2020-03-02 11:09:561ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010941
 3/2/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW RTU'S IN ACCORDANCE WITH SECTION C403.2.1 FBC EC.
  
 2) AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS ARE
 REQUIRED FOR THE O/A INTAKES- SECTION C403.2.4.3 FBC
 EC. PLEASE INDICATE HOW COMPLIANCE IS BEING MET.
  
 3) SEPARATE PERMITS ARE REQUIRED FOR THE WALKIN
 BEVERAGE AND BEER COOLERS AND REFRIGERATION SYSTEMS.
 PLEASE PLACE A NOTE ON THE PLAN ACCORDINGLY- SECTION
 107.2.1 WPB.
  
 3) M1.0: SHOW LOCATIONS OF REQUIRED HEAT HOODS OR LOCAL
 EXHAUST VENTILATION SYSTEMS ABOVE OVENS AND COOKING
 APPLIANCES- SEE SECTION 507.3 FBC M. PLEASE NOTE THAT
 SEPARATE PERMITS ARE REQUIRED FOR HOODS AND FIRE
 SUPPRESSION SYSTEMS- SECTION 107.2.1 WPB.
  
 4) M0.1 & M1.0: WHAT IS THE PURPOSE OF THE 3000 CFM O/A
 LOUVERS SHOWN IN THE WOMEN'S RESTROOM AND BACKROOM?-
 SECTION 107.2.1 WPB. PLEASE NOTE THEY ARE NOT INCLUDED
 IN THE AIR BALANCE CALCULATIONS, AND THE VENTILATION
 CALCS INDICATE 600 CFMS OF O/A REQUIRED.
  
 5) M1.1: SHOW THE CLEARANCE DISTANCES FROM ALL
 SERVICEABLE ROOF MOUNTED MECHANICAL EQUIPMENT AND
 APPLIANCES TO DETERMINE IF GUARDS ARE REQUIRED- SEE
 SECTION 304.11 FBC M.
  
 6) M1.1: PROVIDE COMPLETE WIND LOAD ENGINEERING FOR
 INSTALLATION OF ALL ROOF MOUNTED EQUIPMENT AND
 APPLIANCES- SECTION 301.15 FBC M
  
 7) THE $200,000 JOB VALUE APPEARS LOW FOR THE SCOPE OF
 WORK. PLEASE NOTE THAT PERMIT VALUE IS BASED ON LABOR,
 MATERIALS, EQUIPMENT, APPLIANCES, FIXTURES, DESIGN
 FEES, AND SITE WORK- SECTION 109.3 WPB. PLEASE PROVIDE
 COPIES OF SIGNED CONTRCTS AND/OR ESTIMATES, INVOICES
 ETC. TO VERIFY VALUE. PLEASE NOTE THAT ALL ITEMS
 PURCHASED BY THE OWNERSHIP SHALL BE INCLUDED IN THE
 VALUE, PLEASE REMOVE THE VALUE OF THE REFRIGERATION AND
 EXHAUST HOOD SYSTEMS FROM THE TOTAL VALUE. THOSE ITMES
 WILL BE CHARGED UNDER SEPARATE PERMIT.
  
 8) THE COMCHECK COMPLIANCE CERTIFICATE HAS BEEN SIGNED
 BY "MECH DESIGNER BRANDON ABBEY", HOWEVER THE
 MECHANICAL ENGINEER OF RECORD ON THE PLANS IS ERIC
 CROSS. THEREFORE THE CERTIFICATE SHALL BEAR THE
 SIGNATURE AND SEAL OF THE ENGINEER OF RECORD- FL.
 STATUTE 471.025 AND SECTION 61G15-23.005 FLORIDA
 ADMINISTRATIVE CODE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  