HAS TO BE PROVIDED
 AS WELL. A SEPARATE PERMIT REVIEW AND ASSOCIATED FEES
 WILL BE REQUIRED.
  
 6) 2ND ROUND OF COMMENTS. SHEET A2.1 THE ENLARGED
 RESTROOM DETAIL # 1 SHOWS THE HIGH/ LOW DRINKING
 FOUNTAINS BUT THERE IS NO ELEVATION VIEW TO INDICATE
 THE TYPE OF DRINKING FOUNTAIN AND COMPLIANCE WITH
 PROTRUDING OBJECTS AS FOUND ON SHEET A1.2. THE ISSUE,
 MAYBE WITH THE HIGH DRINKING FOUNTAIN IS A SKIRT MAYBE
 NEED TO BE ADDED TO THE BOTTOM OF THE ENCLOSURE FOR
 COMPLIANCE WITH PROTRUDING OBJECTS FROM THE WALL AND
 COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE SECTION
 307.2 PROTRUSION LIMITS. OBJECTS WITH THE LEADING EDGE
 MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE
 THE FINISH FLOOR OR GROUND SHALL PROTRUDE 4 INCHES
 MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH.
  
 7)2ND ROUND OF COMMENTS. SHEET A2.4, M1.1 & S102 ROOF
 PLANS ALL SHOW NEW ROOF TOP EQUIPMENT. SHEET M1.1 SHOWS
 THE BEER CAVE BACKSTOCK CONDENSER WITHIN 10 FEET OF THE
 ROOF EDGE.
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B:
 2017 FBC-B 1013.6 MECHANICAL EQUIPMENT. GUARDS SHALL BE
 PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS, ROOF HATCH
 OPENINGS OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE
 LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN
 SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS
 LOCATED MORE THAN 30 INCHES ABOVE THE FLOOR, ROOF OR
 GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO
 PREVENT THE PASSAGE OF A SPHERE 21 INCHES IN DIAMETER.
 THE GUARD SHALL EXTEND NOT LESS THAN 30 INCHES BEYOND
 EACH END OF SUCH APPLIANCE, EQUIPMENT, FAN OR
 COMPONENT.
  
 8) 2ND ROUND OF COMMENTS. THE PLANS ELEVATIONS WILL
 NEED TO SHOW HOW COMPLIANCE WITH SECTION 2017 FBC-M
 306.5. EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES. WHERE EQUIPMENT REQUIRING ACCESS OR
 APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR ROOF
 OF A BUILDING SUCH AS PERSONNEL WILL HAVE TO CLIMB
 HIGHER THAN 16 FEET ABOVE GRADE TO ACCESS SUCH
 EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR MEANS
 OF EGRESS SHALL BE PROVIDED.
  
 9) 2ND ROUND OF COMMENTS. SHEETS A2.4 & M1.1 WILL NEED
 TO SHOW COMPLIANCE FOR ROOF TOP A/C CONDENSER STANDS
 WITH COMPLIANCE WHERE ROOFING MATERIALS EXTEND BENEATH
 THE UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A
 MINIMUM CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE
 1510.10 OF THE 2017 FBC-B.
  
 10) 2ND ROUND OF COMMENTS. ROOF TOP CONDENSING STANDS
 WILL NEED TO BE REVIEWED BY THE DESIGNER OF RECORD.
 PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS CALCULATING
 THE AREA (SIDE VIEW) OF THE ROOF TOP COMPRESSORS,
 CONFIGURATION ON STAND, THE MEAN ROOF HEIGHT OF THE
 STAND AND COMPRESSORS, WEIGHT, CIRCLED THE DESIGN
 PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT VERSES
 MOMENT FOR THE UNIT TO THE STAND AND THE STAND TO THE
 ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY THE
 DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT.
 LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 11) 2ND REQUEST. THE STRUCTURAL ENGINEER HAS A THROUGH
 THE ROOF HVAC DETAIL FOR THE RE-ENFORCING OF THE CUT
 HOLE THROUGH THE ROOF. THE ARCHITECT NOW HAS A DETAIL
 ON SHEET A2.4 SHOWING A SIMILAR DETAIL BUT ANCHORING
 THE NEW ROOF TOP CURB ONLY THROUGH THE B METAL DECK AND
 NOT TRANSFERRING THE LOADS TO BE RESISTED TO THE BAR
 JOIST PART OF THE MWFRS (PART OF THE MAIN WIND FORCE
 RESISTING SYSTEM). WHO IS GOING TO WITHDRAW THEIR
 DETAIL? THE ONLY ISSUE I HAD IS THE BELOW IS A NOTICE
 FOR THE CONTRACTOR TO HAVE FIELD WELDED STEEL
 CONNECTIONS, TO HAVE A COPY OF THE WIELDERS
 CERTIFICATIONS ON HAND AT TIME OF INSPECTION.
  
 NOTICE ONLY.SHEET S201 SHOWS WELDED CONNECTIONS TO THE
 BAR JOIST, STIFFENERS, ADDITIONAL STEEL FRAMING AROUND
 NEW ROOF TOP OPENINGS. WELDED OR BOLTED CONNECTIONS.
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 11A) 2017 FBC-B 2204.1 WELDING
 11B) 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 12) NO ACTION REQUIRED. SHEET S001 PROVIDES THE WIND
 DESIGN CRITERIA AND ASSOCIATED PRESSURES, WHICH ARE
 CORRECT.
  
 13) COMPONENTS & CLADDING . 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (G) PRE-ENGINEERED A/C STANDS
  
 14) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 15) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 16) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT
 APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER'S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 17) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  