| 2020-03-02 11:09:56 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20010941 |
| | 3/2/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW RTU'S IN ACCORDANCE WITH SECTION C403.2.1 FBC EC. |
| | |
| | 2) AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS ARE |
| | REQUIRED FOR THE O/A INTAKES- SECTION C403.2.4.3 FBC |
| | EC. PLEASE INDICATE HOW COMPLIANCE IS BEING MET. |
| | |
| | 3) SEPARATE PERMITS ARE REQUIRED FOR THE WALKIN |
| | BEVERAGE AND BEER COOLERS AND REFRIGERATION SYSTEMS. |
| | PLEASE PLACE A NOTE ON THE PLAN ACCORDINGLY- SECTION |
| | 107.2.1 WPB. |
| | |
| | 3) M1.0: SHOW LOCATIONS OF REQUIRED HEAT HOODS OR LOCAL |
| | EXHAUST VENTILATION SYSTEMS ABOVE OVENS AND COOKING |
| | APPLIANCES- SEE SECTION 507.3 FBC M. PLEASE NOTE THAT |
| | SEPARATE PERMITS ARE REQUIRED FOR HOODS AND FIRE |
| | SUPPRESSION SYSTEMS- SECTION 107.2.1 WPB. |
| | |
| | 4) M0.1 & M1.0: WHAT IS THE PURPOSE OF THE 3000 CFM O/A |
| | LOUVERS SHOWN IN THE WOMEN'S RESTROOM AND BACKROOM?- |
| | SECTION 107.2.1 WPB. PLEASE NOTE THEY ARE NOT INCLUDED |
| | IN THE AIR BALANCE CALCULATIONS, AND THE VENTILATION |
| | CALCS INDICATE 600 CFMS OF O/A REQUIRED. |
| | |
| | 5) M1.1: SHOW THE CLEARANCE DISTANCES FROM ALL |
| | SERVICEABLE ROOF MOUNTED MECHANICAL EQUIPMENT AND |
| | APPLIANCES TO DETERMINE IF GUARDS ARE REQUIRED- SEE |
| | SECTION 304.11 FBC M. |
| | |
| | 6) M1.1: PROVIDE COMPLETE WIND LOAD ENGINEERING FOR |
| | INSTALLATION OF ALL ROOF MOUNTED EQUIPMENT AND |
| | APPLIANCES- SECTION 301.15 FBC M |
| | |
| | 7) THE $200,000 JOB VALUE APPEARS LOW FOR THE SCOPE OF |
| | WORK. PLEASE NOTE THAT PERMIT VALUE IS BASED ON LABOR, |
| | MATERIALS, EQUIPMENT, APPLIANCES, FIXTURES, DESIGN |
| | FEES, AND SITE WORK- SECTION 109.3 WPB. PLEASE PROVIDE |
| | COPIES OF SIGNED CONTRCTS AND/OR ESTIMATES, INVOICES |
| | ETC. TO VERIFY VALUE. PLEASE NOTE THAT ALL ITEMS |
| | PURCHASED BY THE OWNERSHIP SHALL BE INCLUDED IN THE |
| | VALUE, PLEASE REMOVE THE VALUE OF THE REFRIGERATION AND |
| | EXHAUST HOOD SYSTEMS FROM THE TOTAL VALUE. THOSE ITMES |
| | WILL BE CHARGED UNDER SEPARATE PERMIT. |
| | |
| | 8) THE COMCHECK COMPLIANCE CERTIFICATE HAS BEEN SIGNED |
| | BY "MECH DESIGNER BRANDON ABBEY", HOWEVER THE |
| | MECHANICAL ENGINEER OF RECORD ON THE PLANS IS ERIC |
| | CROSS. THEREFORE THE CERTIFICATE SHALL BEAR THE |
| | SIGNATURE AND SEAL OF THE ENGINEER OF RECORD- FL. |
| | STATUTE 471.025 AND SECTION 61G15-23.005 FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |